The text of a manual · part 37 of 44
Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual: 9. Built-in function, pages 326 to 335
Pages 326 to 335 of 387, from Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual
The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Toyopuc OUT-15 and Toyopuc OUT-18
Page 326
(6) (error E2) Transmission
Sending error error:
For the master, connected confirmation of the slave cannot have been done. (There is no answer from all slaves)
Check the attachment of connector.
Attachment OK?
N
Y
Attach the connector to securely.
When the T-branch connector is used in the control board, is the connection good? N
Connection OK?
Confirm the slave power source.
Power ON?
N
Connected correction
Y
N
Recovery?
Y Y
N
Y
Supply power to the slave. N
All the communication speed same?
Recovery?
Y
Confirm the communication speeds of DLNK-M2 and all the slaves. Procedure C
N Set all the communication speed same.
Y
N
Recovery?
Y
Confirm the communication cable. Procedure B
Recovery?
Recovery?
Y
N
Exchange PC3JG
End
9-101
Page 327
(7) (error F1) Busoff: Communication stop owing to data errors
Busoff detection
Confirm the communication speeds of the master and all the slaves. Procedure C All the communication speed same?
N Set all the communication speed same.
Y
N
Recovery?
Y
Confirmation of end terminal resistance Resistance value 121Ω Connect it to each of the ends of main line Procedure B to (1)
N
Connection OK?
Y
Connect a 121Ω end terminal resistance to each of the ends of main line of the network.
Confirm the position of terminal resistance. Procedure B to (2)
Recovery?
Y
N
Position OK? Y
Correction of the position
Confirm the communication cable. Procedure B (3)to(6)
Recovery?
N
N
Recovery?
Y
Y
N
Exchange PC3JG
End
9-102
Page 328
(8) (No display) Confirm the error code (lower) of the link error data output special register.
11
12
13
14
15
21
Communication portion hardware error
22
23
24
25
26
27
28
29
2A
Link parameter error
Supply power once again
Y
Battery error? N Write the normal parameter, and supply power once again.
Recovery?
Remove the error in accordance with the instruction manual for CPU.
N
Y End
Exchange PC3JG
A How to check the communication power: (1) Check the voltage at the master. Confirm that the voltage between V+ (red) and V- (black) of the terminal block is 11 to 25 V. (2) Check the communication power (24 V power). Confirm that 24 V is being supplied correctly. -
In case of power interruption (trip), there is a short circuit; check the wiring.
-
If 24V is being output correctly, check the wiring for disconnection or wrong connection.
-
Check the power source for faults.
9-103
11 to V?
25
Page 329
B How to check the communication cable: (1) Check the terminating resistor. Confirm that there are both 121 Ω terminating resistors. It easy to check with the following method. Keep the communication wiring connected, turn off the power, and ensure that the resistance between CAN-H (white) and CAN-L (light blue) of the communication connector is 60.5 Ω (60.5 to 65.1 Ω [see Note 1]). If there is only one terminating resistor, it is 121 Ω. If there are three terminating resistors, it is 40 Ω. (2) Location of the terminating resistors The line that has a terminating resistor at each of its ends is the main line. Branches are added to the main line. Please note that there are length restrictions for main line and branches. Communication speed 500kbps 250kbps 125kbps
Maximum network length 100 m Max. 250 m Max. 500 m Max.
Branch line length 6 m Max. 6 m Max. 6 m Max.
Total branch line extension 39 m Max. 78 m Max. 156 m Max.
Check the wiring diagram included in the electric circuit diagram and the actual wiring. (3) Check the terminal block for looseness. Check for items such as pressure adhesion, unnecessary pieces of wire, foreign plastic chip entanglement, and pressure terminal size. (4) Check the connector for looseness. (5) Check the cable routing. Verify whether the cable is subjected to forcible bending. (Is it being stretched by the tie-wrap inside the bear? Is the junction connector inside the bellow?) (6) Confirm that there is no disconnection, short circuits, or incorrect wiring (reverse connection of CAN-H/-L, reverse connection of V+/V-). 0.1 Ω/m with standard cables
(Note 1) R: Terminating resistor r: Cable resistance
Assuming max. 100 m at 500 kbps, the overall resistance (max.) is:
r
R r
=
R
9-104
1
1 R
+
1 R+2r
1
=
1 121
=
65.1(Ω)
1 + 121+2×10
Page 330
C
Setting switches and MS (module status) lamp
PC3JG
MS lamp NS lamp
DRMT
DLNK-1S
MS lamp NS lamp
Communication speed: 500 kbps
DLNK-S
DLNK terminal MS lamp NS lamp
Address switch
Communication speed: 500 kbps
Communication speed: 500 kbps
DLNK-S Address
NS lamp MS lamp Communication speed: 500 kbps
9-105
Page 331
D Confirmation of link parameter (set example in PCwin) (1) Select "Set of the link
(2) DLNK-M2 is selected and
(3) Link area parameter"
"Details
Confirm the each slave’s setting, from parameter menu.
the setup" button is do/do not, direction of forwarding selected.
