Page 200

7.5.3 Identification and function of each I/O module component

I/O display LED

Terminal block lock lever

Terminal block

Terminal block lock lever

1

I/O display LED ----- 0 - F lamps display ON/OFF status of I/O. (OUT-1, OUT-11, OUT-12, OUT-15, and OUT-16 modules “FUSE BLOWN" of each is alarmed by other ALM lamp, in addition to

2 status display by 0 - F lamps. Terminal block lock lever -- To set and lock terminal block to the module. (2 levers altogether at top and bottom )

3

Terminal block ------- Detachable terminal block for I/O wiring

Detachment of terminal block • PC3J/2J I/O module is of such a construction as to permit simple detachment of I/O terminal block. In detaching and attaching, follow the operation sequence given below. How to remove the terminal block 1

Open outward both of top and bottom terminal block lock levers with them in fingers.

2

After complete open of the levers, draw frontward the terminal block. (If single-side lever only is opened, again draw frontward the terminal block, with its floated-up end in hand.)

7-81

Page 201

[ How to remove the terminal block 1 ]

[ How to remove the terminal block 2 ]

How to set the terminal block 1 Be sure to check that both of top and bottom terminal block lock levers are fully opened outward. 2

Push-in the terminal block, with its lower stage faced to the left, until it clicks. Be sure to check that the terminal block is perfectly locked at both top and bottom sides when the lever was push in.

[ Hot to set the terminal block 1 ]

7-82

Page 202

7.5.4

Fuse Specification Type name

Item

GP-50

GP-75

MP-63

HM-32

LM-32

Module used

OUT-1

OUT-12

OUT-15 OUT-16

OUT-11

OUT-18* OUT-19* OUT-28D* OUT-29D* OUT-38F* OUT-39F*

Profile Rated current *

Plug-shaped 5A

7.5A

Dip shaped micro fuse 6.3A

3.2A

The fuses used in OUT-18, OUT-19, OUT-28D, OUT-29D, OUT-38F, OUT-39F can not be replaced because of the soldered type.

Fuse blown detecting function: Output modules OUT-1, OUT-11, OUT-12, OUT-15, OUT-16 have fuse blown detecting function, which then enables to set up at the unit of each module whether fuse blown is detected or not as error. (OUT-3, OUT-18, OUT-19, OUT-28D, OUT-29D, OUT-38F, OUT-39F are not provided with this function.)

Error setup jumper

Cooling wheel

Fuse

Jumper status or

Setting

Contents

CPU status

ON

Fuse blown .. detected as error

RUN stop Error code 43

ALM LED .. ON

OFF

Fuse blown .. not detected as error

RUN goes on

ALM LED .. ON

7-83

Output module display

Page 203

7.6 Base Specification Five different bases of 2-slot base, 4-slot base, 6-slot base, and 8-slot base (2 bases) are available to install according to the number of I/O modules. These can be used with additional I/O rack. And, there is Selector Base. It has selector function. Bases for PC3J /2J application Type Items

THR-2766

Number of I/O modules installed Outer dimension (W×H×D mm) Installing dimension (W×Hmm)

THR-2872

8 modules

*

THR-2775

THR-2814

6 modules

4 modules

2 modules

406×130×7

424×130×7

335×130×7

264×130×7

193×130×7

391×86

409×86

320×86

249×86

178×86

Mounting hole Weight (kg)

THR-2813

06 bell-shaped hole (M5 screw used) 0.8

0.85

0.65

0.5

0.35

Precautions in use of PC2J: Only one I/O bus connector is used for 2-slot base, 4-slot base, 6-slot base and 8-slot base.

Hence, the number of additionally connectable bases is one set maximum. When connecting two or more additional bases, use two 8-slot bases (2 pieces of I/O bus connectors) or I/O Branch Module. Further, in this case the total length of I/O cables and length per cable shall be 5m max and 3m max respectively. (Note) The maximum quantity of additionally connectable bases is 3 sets maximum. When connecting MC256 IV, calculate the quantity of additional bases as one base for one MC256 IV.

