Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual: 8. Link function
Pages 215 to 225 of 387, from Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual
The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Toyopuc OUT-15 and Toyopuc OUT-18
Page 215
8. Link function PC3JG CPU has SN-I/F, computer link, PC link and DLNK-M2 as standard. PC3JG CPU has capability to install as many as 14 sets of link (communication) module*1 other than built-in links. Refer to operation manual for each link module in PC3J/PC2 Series concerning each link module. Concerning built-in link refer to “10. Built-in link function”. *1
Maximum link number is total 16 links: 14 sets of link module and such 2 links as SN-I/F, computer link, PC link and DLNK (However “8 module/program” and “consuming memory capacity is less than 60K bit”). SN-I/F, computer and PC link require no consuming memory. Maximum 8 modules are required for a program (1 module is allocated for built-in link except SN-I/F.) Accordingly, maximum module number will become 8 modules when such operation mode requires only one program (PRG.1) as PC2 compatible mode. Also such installation that requires more than 60K bite of consuming memory more is incapable. Consuming memory capacity varies depending on each communication module.
8.1. Link parameter setting Set parameter for each program when link module is used installing on PC3JG.Please do not set the same link parameter to link No.1~8. Moreover, please do not set the same parameter through the other programs.
8
When link module is used installing on PC3JG *2, a few notices are required to set parameter for each program. Have a good understanding explanation in this chapter before operation start. *2 Handling of link module is the same with conventional PC2 Series when CPU in PC3JD Series is used in PC2 compatible mode. Except that link No. is handled as 1-1 ~ 1-8. Accordingly Link No. data in CPU in PC2 Series and CPU in PC3J Series become different as shown below when status information is stored in special register at the time communication abnormality. < Link No. data stocked in special register > CPU in PC2 Series: “01H” ~ ”08H” (expression in hexadecimal notation) CPU in PC3J Series: “11H” ~ ”18H” (expression in hexadecimal notation)
8-1
Page 216
8.2. Data link area When the link modules for data link are mounted in the PC3J, the data link areas available for use (usable devices) are as listed below. Data link areas (usable devices ) Link modules L,M
X,Y
R,D
EL,EM
EX,EY
GM
GX,GY
U
PC link PC1-I/F High speed remote I/O *1
HPC link Multiple communication I/F M-NET Pulse output DLNK-M DLNK-M2 AF1K MA1K ME-NET FL-NET PROFI-S2 Motion controller
-marked devices are the conventional usable devices and the device that can use the • The division mode of 3J is and and the device that can be the use it at the PC3JG division mode is , , and . • Where the PC3J CPU is in run under PC2 compatible Mode, the usable devices are limited to the -marked ones. Use of the -marked devices is not allowed. *1: For HPC link, Ver 2.20 and higher Ver can use some (EL, EM) of the extended relay areas.
Furthermore, availability of the data link areas differs depending on CPU operation mode. < Case of Data Area Separate Mode > Only data areas in a program wherein applicable link parameters are set up can be applied to the data link areas (devices). For example, where PC link host station is set up in Program 2 and parameters are set up so as to send L0000 ~ L001F to slave station 1, L0000 ~ L001F in Program 2 are sent to slave station 1. Under "Data Area Separate Mode", attention must be paid to the following items regarding the data link areas.
8-2
Page 217
• L, M, R. D are independent every program.
Set up each area to store the received data so as to avoid doubling in each link setup every program. Furthermore, set up each area so as to avoid doubling with those in the data registers intended to store output coil in the program and calculated result. • X, Y, EL, EM, EX, EY,GX, GY ,GM and U are common to each program. Set up each area to store the received data so as to avoid doubling in all the installed links. In addition, set up each area so as to avoid doubling with the data register to store the output coils of all programs and calculated result.
< Case of Data Area Single Mode or PC2 compatible Mode> Only data areas common to each program are applied to the data link areas. For example, where PC link host station is set up in Program 2 and link parameters are set up so as to send L0000 ~ L001F to slave station 1, L0000 ~ L001F in the basic area are sent to the slave station 1. In the case of Data Area Single Mode or PC2 compatible Mode, attention must be paid to the following regarding the data link areas. • All the data link areas are common to each program . Set up each area to store the received data so as to avoid doubling in all the installed links. In addition, set up each area so as to avoid doubling with the data register to store the output coils of all programs and calculated result.
