The text of a manual · part 23 of 44
Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual: 7. SPECIFICATIONS, pages 190 to 199
Pages 190 to 199 of 387, from Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual
The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Toyopuc OUT-15 and Toyopuc OUT-18
Page 190
(2) OUT-3 Module (THK-2931) Title
Independent contact relay output module
Specification
OUT-3
Number of circuits
8 points *1
Insulation method
Relay insulation
Rated switching voltage
DC24V 2A (Resistance load)
DC5V 10mA
Maximum switching voltage
DC30V AC264V
Response time
OFF→ON
8ms Max (at DC 24V)
ON →OFF
15ms Max (at DC 24V)
2EH)
2A/COM
Rated switching current AC240V 2A(cosφ=1) Minimum switching load
(Identification Code:
Electric:
Resistance load 200,000 cycles min Induced load Mechanic: 20,000,000 cycles min
Relay life Maximum switching frequency
At ON:
1 sec min
At OFF:
1 sec min
Surge killer
None
Internal current consumption (5V)
356mA (TYP. All points ON) (11 + 43n) mA
Common system
1 point/COM (Inter common insulation)
Status indication
LED ON at switch ON
Weight
0.31kg
External Connection and Internal Circuit Block Diagram
Relay
1
Internal circuit
2
L
~
AC100V to CPU n: On Number of points
Terminal
No.
Signal name
1
OUT00A
3
OUT01A
5
OUT02A
7
OUT03A
9
OUT04A
11 OUT05A 15
L
13 OUT06A 15 OUT07A
16
~
AC100V
17
NC
19
NC
Terminal
No.
Signal name
2
OUT00B
4
OUT01B
6
OUT02B
8
OUT03B
10 OUT04B 12 OUT05B 14 OUT06B 16 OUT07B 18
NC
*1: OUT-3 Module's real I/O points is 8 points. However, PC3JG CPU permits allocation of I/O address 16 points.
At this time Lower 8 points of address becomes the real I/O.
Therefore, do not use upper 8 points. 7-71
Page 191
(3) OUT-4 Module (THK-5040) Title
TRIAC (Triode AC) Output Module
Specification
OUT-4
Number of circuits
8 points *1
Insulation method
Photo coupler insulation
Rated load voltage
AC240V 50/60Hz
Maximum load voltage
AC265V
Maximum load current
1A/Point, 4A/COM
Minimum load voltage/current
AC15V 10mA
Maximum rush current
80A
(Identification Code:
1DH)
Leak current at OFF 1.5mA Max Max voltage drop at ON 1.5V Max Response time
OFF→ON
150µs
ON→OFF
1/2 cycle + 1ms
Internal current consumption (5V)
174mA (TYP. All points ON) (11 + 20.3n) mA
Surge killer
CR Absorber (0.01µF + 47Ω)
Fuse rating
5A
Fuse blown display
With (ALM LED ON against fuse blown)
Common method
8 points-1 common
Status indication
LED ON at switch ON
Weight
0.29kg
External Connection and Internal Circuit Block Diagram
TRIAC
1
Internal circuit
8 FUSE to CPU DC5 Fuse blown detection
17 n: On Number of points
Terminal
No.
Signal name
1
OUT00
3
OUT02
5
OUT04
L
7
OUT06
~
9
NC
AC200V
11
NC
13
NC
15
NC
17
COM
19
NC
L
Terminal
No.
Signal name
2
OUT01
4
OUT03
6
OUT05
8
OUT07
10
NC
12
NC
14
NC
16
NC
18
NC
*1: OUT-3 Module's real I/O points is 8 points. However, PC3JG CPU permits allocation of I/O address 16 points.
At this time Lower 8 points of address becomes the real I/O.
Therefore, do not use upper 8 points. note:Please use the diode for the serge killer when you use the inductive load with DC. 7-72
Page 192
(4) OUT-11 Module (THK-2795) Title
TRIAC (Triode AC) Output Module
Specification
OUT-11
Number of circuits
16 points
Insulation method
Photo coupler insulation
Rated load voltage
AC100V/115V 50/60Hz
Maximum load voltage
AC132V
Maximum load current
0.5A/Point 2A/COM
Minimum load voltage·Current
AC15V 10mA
Maximum rush current
60A
(Identification Code:
1EH)
Leak current at OFF 15mA Max Max voltage drop at ON 15V Max Response time
OFF→ON
150µs
ON→OFF
1/2 cycle + 1ms
Internal current consumption (5V)
336mA (TYP. All points ON) (11 + 20.3n) mA n: On Number of points
Surge killer
CR Absorber (0.01µF + 47Ω)
Fuse rating
3.2A/COM
Fuse blown display
With (ERR LED ON against fuse blown)*1
Common method
8 points-1 common (Inter common insulation) (note:It is 16 points 1 common to suit the CE marking.)
