Page 316

(6)Loading of link file The link file is read to the CPU with special module byte data reading fiat (SPR-FUN304). (6-1)Usage of SPR fiat SPR Execution condition

D0000 D0001 D0002

1 0 3

OP1

OP2

OP3

D0

D1

D2

Link No.1 2 3 4 5 6 7 8 Link fiat available flag (V90,92,94,96,98,9A,9C,9E)

Link No. 1 - 8 0 0 5 0 4 0 0 0 0

Number of loading bytes (Hex) The top address of link file (Hex) The first indirect addressing of register forwarding ahead (Hex)

1 : A link fiat available flag is a flag which shows the response of the link module to the link file loading demand of the CPU. The address of the flag is decided by link No. Link No.

1

Flag address V90

2

3

4

5

6

7

8

V92 V94 V96 V98 V9A V9C V9E

2 : OP1 sets link No. and the number of loading total bytes from the link file. 3 : OP2 sets the top address of the loading link file. 4 : OP3 sets the top address forwarding of the loading link file ahead by indirect addressing. (6-2)Attention of link file loading 1 : The link file is not load while RUN of the CPU is stopping. 2 : Execute the execution condition by the edge in two seconds or more. 3 : The number of loading bytes is 256 bytes or less (100h). 4 : Setting as follows, becomes applied fiat error 1(special relay V50:ON). * Set link No. excluding 1-8. * The link module does not exist in specified link No.. * The address of the register forwarding ahead is outside a regulated range. 5 : Setting as follows, becomes applied fiat error 2(special relay VC9:ON). * Read link file address exceeds 19Fh. * Number of total bytes of read link files exceeds 416 bytes. * There is no response from the link module.

9-91

Page 317

(6-3)Example of circuit to loading retry frequency It is an example of the circuit to read D0000-D001F the retry frequency of the slave. Example of circuit reference 00000

F0002 WMOV

FUN 101 2040h D100

Forwarding byte number 64 bytes Link No. 2 (It is set according to link No. as for 1-8).

00001

00002

F0003 WMOV

FUN 101 C0h

F0004 WMOV

FUN 101 2000h

D101

D102

The top address of link file is stored

The top indirect address as destination register is stored.

D0000

00003

FUN 448 START

00004

2 sec clock

Link No. 1 2 3 4 5 6 7 8 Link command available flag (V90,92,94,96,98,9A,9C,9E) F0001 FUN 304 SPR D100 D101

V073 V092 P000

00005

D102

Command to load the data from link file to CPU

FUN 452 END

It is necessary to load the data to the CPU so that the 00006

FUN 456 link file is in DLNK-M2.

PEND

Register table Register

H

L

Slave 01

Slave 00

Slave 03

Slave 02

D0000 The retry frequency is hexadecimal data.

D0001 Slave 05

Slave 04

D0002

9-92

Page 318

9.3.11. Error Contents and Supposed Causes Special register Error contents Main supposed cause contents RAM check error during initial @@F9 RAM (memory) error processing Read / storage of config uration @@F8 Non-volatile memory error data impossible

0011 @@12 @@13

0014 0015 0021 0022 0023 0024 0025 0026 0027 0028 0029 002A

No response from communication portion (at normal condition) Communication no resume Communication no stop No response from communication portion at power supply or at reset No response from communication portion after parameter transfer Total number of bytes exceeding 256 Station with 0 byte present Total number of bytes of one slave exceeding 64 Input / output designation error Range over PLC input / output and range in duplication Sub code error Setting error of “General-purpose status area” Setting error of “Short-circuit state area” Setting error of “Unconnected state area”

Recovery method When it dose not start by supplying power once again, exchange PC3JG.

Communication portion hardware error • Error with communication circuit of DLNK

When it dose not start by supplying power once again, exchange PC3JG.

Link parameter error • Error with CPU main body or memory

Rewrite normal parameter, and reset or supply power once again.

