Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual: 7. SPECIFICATIONS, pages 210 to 214

Pages 210 to 214 of 387, from Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual

The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Toyopuc OUT-15 and Toyopuc OUT-18

Page 210

7.9

I/O Cable Specification This cable is used to connect the basic base, on which CPU is mounted, with additional base on which Selector Module is mounted. Type

THY-2770

THY-2771

Cable length

0.5m

1m

Weight

0.17 kg

0.24 kg

Items

*) Cable length is optionally available up to 3m maximum on special request (order).

7.10

I/O Branch Module Specification This module is used to connect two or more additional bases. Type

THU-2774

Items Outside dimension

93(W)×113(H)×18.5(D)mm

Installing dimension

77.6(W)×86(H)mm

Installing holes

06 bell-shaped hole (M5 screw used)

Weight

0.19 kg

*) This module is not needed when 8-slot bases (2 pcs.)are used.

7.11

I/O Conversion Cable Specification This cable is used to connect bus line to devices (MC256IV, etc.) where in PC2 bus is ready and to connect bus line to the I/O base of PC2. Type

THY-2772

THY-2773

Cable length

0.5m

1m

Weight

0.17kg

0.24kg

Items

*) The cable length is optionally available up to 3m maximum on special request (order).

7-91

Page 211

7.12 Selector base specification Selector base PC3J/PC2J is the integrated base combining conventional base and selector module and can be used additional base for each CPU module. (However cannot be used for CPU base.) Setting for rack No. and heading address setting for I/O module are executed. Selector base Type Item Actually installed I/O number Outer dimension (W×H×D mm) Mounting dimension (W×H mm)

THR-5643

THR-5644

THR-5645

8 Modules

6 Modules

4 Modules

370.5×160×7

299.5×160×7

228.5×160×7

350×145

280×145

210×145

Consuming current Weight

32mA(Typ.) 0.69kg

7-92

0.57kg

0.45kg

Page 212

7.12.1 Composition example of Selector Base Selector base has configuration shown in below:

I/O module Communication module Special module or blank

System configuration example

CPU module

POWER module

CPU base

CPU base

I/O cable POWER module

8 slots selector base POWER module

Additional base

6 slots selector base POWER module

4slots selector base

Note) Selector base cannot be used as CPU base. Use one of the bases for CPU from 8 slots base(2), 6 slots base, 4 slots base and 2 slots base.

7-93

Page 213

7.12.2 Name and function of each portion for Selector Base

(1) POWER lamp

POW ERR

(2) Error lamp (3) Rack No. select switch

S W 1

RACK

C

C

No. I/O H

N

N

ADRS

1

2

I/O L

(4) I/O address select switch

ADRS

5 V

(5) 5V power source terminal

0 V F G

(6) I/O bus connector

(7) Connector for power module

(8) Connector for I/O module

(1) POWER lamp Indicates 5V power source is supplied to base module. However the lamp turned off when interruption of power source is detected. (This lamp does not light because CPU detects I/O power down when power source of selector base is turned on after CPU started up. Turn on CPU’s reset switch to release this state) (2) Error lamp Lights when module error and I/O bus parity error that are amounted on applicable rack are generated. (3) Rack number selective switch Rack number is set within range 1 ~ E (Hexadecimal notation). rack number “E” is selected or duplicated rack No. is selected.

Error is generated when

(4) I/O address selective switch Determines heading of address number for rack I/O module within range 00 ~ 3F. Pay attention for giving overlapped I/O address to the rack belonging to other rack. Random setting of I/O address is not problem.

7-94

Page 214

Setting example of rack No. and I/O address

RACK No.

Rack No.=1

I/O H ADRS I/O L ADRS

I/O heading address X130 (or Y130) is set.

(1) 5V power source terminal This terminal is used for receiving terminal 5V from external source or supply 5V to outer load. Do not connect 5V and 0V terminals between racks having power source in their rack. This will be parallel operation of module, which causes breakage of module. Also do not connect terminal in reverse polarity or supply power other than 5V, which prevents module from breakage. (Recommending screw tightening torque: 1N·m) (2) I/O bus connector Serves to connect I/O bus cable. (3) Connector for power module This connector is used to connect POWER 1 module or POWER 2 module. (4) Connector for I/O module This connectors are used to connect with such module as I/O module, communication module or special module. Do not connect with CPU module or selector module, if connected the module could be broken.