Status indication
LED ON at switch ON
Weight
0.32kg
External Connection and Internal Circuit Block Diagram
TRIAC
1
Internal circuit
8 FUSE
17 to CPU 9 16 19
Terminal
No.
Signal name
1
OUT00
3
OUT02
5
OUT04
~
7
OUT06
AC100V
9
OUT08
11
OUT0A
13
OUT0C
15
OUT0E
17
COM1
19
COM2
L L
L L
~ AC100V
Terminal
No.
Signal name
2
OUT01
4
OUT03
6
OUT05
8
OUT07
10
OUT09
12
OUT0B
14
OUT0D
16
OUT0F
18
NC
(note:Please use a short bar for terminal COM1-2 connection of the terminal block attachment to suit the CE marking.) *1 Modules produced before January 1996, the "ERR" is not printed on the LED cover.
7-73
Page 193
(5) OUT-12 Module (THK-2752) Title
Contact Output Module
Specification
OUT-12
Number of circuits
16 points
Insulation method
Relay insulation
Rated switching voltage
DC24V 2A (Resistance load)
Rated switching current AC240V 2A(cosφ=1) Minimum switching load
DC5V 10mA
Maximum switching voltage
DC30V AC264V
Response time
5A/COM
(Identification Code:
2FH)
(note:It is rated switching voltage DC24V,AC120V to suit the CE marking.)
(note:It is DC30V or AC132V to suit the CE marking.)
OFF→ON
13ms Max (at DC 24V)
ON→OFF
13ms Max (at DC 24V) Electric:
Resistance load 200,000 min Induced load Mechanic: 20,000,000 min
Relay life Maximum switching frequency
At ON:
Surge killer
None
Internal current consumption (5V)
380mA (TYP. All points ON) (11 + 23.1n) mA
Fuse rating
7.5A/COM
Fuse blown display
With (ALM LED ON against fuse blown)
Common method
8 point-1 common (Inter common insulation) (note:It is 16 points 1 common to suit the CE marking.)
Status indication
LED ON at switch ON
Weight
0.3kg
1 sec min
At OFF:
1 sec min
External Connection and Internal Circuit Block Diagram
Relay
1
Internal circuit
8 FUSE
To CPU
17
L L
~
AC100V
DC5 9 Fuse blown detection
16 FUSE
19
L L
~
AC100V n: On Number of points
Terminal
No.
Signal name
1
OUT00
3
OUT02
5
OUT04
7
OUT06
9
OUT08
11
OUT0A
13
OUT0C
15
OUT0E
17
COM1
19
COM2
Terminal
No.
Signal name
2
OUT01
4
OUT03
6
OUT05
8
OUT07
10
OUT09
12
OUT0B
14
OUT0D
16
OUT0F
18
NC
(note: It is rated switching voltage DC24V,AC120V and maximum switching voltage DC30V,AC132V to suit the CE marking. Moreover, please use a short bar for terminal COM1-2 connection of the terminal block attachment.) (note2 : Please use the diode for the serge killer when you use the inductive load with DC. 7-74
Page 194
(6) OUT-15 Module (THK-2790) Title
Power MOS FET Output (-) COM
Specification
OUT-15
Number of circuits
16 points
Insulation method
Photo coupler insulation
Rated load voltage
DC5V/12V/24V
Operating load voltage range
DC4.75~30V
Maximum load current
1A/Point (2A/2 Points)
Leak current at OFF
0.1mA Max
Max voltage drop at ON
0.3V Max, 0.17V (TYP.) 1A/point 2A/at 2 poins
Response OFF→ON time ON→OFF
2mS Max
14H)
4A/COM
6mS Max
Internal current consumption (5V)
310mA Max (All points ON) (11 + 18.4n) mA
Surge killer
Silicon surge absorber
Fuse rating
6.3A/COM
Fuse blown display with (ALM LED ON against fuse blown)
Common method
8 points, 1 common (Inter common insulation)
Status indication
LED ON at switch ON
Weight
0.26kg
External Connection and Internal Circuit Block Diagram
Photo vol Coupler
FET
Internal circuit
To CPU
(Identification Code:
1 8 FUSE
Terminal
No.