(M
S) and number of bytes.
Link parameter screen
DLNK-M2 screen Please refer to the instruction manual of PCwin for details.
E If communication errors may occur at different slaves on the line: There is highly likely a short-circuited cable (in the case of a momentary short circuit). Momentary short circuits occur during communications and related slaves are indicated as problem slaves. To check for short circuits, disconnect the problem slaves and their wiring and specify "do not connect" with the link parameters. This problem may also result from noise; check the number of CAN errors. Procedure
F
9-106
Page 332
F How to check the number of CAN errors: (1) Example of a measuring tool (ex. measure with the diagnostic tool described below) Checks with DeviceNet Detective (Synergetic Microsystems, Inc.) Connection to the DeviceNet line will enable measuring the number of CAN errors. (during communications only) (2)Check on the DLNK master (S register monitor on the operation panel or the peripheral equipment) The number of CAN errors from the POWER ON is stored in S306-S30B(in case of Link No. = 1). (They are cleared at the POWER OFF) The address are determined by link No. Address : S3#6 – S3#B link No.
1
2
3
4
5
6
7
8
#
0
2
4
6
8
A
C
E
If CAN errors are being counted, the communication cable and the devices may be subjected to noise. please confirm that CAN-H, CAN-L, and additionally (DRAIN, V+, V-) are not short-circuited.
9-107
Page 333
9.4.
SN-I/F If Rack No.: Built-in / Slot N0.: Standard is not made setting in the link parameters, SN-I/F is selected automatically. Because fixed parameters are automatically set as for the data link area, they can not be changed. In the case of PC2 compatible mode, it cannot be used as SN-I/F. If TOYOPUC-PCS is connected, the terminator must be turned ON If TOYOPUC-PCS is not connected, the terminator must be turned OFF terminator switch for SN-I/F ON
TOYOPUC-PCS
9-108
Page 334
(1) PC link specification Items
Specification
Data link
I/O : 32byte,
Transmission distance
Synchronous system Transmission system
Max 3 m (only inside of controller box) Parity ..............1 bit (even parity) Data length .....8 bit Stop bit ...........1 bit Start-stop synchronous Semi-dual system (2-wire type)
Communication speed
288kbps
Cable
Shielded twist bare cable
Data type register : 32byte
(2) Data link areas When PC3JG does not communicate with TOYOPUC-PCS (S130 bit 0 is OFF), The input data is all OFF. Items I/O register input output input output link area note
EVE00-EVEFF EVF00-EVFFF S140-S14F S150-S15F
32 byte (256 points) 32 byte (256 points) 32 byte 32 byte
(3) Special registers The communication state with TOYOPUC-PCS and The run state of TOYOPUC-PCS can be confirmed with S130 (communication status). registers
S130
S131 S132 S133 contents Communication status information bit0:communicating bit1:RUN signal bit2:ERR0 signal bit3:ERR1 signal bit4:ALM signal bit8:link command usable bit9:link command error Flaming error counter Parity error counter Over run error counter
9-109
Page 335
9.5.
Set built-in link parameter Total two ports are equipped as standard; one is port for CMP link (computer link) or PC link or SN-I/F, the other port for DLNK-M2. Rack No. and slot No. when setting the link parameter set CMP link(computer link) or PC link as a rack No. built-in and slot No. standard; DLNK-M2 as a rack No. and slot No.0.
When you use it as SN-I/F, please give rack number and slot number as un-setting up. It operates as CMP for PC2 interchangeable mode. Link No. can freely be changed. However, please do not set the same link parameter to each link No. Set I/O module of rack No.0 and slot No.0 Link
Link No.
rack No.
Slot No.
Module name
CMP PC
Given
Built-in (F)
Standard (0)
Computer link PC link
DLNK
Given
0
0
DLNK-M2
(Note1) If built-in lack No., standard slot No. is not made setting, SN-I/F is selected. In the case of PC2 compatible mode, it can be used as computer link. (Note2) Even when not using built-in DLNK-M2, a link module needs to be set up. It is necessary to choose 「Do not」 to slave in a detailed setup of a link parameter.
9-110