8-3
Page 218
8.3. Commands Where link module to issue commands is mounted in the PC3J, some restrictions are given to handling of the commands as described below. 1. Where commands for data read, etc. are sent, the PC3J operation and response are different depending on CPU operation mode. < Case of Data Area Separate Mode > Where commands for data read, etc. are sent, the data areas in a program wherein link parameters are set up are applied to the PC3J operation and response. The data areas in other program (no link parameters set up therein) can not be applied. For example, where the computer link is set in Program 1 and V40 is read using one I/O point read command, the response data is V40 in Program 1. < Case of Data Area Single Mode or PC2 compatible Mode > Where the commands for data read, etc. are sent, the data areas common to each program are applied to the PC3J operation and response. For example, where the computer link is set in Program 2 and S200 is read using I/O register word read command, the response data is S200 in the basic area. 2. Extended relay and extended register can not be applied to the commands. 3. Commands intended for control of CPU operation such as scan halt, halt reset (release), etc. are applied to control of the system overall.
These can not be applied to individual control every program. 4. Some commands for program read, etc. are not available for the use. However, it is possible to issue the commands intended to support the PC3J CPU function by mounting a link module which contains therein the command function corresponding to the PC3J, whereby the restrictions mentioned above are eliminated. 8.3.1.
Computer Link commands Where any of the computer link modules in Ver 5.00 and lower Version is mounted in the PC3J, the PC3J operates and responds as described on next page when the computer link commands are sent. However, the PC3J operation and response are identical to Ver 5.00 and lower Version when it is operated in PC2 compatible Mode. Even if the computer link modules Version is before Ver 5.20, it cannot access “GM, GX, GY, EB" domain added to the PC3JG division mode.
• The computer link built in as a standard corresponds to the PC3J commands • Only the computer link bulit in PC3JG can access "GM,GX,GY,EB" domain.( Version 6 or more) PC2J PC/CMP LINK(THU-2755) PC2J PC/CMP LINK2(THU-5139) PC2J 2PORT LINK(THU-2927) 8-4
Page 219
No
Commands
PC3J operation and response
1
I/O 1 POINT READ
Response is sent to the data area in the
2
I/O REGISTER BYTE READ parameter-set program from the computer
3
I/O 1 POINT WRITE link. ( But unable to be applied to extended
4
I/O REGISTER BYTE WRITE
5
SEQUENCE PROGRAM READ relay and extended register .) *1 Unable to be applied .( NAK sent back)
6
SEQUENCE PROGRAM WRITE
7
I/O REGISTER WORD READ
Response is sent to the data area in the parameter-set program from the computer
8
I/O REGISTER WORD WRITE link. ( But unable to be applied to extended
9
SCAN HALT relay and extended register .) *1 Works for the system overall.
10
SCAN HALT RESET(RELEASE)
( not work individually every program.)
11
SCAN RESTART
12
CPU STATUS READ
Identical to conventional Ver.
13
FILL I/O REGISTER
Response is sent to the data area in the parameter-set program from the computer link. ( But unable to be applied to extended relay and extended register .) *1 Identical to conventional Ver.
14
WRITE MODE SETTING
15
WRITE MODE READ
16
RESET
Identical to conventional Ver.
17
DUMMY SCAN HALT
Unable to be applied .( NAK sent back)
18
DUMMY SCAN HALT RESET(RELEASE)
19
CPU ID READ
Identical to conventional Ver.
20
TIMER/ COUNTER SETUP VALUE & PRESENT VALUE READ
Response is sent back to the timer/counter of
21
TIMER/ COUNTER SETUP VALUE & PRESENT VALUE WRITE parameter-setup program from the computer
22
TIMER/COUNTER SETUP VALUE WRITE link.
23
TIMER /COUNTER PRESENT VALUE WRITE
24
PARAMETER READ
25
PARAMETER WRITE
26
EXECUTE RIGHT LIMIT SETTING
27
EXECUTE RIGHT LIMIT READ
28
CLOCK TIME READ
29
CLOCK TIME SETTING
30
FILL SEQUENCE PROGRAM
Unable to be applied .( NAK sent back)
31
I/O REGISTER MULTI-POINT READ,
Response is sent to the data area in the
Unable to be applied .( NAK sent back) Identical to conventional Ver. Identical to conventional Ver.
ADDRESS REGISTRATION parameter-set program from the computer 32
I/O REGISTER MULTI-POINT WORK READ link. ( But unable to be applied to extended relay and extended register .) *1 *1 Extended relay: EP, EK, EV, ET, EC, EX, EY, EM, GX,GY,GM Extended register: ES, EN, H, U, EB
8-5
Page 220
8.3.2. Ethernet commands Where any of the ETHERNET modules for Ver 1.10 and lower Versions is mounted in the PC3J, the PC3J operation and response are as described below when the ETHERNET commands are sent. However, the PC3J operation and response are identical to Ver 1.10 and lower Versions when it is in run under PC2 compatible Mode.