Signal name
1
OUT00
3
OUT02
5
OUT04
7
OUT06
9
OUT08
L
11
OUT0A
L
13
OUT0C
15
OUT0E
17
COM1
19
COM2
L L
17 DC5/12/24V
DC5V
9 Fuse blown detection
16 FUSE
19 DC5/12/24V
1 2 17
7-75 n: On Number of points
L
Terminal
No.
Signal name
2
OUT01
4
OUT03
6
OUT05
8
OUT07
10
OUT09
12
OUT0B
14
OUT0D
16
OUT0F
18
NC
For 2A/2-point output, turn ON/OFF 2 points simultaneously
Page 195
(7) OUT-16 Module (THK-2791) Title
Power MOS FET Output (+) COM
Specification
OUT-16
(Identification Code:
Number of circuits
16 points
Insulation method
Photo coupler insulation
Rated load voltage
DC5V/12V/24V
Operating load voltage range
DC4.75~30V
Maximum load current
1A/Point (2A/2 Points)
Leak current at OFF
0.1mA Max
Max voltage drop at ON
0.3V Max, 0.17V (TYP.) 1A/point 2A/at 2 Points
Response OFF→ON time ON→OFF
2mS Max 6mS Max
Internal current consumption
310mA Max (All points ON) (11 + 18.4n) mA
Surge killer
Silicon surge absorber
Fuse rating
6.3A/COM
Fuse blown display
With (ALM LED ON against fuse blown)
Common method
8 points, 1 common (Inter common insulation)
Status indication
LED ON at switch ON
Weight
0.26kg
4A/COM
External Connection and Internal Circuit Block Diagram
Photo vol Coupler
1
Internal circuit
8 FUSE
No.
Signal name
1
OUT00
3
OUT02
5
OUT04
7
OUT06
9
OUT08
L
11
OUT0A
L
13
OUT0C
15
OUT0E
17
COM1
19
COM2
L L
DC5/12/24V
DC5V
9 Fuse blown detection
16 FUSE
19 DC5/12/24V
1 2 17
7-76 n: On Number of points
Terminal
17
FET to CPU
15H)
L
Terminal
No.
Signal name
2
OUT01
4
OUT03
6
OUT05
8
OUT07
10
OUT09
12
OUT0B
14
OUT0D
16
OUT0F
18
NC
For 2A/2-point output, turn ON/OFF 2 points simultaneously
Page 196
(8) OUT-18 Module (THK-2753) Title
Transistor Output Module (-) COM
Specification
OUT-18
(Identification Code:
Number of circuits
16 points
Insulation method
Photo coupler insulation
Rated load voltage
DC12V/24V
Operating load voltage range
DC10~30V
Maximum load current
0.5A/Point
Leak current at OFF
0.1mA Max
Max voltage drop at ON
1.5V Max
Response OFF→ON time ON→OFF
1ms Max 1ms Max
Internal current consumption
136mA Max (All points ON time) (11+7.8n) mA
Surge killer
By Zener diode contained in the transistor (Zener voltage 60±10V)
Fuse rating
3.2A/COM
Fuse blown display
None
Common method
8 points, 1 common (Inter-common insulation)
Status indication
LED ON at switch ON
Weight
0.23kg
2A/COM
1 Internal circuit
Terminal
L
17 DC24
Transistor 9
L
(This fuse is soldered to the printed circuit board.)
7-77
3
OUT02
5
OUT04
7
OUT06
9
OUT08
15 OUT0E
DC24 element may be unable to protect the elements.
OUT00
13 OUT0C
19
*1: This fuse is to protect printed circuit board from burning.
1
11 OUT0A
L
16
Termi-
Signal nal Signal No. name No. name
L
8 FUSE to CPU n: On Number of points
*1
External Connection and Internal Circuit Block Diagram
Photo coupler
16H)
17
COM1
19
COM2
2
OUT01
4
OUT03
6
OUT05
8
OUT07
10 OUT09 12 OUT0B 14 OUT0D 16 OUT0F 18
NC
When short-circuited, this fuse
Page 197
(9) OUT-19 Module (THK-2754) Title
Transistor Output Module (+) COM
Specification
OUT-19
(Identification Code : 17H)
Number of circuits
16 points
Insulation method
Photo coupler insulation
Rated load voltage
DC12V/24V
Operating load voltage range
DC10~30V
Maximum load current
0.5A/Point
Leak current at OFF
0.1mA Max
Max voltage drop at ON
1.5V Max
Response OFF→ON time ON→OFF
1ms Max 1ms Max
Internal current consumption
136mA Max (All points ON time) (11+7.8n) mA
Surge killer
By Zener diode contained in the transistor (Zener voltage 60±10V)
Fuse rating
3.2A/COM
Fuse blown display
None
Common method
8 points, 1 common (Inter-common insulation)
Status indication
LED ON at switch ON
Weight
0.23kg
2A/COM
*1
External Connection and Internal Circuit Block Diagram
Terminal
Internal circuit to CPU
L
8 FUSE
L
17 DC24V
Transistor 9
L
3
OUT02
5
OUT04
7
OUT06
9
OUT08
15 OUT0E
DC24V
*1: This fuse is to protect printed circuit board from burning.
