Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual: 9. Built-in function, pages 336 to 345

Pages 336 to 345 of 387, from Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual

The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Toyopuc OUT-15 and Toyopuc OUT-18

Page 336

9.5.1.

Set the rack, slot and link module.

Click the link module and select a module name from a table after inputting the rack No. and slot No.

9.5.2. Computer Link

Set the computer link When setting a built-in computer link of PC3JG, it is necessary to set the rack No. “built-in” and slot No. “standard”.

Select the computer link and click a detailed setting.

9-111

Page 337

Operating procedure 1. Set the station No. 2. Set the data length. 3. Set the stop bit. 4. Set the baud rate. Click 5.

for the baud rate and select a desired baud rate from the list.

Set the 2-wire/4-wire system. Select 2-wire.

6.

When the setting is completed, click [OK].

9-112

Page 338

9.5.3.

PC Link

When setting a built-in computer link of PC3JG, it is necessary to set the rack No. “built-in” and slot No. “standard”. (1) Set up the master station of PC link Select PC link (master).

Select PC link (master) and click a detailed setting.

Click a PC link (master).

9-113

Page 339

Operating procedure 1. Set the head address of a link area. The range available for input Link relay Internal relay

L00L - L7FH M00L - M7FH

Input-output Link relay(extended area)

X/Y04L - X/Y7FH EL000L - EL1FFH

Internal relay(extended area)

EM000L - EM1FFH GM000L – GMFFFH Input-output(extended area) EX/Y000L - EX/Y7FH GX/Y000L – GX/YFFFH Note) Take care not to overlap I/O that is used in PC3JG when using X and Y areas. 2. Set up the connective slave stations. Select the slave station to connect and click the set the slave station. 3. Set up the number of transmission bytes. The sum total of the number of transmission is to 64 bytes. 4. [Software SW] is clicked and a soft switch is set up. 5. If a setup is completed, please click [O.K.].

9-114

Page 340

Setting of soft switch The following switches need to be set up for built-in PC link.

Operating procedure 1. Select the state of transmitting data at CPU stop. • transmitting data when CPU stop OFF DATA Off DATA is transmitted at the time of CPU stop. DATA BEFORE A STOP Data before a stop is transmitted at the time of CPU stop.

2. Select state of CPU RUN at the time of the communication error. • CPU operation at the communication error. STOP CPU is stopped at the time of the communication error. RUN Continuation CPU RUN is continued at the time of the communication error. The special relay for communication error is turned ON.

9-115

Page 341

3. Select the baud rate of communication. • Baud rate of communication Select the baud rate of communication. • 57600 bps • 19200 bps • X3 (triple) speed Attention Communicating with NC machine which corresponded to X3 (triple) speed, if a setup of baud rate is set to 57600bps, the check of communication error may not be made. 4. If a setup is completed, please click [O.K.].

(2) Set up the slave station of PC link Select PC link (slave).

Select PC link (slave) and click a detailed setting.

Click a PC link (slave). Refer to the setup of PC link master station for the following setup.

9-116

Page 342

9.5.4.

DLNK-M2

When setting a built-in DLNK of PC3JG, it is necessary to set the rack No. “0” and slot No. “0”. 9.5.4.1. I/O Module Parameter Setting "I/O Module" is chosen at a parameter menu and the following screen is displayed.

(2) (1)

(1) Rack No. and Slot No. in which the module is mounted are chosen. (2) [Setup] is clicked and the following screen is displayed. (5)

(4) (3) (3) [Special/Communication] is chosen in Module identification. (4) [High speed remote I/O, DLNK-M, DLNK-S2, AS-i, DLNK-M2] are chosen in Module Name. (5) By clicking [OK], the following screen is displayed and Allocated Points and Module Name are set up.

(6) (6) [OK] is clicked after completing the setup.