No
Commands
PC3J operation and response
1
SEQUENCE PROGRAM WORD READ
Unable to be applied .( NAK sent back)
2
SEQUENCE PROGRAM WORD WRITE
3
I/O REGISTER
WORD READ
4
I/O REGISTER
WORD WRITE
5
I/O REGISTER
BYTE READ
6
I/O REGISTER
BYTE WRITE
7
I/O REGISTER
BIT READ
8
I/O REGISTER
BIT WRITE
9
I/O REGISTER MULTI-POINT WORD READ
10
I/O REGISTER MULTI-POINT WORD WRITE
11
I/O REGISTER MULTI-POINT BYTE READ
12
I/O REGISTER MULTI-POINT BYTE WRITE
13
I/O REGISTER MULTI-POINT BIT READ
14
I/O REGISTER MULTI-POINT BIT WRITE
15
PARAMETER READ
16
PARAMETER WRITE
17
SCAN RESTART
18
SCAN HALT, HALT RESET
19
DUMMY SCAN HALT, HALT RESET
Unable to be applied .( NAK sent back)
20
CPU ID READ
Identical to conventional Ver.
21
EXECUTE RIGHT LIMIT STATUS DETAIL
Identical to conventional Ver.
22
EXECUTE RIGHT LIMIT SETTING
23
FILL
24
TIMER/ COUNTER SETUP VALUE & PRESENT VALUE READ
25
TIMER/ COUNTER SETUP VALUE & PRESENT VALUE WRITE
26
TIMER/COUNTER SETUP VALUE WRITE
27
TIMER /COUNTER PRESENT VALUE WRITE
28
CLOCK TIME READ
Response is sent back to the data areas in parameter setup program from ETHERNET .( but unable to be applied to extended relays and extended registers. )*1
Unable to be applied .( NAK sent back) Works for the system overall. ( not work individually every program.)
Unable to be applied .( NAK sent back) Response is sent back to the timer/counter of the parameter setup program from ETHERNET.
Identical to conventional Ver.
29 CLOCK TIME SETTING *1 Extended relay: EP, EK, EV, ET, EC, EX, EY, EM, GX, GY, GM Extended register: ES, EN, H, U, EB
8-6
Page 221
8.4. Special Relays and Special Registers The PC3J CPU stores the link module related error information and status information in special relays and special registers individually every each program. The areas and addresses to be stored in these special relays and special registers differ depending on CPU operation mode applied. (1) Data Separate Mode < Special relays > Store area
Address *2 V80 ~ V87
Name and content COMMUNICATION RESET LINK COMMAND USE OK FLAG
V90 ~ V9F PRG.1 VA0 ~ VBF
LINK PARAMETER ERROR IN COMMUNICATION WITH ALL STS / COMMUNICATION ERROR
V80 ~ V87
COMMUNICATION RESET LINK COMMAND USE OK FLAG
V90 ~ V9F PRG.2 VA0 ~ VBF
LINK PARAMETER ERROR IN COMMUNICATION WITH ALL STS / COMMUNICATION ERROR
V80 ~ V87
COMMUNICATION RESET LINK COMMAND USE OK FLAG
V90 ~ V9F PRG.3
LINK PARAMETER ERROR IN COMMUNICATION WITH ALL STS / COMMUNICATION ERROR
VA0 ~ VBF
8-7
Link 2-1
Link 2-8
Link 3-1 ~
LINK COMMAND ERROR FLAG
Link 1-8
~
LINK COMMAND ERROR FLAG
Link 1-1 ~
LINK COMMAND ERROR FLAG
Applicable link No. *1
Link 3-8
Page 222
< Special Registers > Name and content LINK MODULE CODE
S0AF S300 S3FF S0A8
PRG.2
S0AF S300 S3FF S0A8
PRG.3
S0AF S300 S3FF
Link 2-8 Link 3-1 Link 3-8 Link 3-1 ~
~
COMMUNICATION (LINK) MODULE STATUS INFORMATION
Link 2-8 Link 2-1
~
~
LINK MODULE CODE
Link 1-8 Link 2-1
~
~
COMMUNICATION (LINK) MODULE STATUS INFORMATION
Link 1-8 Link 1-1
~
~
LINK MODULE CODE
Link 1-1
~
~
COMMUNICATION (LINK) MODULE STATUS INFORMATION
Applicable link No.