7-78
OUT00
13 OUT0C
19
(This fuse is soldered to printed circuit board.)
1
11 OUT0A
L
16 element may be unable to protect the elements.
Termi-
Signal nal Signal No. name No. name
1
Photo coupler n: On Number of points
17
COM1
19
COM2
2
OUT01
4
OUT03
6
OUT05
8
OUT07
10 OUT09 12 OUT0B 14 OUT0D 16 OUT0F 18
NC
When short-circuited, this fuse
Page 198
(10)
OUT-28D Module (THK-2870) Title
Transistor Output Module (-) COM
Specification
OUT-28D
(Identification Code:
Number of circuits
32 points
Insulation method
Photo coupler insulation
Rated load voltage
DC12V/24V
Operating load voltage range
DC10~30V
Maximum load current
0.2A/point 2A/COM
Leak current at OFF
0.1mA Max
Max voltage drop at ON
1.5V Max, 0.8V (TYP.) 0.2A
Response OFF→ON time ON→OFF
1ms Max
Internal current consumption (DC5V)
210mA Max (All points ON)
voltage External power supply Current
DC12/24V(DC10~30V)
Surge killer
C-E .. by Zener diode
Fuse rating
3.2A/COM *1
Fuse blown display
None
Common method
16 points, 1 common (Inter-common insulation)
Status indication
LED ON at switch ON (16 points display switching)
External connecting method
37-Pin D-sub connector, 1 piece
Weight
0.20kg
1ms Max
38mA (Typ. DC24V, per 1 PWR)
PWR1
A0
L ~
Internal circuit
AF
L
COM1
Photo coupler
FUSE
DC24V PWR2
B
L
BF
~ L
COM2
Connector pins configuration
External Connection and Internal Circuit Block Diagram to CPU
03H)
A0 A2 A4 A6 A8 AA AC AE
1
20
COM1
PWR1
B0 B2 B4 B6 B8 BA BC BE
B1 B3 B5 B7 B9 BB BD BF
COM2
DC24V
*1: This fuse is to protect printed circuit board from burning. may be unable to protect the elements.
NC
A1 A3 A5 A7 A9 AB AD AF
19
37
PWR2
When short-circuited, this fuse
(This fuse is soldered to the printed circuit board.)
7-79
Page 199
(11)
OUT-29D Module (THK-5025) Title
Transistor Output Module (+) COM
Specification
OUT-29D
Number of circuits
32 points
Insulation method
Photo coupler insulation
Rated Load voltage
DC12V/24V
Operating Load voltage range
DC10~30V
Maximum Load current
0.2A/point 2A/COM
Leak current at OFF
0.1mA Max
Max voltage drop at ON
1.5V Max, 0.8V (TYP.) 0.2A
Response OFF→ON time ON→OFF Internal current consumption (DC5V)
External power supply
(Identification Code:
12H)
1ms Max 1ms Max 210mA Max (ALL points ON)
voltage
DC12/24V (DC10 - 30V)
Current
Max 148mA (at DC30V, per 1 PWR) Typ. 82mA (at DC24V, per 1 PWR)
Surge killer
C-E .. by Zener diode
Fuse rating
3.2A/COM *1
Fuse blown display
None
Common method
16 points, 1 common (Inter-common insulation)
Status indication
LED ON at switch ON (16 points display switching)
External connecting method
37-Pin D-sub connector, 1 piece
Weight
0.20kg
PWR1 OUT00 OUT0F to CPU
L ~
Internal circuit
Photo coupler
L
COM1
FUSE
DC24V PWR2 OUT10
L ~
OUT1F
L
COM2 may be unable to protect the elements.
A0 A2 A4 A6 A8 AA AC AE
1
20
COM1
NC
A1 A3 A5 A7 A9 AB AD AF PWR1
B0 B2 B4 B6 B8 BA BC BE
B1 B3 B5 B7 B9 BB BD BF
COM2
DC24V
*1: This fuse is to protect printed circuit board from burning.
Connector pins configuration
External Connection and Internal Circuit Block Diagram
19
37
PWR2
When short-circuited, this fuse
(This fuse is soldered to the printed circuit board.)
7-80