Reset so that there should not be duplication of node address, and supply power once again. Reset the correct communication speed, and supply power once again.

@@F0

Node address duplication

Duplication of DLNK node address with other node

@@F3

Switch setting error

Setting error in the communication speed setting switch

@@ : Master's node address, ## : Node address of abnormal slave

9-93

Page 319

Special register contents

##D6

Error contents

Main supposed cause

The number of bytes of a slave and the number of bytes of a link parameter are not in agreement. Collation error (Note) When "recognition of the (Disagreement of number of slave I/O bytes" of a link the number of I/O parameter setup is set up for "not bytes) recognize" by DLNK-M2 or when a slave cannot be recognized, the number of I/O bytes of a slave becomes 0 byte. There is no response from a slave or A slave does not exist. (Note1) After the abnormalities (Error code: d9) in transmission Collation error occur, it detects "a slave cannot be (A slave cannot be recognized", also when it resets, recognized.) while an unusual cause has not been canceled. (Note2) When a slave cannot be recognized, the number of I/O bytes of a slave becomes 0 byte.

Response timeout from slave

##D9

Transmission error

@@E0

Transmission error (network power error)

Communication power is not supplied to the communication connector.

Transmission error (sending timeout)

Sending has not completed owing to any of the following: (1) No slave (2) Communication speed in discrepancy (3) Failure with DLNK-M2 Trouble with communication environment

@@E2

Recovery method Confirm the I/O byte number of the slave to be connected, and change link parameter. (*When the node address of the slave has been changed, turn on the slave once again and change the link parameter. When the slave has been removed, it is also necessary to change the link parameter.) Please check the following item. ・Is the power supply supplied to the slave? ・The connector of a slave is connected correctly? ・Doesn't the node address overlap? ・Aren't there any abnormalities in a telecommunication cable? Check whether the slave connector is connected correctly or not. Check whether the power is supplied to the slave or not. Check the wiring portion to the connector for disconnection or short circuit in communication line. In the case of a slave by other manufacturers, refer to the instruction manual for the slave concerned. Check whether the communication power supply unit works normally or not, and whether the voltage is within the rating or not. Check the power line for disconnection or short circuit. Check the following and turn it on again. • Whether the connector of DLNK is connected or not • Whether power is supplied to the slave or not • Whether the communication speed of master meets that of the slave • Whether there is disconnection or short circuit in the connector concerned or not. In the case of recurrence, exchange module.

@@ : Master's node address, ## : Node address of abnormal slave

9-94

Page 320

Special register contents

@@F1

Error contents

Busoff detection

Main supposed cause

Recovery method

Busoff condition (communication stop owing to data error) detected

Check the following and turn it on again. • Whether the communication speed of master meets that of the slave • Whether the end terminal resistance (121Ω) is connected to each of the ends of network bus or not • Whether all the slaves are set correctly or not • Whether the communication cable is wired correctly or not • Whether the power cable and power source are connected correctly or not • Whether there is disconnection or short circuit in the wiring portion to the connector connected or not. In the case of recurrence, exchange module.

@@ : Master's node address, ## : Node address of abnormal slave

9-95

Page 321

9.3.12. Error Check Flowchart of DLNK-M2

PC3JG terminator terminator Trunk line

Trunk line

Slave

T-branch tap

T-branch tap Network power supply (24V)

Trunk line

Branch line

Branch line

Branch line

Slave

Slave

Slave

<Main, error list> When trial run Be in is adjusted operation

Error

Main presumption cause

Standard value

E0:Network power supply error

O

O

E2:Sending error

O

O

F9:Hard error

O

-

F1:BusOFF

O

-

D9:Transmission error

O

-

Out of response time from slave

-

- a).”Disagreement of the number of I/O bytes” The number of bytes of a slave and the number of bytes of a link parameter are not in agreement. Note) When "recognition of the number of slave I/O bytes" of a link parameter setup is set up for "not recognize" by DLNK-M2 or when a slave cannot be recognized, the number of I/O bytes of a slave becomes 0 byte. b). “A slave cannot be recognized.” There is no response from a slave or A slave does not exist. Note1) After the abnormalities (Error code: d9) in transmission occur, it detects "a slave cannot be recognized", also when it resets, while an unusual cause has not been canceled. Note2) When a slave cannot be recognized, the number of I/O bytes of a slave becomes 0 byte.