~
PRG.1
Address *2 S0A8 ~
Store area
Link 3-8
*1 *-mark prefixed to Link No. (Link *-1 ~ *-8) means corresponding Program No.(PRG.1 ~ 3). *2 The name and content of each address are same as those in PC2 Series.
For the details, see " 7-2-5 Table of Special Relays" and "7-2-6 Table of Special Registers ".
8-8
Page 223
(2) Data Single Mode < Special Relays > Store area
Address *2 *3 V80 ~ V87
Name and content COMMUNICATION RESET LINK COMMAND USE OK FLAG
V90 ~ V9F Basic area
LINK PARAMETER ERROR IN COMMUNICATION WITH ALL STS /
VA0 ~ VBF
Link 1-1 ~
LINK COMMAND ERROR FLAG
Applicable link No. *1
Link 1-8
COMMUNICATION ERROR COMMUNICATION RESET
EV00 ~ EV07
LINK COMMAND USE OK FLAG
EV10 ~ EV1F
LINK PARAMETER ERROR IN COMMUNICATION WITH ALL STS / COMMUNICATION ERROR
EV20 ~ EV3F Extended area
Link 2-1 ~
LINK COMMAND ERROR FLAG
Link 2-8
COMMUNICATION RESET
EV40 ~ EV47
LINK COMMAND USE OK FLAG
EV50 ~ EV5F
Link 3-1
LINK PARAMETER ERROR IN COMMUNICATION WITH ALL STS / COMMUNICATION ERROR
Link 3-8
Address *2 *4 S0A8
Name and content
Applicable link No.
~
~
LINK COMMAND ERROR FLAG
LINK MODULE CODE
EV60 ~ EV7F
< Special Registers > Store area
SBF S300 S3FF ES000
Extended area
ES0FF ES100 ES1FF
Link 2-8 Link 3-1 ~
~
COMMUNICATION (LINK) MODULE STATUS INFORMATION
Link 1-8 Link 2-1 ~
~
COMMUNICATION (LINK) MODULE STATUS INFORMATION
Link 3-8 Link 1-1 ~
~
COMMUNICATION (LINK) MODULE STATUS INFORMATION
~
Basic area
Link 1-1
Link 3-8
*1 *-mark prefixed to each Link No.( Link *-1 ~ *8) means corresponding Program No. (PRG. 1 ~ 3). *2 The name and content of each address in the basic area are same as those of same address in PC2 Series. *3 The name and content of each address in the extended area are as follows. V80=EV00=EV40,V81=EV01=EV41...VBF=EV3F=EV7F *4 The name and content of each address in the extended area are as follows. S300=ES000=ES100,S301=ES001=ES101...S3FF=ES0FF=ES1FF
For the details, see " 7-2-5 Table of Special Relays" and "7-2-6 Table of Special Registers ".
8-9
Page 224
(3) PC2 compatible Mode < Special Relays > Address *2 V80 ~ V87 V90 ~ V9F
Name and content COMMUNICATION RESET LINK COMMAND USE OK FLAG LINK PARAMETER ERROR
VA0 ~ VBF
IN COMMUNICATION WITH ALL STS /
Link 1-1 ~
LINK COMMAND ERROR FLAG
Applicable link No. *1
Link 1-8
COMMUNICATION ERROR
< Special Registers > Address *2 S0A8
Name and content
~
LINK MODULE CODE
Applicable link No.
Link 1-1
S3FF
Link 1-8 Link 1-1 ~
~
COMMUNICATION (LINK) MODULE STATUS INFORMATION
~
S0AF S300
Link 1-8
*1 *-mark prefixed to Link No. (Link *-1 ~ *-8) means corresponding Program No.(PRG.1 ~ 3). *2 The name and content of each address are same as those in PC2 Series.
For the details, see " 7-2-5 Table of Special Relays" and "7-2-6 Table of Special Registers ".
8-10
Page 225
Link module code list module name code
PC link master
0102
PC1-I/F output
0102
PC link slave
0002
PC1-I/F input
0002
Computer link
0003
ME-NET master
0104
ME-NET slave
0004
SIO module
0005
Memory card I/F
0005
High speed remote I/O
0008
AS-I
0008
HPC link master
4009
SUB-CPU master
4009
HPC link slave
**09
SUB-CPU slave
**09
2-port M-NET
0002
Pulse output module
0100
DLNK-M
8008
DLNK-S2
8008
DLNK-M2
8208
Ethernet
8203
AF1K
800E
MA1K
810E
Motion controller
820E
FL-net(8KB)
8009
FL-net(16KB)
8109
FL-net(32KB)
8209
PROFI-S2
8309
** : Slave number ** : Slave number
8-11