9-117

Page 343

9.5.4.2. Link Parameter Setting “Link parameter" is chosen at a parameter menu and the following screen is displayed.

(1) (2)

[Setting Link module name] (1) Program No. and Link No. are chosen. (2) [Link setup] is clicked and the following screen is displayed.

(3)

(4)

(5) (6)

(3) Rack No. in which the module is mounted is chosen. in Rack No. column is clicked and rack No. (0 - E) is chosen. (4) Slot No. in which the module is mounted is chosen. in Slot No. column is clicked and Slot No. (0 - 7) is chosen. (5) Setting Link module name in Link module name column is clicked and Link module name is chosen. Here, the example which chose [DLNK-M2] is shown. (6) By clicking [OK], the following screen is displayed and Link module name is set up.

(7)

(7) By clicking [Detail], the following screen is displayed. 9-118

Page 344

[Setting detailed setup] Setting the detailed parameter of DLNK-M2 (1) (2)

(9)

(4)

(3) (5) (6) (7)

(7)-1

(7)-2

(8)

(1) [Link area] The top address of the communication area is set up. The last address is automatically set up by the sum total of transmission bytes of slaves. The area which can be used as I/O communication is as follows. Input / Output relay: X•Y000-X•Y7FF,EX•EY000-EX•EY 7FF,GX•GY000-GX•GYFFFF Link relay: L000-L7FF,EL000-EL1FFF Internal relay: M000-M7FF,EM000-EM1FFF,GM000-GMFFFF Note 1: GX•GY and GM area can be used in the PC3JG separate mode. Note 2: When using X•Y area for the communication area, don't overlap I/O address used by CPU. (2) [Slave setup list] Slave No. at Slave setup list is clicked, [Slave setup] is clicked, and detailed parameter of Slave is set up. Please refer to "Setting detailed parameter of Slave " for details. (3) [Communication stop in communication error] Communication is set up for "stop" or "not stop" in communication error. When it sets up for "not stop", the master does not report errors to CPU in communication error, but the master continues the communication with normal slaves. The master resumes the communication with the slaves automatically, when error slaves return normally.

9-119

Page 345

(4) [Number of real slave I/O bytes] •The number of I/O bytes of each slave connected on the network is set up for "Recognizes" or "Not recognize". •When it sets up for "Recognizes", the number of real slave I/O bytes is set to the link error data output special register at the time of the I/O size mismatch (error code: d6) generating. When it sets up for "Not recognize", it is not set (00h is set). •When it sets up for "Recognizes", the time of the processing which the number of I/O bytes recognizes is added to initial processing time until supplying power or reset/start to the establishment of communication for about 10 seconds. Therefore, we recommend you to set up for "Recognizes" during network configuration and to set up after the completion of configuration for "Not recognize". (5) [Message issue retry count] DLNK-M2 issues Explicit messaging to a slave at the time of collecting diagnosis data on DRMT series or at the time of MSET command execution. The number of times of message retrying after failing in the receipt of the response data from a slave is set up as [Message issue retry count]. Usually, default 0 is set up. Setting range: 0 to 15 (Decimal) (6) [Message response watch time] The waiting time of the response data from the slave to explicit messaging by DLNK-M2 is set up. Usually, default 20 (2 seconds) is set up. Setting range: 1 to 655 (Decimals) (7) [Extended setting] When a slave is DRMT series, the area that stores diagnosis data (General-purpose status, Short-circuit state, Unconnected state) in CPU is set up. Refer to "9.5.4.3 Collection of Diagnosis Data" for the details of diagnosis data. 1. "P1", "P2", "P3", "Ext." selection Either program No. (P1-P3) or Extended I/O Address is chosen. 2. Setting top address The top address of the storing area is set up. The last address is set up automatically (The capacity of each diagnosis data is fixed to 128 bytes.) Useful I/O Address: Area other than "B" and "EB" (8) [Unconnected detecting effective I/O address list] The I/O address that set “Enable” to Unconnected detecting is displayed about a slave clicked in [Slave setup list]. (9) [OK] is clicked after completing the setup.

9-120