-

D6:Collation error

O

The power supply voltage is abnormal in the 11 - 25Vdc network. Wiring the same as Connected confirmation of the slave cannot have system chart. Agreement of been done (There is no answer from all slaves). transmission rate. Abnormality occurred by the memory check in Abnormality does PC3JG. not occur. Abnormality does Forwarding data layout is outside regulations not occur. (protocol abnormality). (The protocol is CAN standard)

Machine error occurrence N Is DLNK error? Y According to the instruction manual of each equipment Please do the troubleshooting.

Error code is confirmed. D9: MS and the NS lamp of the slave are confirmed at abnormal transmission.

To the next page

9-96

Page 322

From former page

F0

F1

F3

F9

F8

To (1) To (7) To (2)

D6 To (4)

RAM error

D9

E0

E2

To (3) To (5) To (6)

No display To (8)

Non-volatile memory error

Supply power once again.

Recovery?

Y

N Exchange PC3JG End

Note 1: At the event of serious failures, CPU memorizes up to 8 error codes. Therefore, check whether there is other serious failure by I/O monitor or so. In the case of serious failure with DLNK-M2, error code 84 I/O MODULE ERROR 2 occurs.

9-97

Page 323

(1) (error F0)

(2) (error F3)

Node address duplication Set the switch so that there should not be duplication on node address, and supply power once again. * Fix the node address of DLNK-M2 to “00.”

Recovery?

Y

Switch setting error Set the communication speed setting switch correctly. * The communication speed cannot be set other than 125, 250, or 500 Kbps.

N Exchange PC3JG

End

9-98

Page 324

(3) (error D9) Transmission error Different station numbers for error occurrences

Slave communication speed and address setting correct?

Procedure

C

Procedure E

Y Power is being correctly supplied to the slave (MS lamp lit)?

Procedure C

Lit in red (hardware fault) Not lit (power is not being supplied)

Lit in green (hardware is operating correctly)

Check the NS lamp for the slave.

Not lit and flashing in green (communication power is turned back on again)

Flashing in red (communication error) Check the communication cable. Procedure B (3) to (6) Check the communication Procedure B (1) to (6)

OK cable.

Check the communication power. Procedure A

OK

OK

Check the number of CAN errors. Procedure F OK Replace the faulty slave. NG Exchange PC3JG

9-99

Page 325

(4) (error D6) Collation error (“Disagreement of the number of I/O bytes” or ”A slave cannot be recognized.”)

For the link parameter setting, please confirm "Number of real slave I/O bytes" is set to "Recognized".*1 If it is "Not recognized", set it to "Recognize". And then reset and restart CPU or turn on the power supply again. *1Refer to "9.5.4.2 Link Parameter Setting".

Please confirm the number of I/O bytes in the link parameter and the number of Procedure D I/O bytes of slaves. *2 Number of I/O bytes of slaves. =0 bytes?

*2: Refer to special register S3*0~ S3*4 for link error data output.

Accord?

N

Y

N Set parameters correctly.

Y

A slave cannot be recognized. The following item is checked. - Is the power supply supplied to the slave? - Is the connector of a slave connected correctly? - Doesn't the node address overlap? - Aren't there any abnormalities in communication cables? Please exchange slaves if there is no problem in items mentioned above

Exchange the slave.

(5) (error E0) Network power source error

Confirm the communication power source. Procedure A Recovery?

Y

N Confirm the communication cable. Procedure B (3) to (6) Y Recovery?

N End

Exchange PC3JG

9-100