7-84

Page 204

Base (5) 5V terminal block

(1) Module fixing hole

(2) Module connector

(4) I/O bus connector

(3) Base mounting hole

(1) Module fixing hole To fix the selector module, I/O module, power module, etc. (2) Module connector To connect the power module to the power unit, the selector module, high-speed remote SAT Station module to CPU/SEL, and I/O, communication and special modules to 0 - 7 respectively. (3) Base mounting hole Used to mount the base. (4) I/O bus connector To connect I/O cable. (5) 5V terminal block (5V, 0V, FG) DC5V and FG terminal block

7-85

Page 205

7.7 Power Module Specification There are power supply module, AC input power source unit (POWER 1) and DC input power source unit (POWER 2). The POWER 1 can work on input voltage ranging from AC85 to 264V. The POWER 2 can work on input voltage ranging from DC18 to 264V. Power module specification Type

THV-2747

THV-2748

POWER1

POWER2

Input voltage

AC85 ~ 264V

DC18 ~ 32V

Input frequency

47 ~ 66Hz

-

38W max, 80VA max

40VA max

Max 20A (subject to AC100V input) 40A (subject to AC200V input)

Max 5A

Items Name

Power consumption Rush current Rated output current

DC5V

4A over current protection

DC5V

5.25A min

Over-voltage protection Efficiency

5.75 ~ 7.00V 65%typ

Outside dimension Weight

70%typ 35(W)×130(H)×110(D) mm

0.33kg

7-86

0.34kg

Page 206

Power module

(1) Lower cover

(2) Terminal block

(1) Lower cover (2) Terminal block POWER 1 is the terminal block to input AC85 - 264V and output to RUN relays. POWER 2 is the terminal block to input DC18 - 32V and output to RUN relays. "RUN relay" output contact will open and close synchronizing with the CPU-RUN signal. CPU at running: output contact is closed CPU at not running: output contact is opened But the output to RUN relays is only effective in the rack (CPU rack) wherein CPU module is installed. (No output is effective in the additional I/O rack.) note:Please use the diode for the serge killer when you use the inductive load with DC.

7-87

Page 207

7.8 Selector Module Specification This selector module is used when using additional base other than the basic base on which CPU is mounted.

This module enables to set up Rack No. and head address of

I/O Module addresses to be allocated.

When Selector Base is used, this module isn't used. Type

THU-2765

Items Function

Enable to set up Rack No. and I/O address

Consumption current

31mA

Outside dimension

35(W)×130(H) ×110(D)mm

Weight

0.16kg

7-88

Page 208

Selector module This is needed when I/O rack for additional installation is used.

(1) POWER lamp

(2) ERROR lamp

(3) RACK NO. selector switch

(4) I/O ADDRESS selector switch

(5) Upper cover

(1) POWER lamp Showing that 5V power supply is ready in the base, but turning off when instantaneous interruption of the power is detected.

(When power throw-in is made at the additional

I/O rack side later than the CPU rack, the CPU detect hence, this lamp does not turn ON.

I/O power interruption and,

For resetting it, turn on CPU RESET switch.

(2) ERROR lamp This lamp turns ON against error of the I/O module, which is installed on applicable rack, and parity error of I/O bus. (3) RACK NO. selector switch This switch is to select Rack No. in the range of 1 - E (hexadecimal). Selection of Rack No. "F" or Rack No. doubling would result in error. (4) I/O ADDRESS selector switch This switch intended to decide the head address of the rack selects the addresses in the range of 00 - 3F (hexadecimal). (5) Upper cover

7-89

Page 209

Rack No. setup and head address setup Where additional I/O racks are installed, rack No. and head address must both be set up using RACK NO. selector switch and I/O ADDRESS selector switch in the selector module.

Further, with PC3JNF and PC3JNM, CPU Rack No.= 0 and head address =

X000 (Y000) are fixed. (1)

Rack No. Rack No. is selected from the range of 0 to E. (But actual selection range of additional I/O rack No.is 1 to E because of fixed CPU rack No.0 for PC3JNF and PC3JNM) Rack No. has no relation with I/O cable connection order. discriminate each rack.

(2)

Rack No. is intended to

Where two or more racks exist, avoid double setup.

Rack head address PC3 enables to set up the head address individually for each rack. Set up it by upper two digits of the head address of each rack and I/O ADDRESS selector switch. Further, in setting up, be careful to avoid overlapping of other rack to I/O address.

Skip setup of I/O address is trouble free. [EX.] Rack No.=2 head address = X130 (or Y130)

Rack RACK NO.

I/O HIGH ADDRESS I/O LOW ADDRESS Note) Switch OFF the power source before switch setting up. Related self-diagnosis For the details of the following items, refer to “Self-Diagnosis." • Use of I/O Rack F • I/O Rack No. overlap • Overlap of I/O Rack No. (3)

I/O Address I/O addresses in each base are allocated according to the number of allocation points which were setup on PARAMETER in the order from left slot (slot 0), based on the head address as a reference.

7-90