For the Toyopuc OUT-15 and Toyopuc OUT-18
Page 52
(2) Execution/non-execution of program Execution/non-execution of program 2 and program 3 is set using the CPU operation mode parameters. Program for which non-execution was selected is not executed. Execution of program -1,to -3
(3)
Execution of program -1,-3
Execution of program -1,-2
Execution of program –1 only
PRG.1
PRG.1
PRG.1
PRG.1
Execution (fixed)
Execution (fixed)
Execution (fixed)
Execution (fixed)
PRG.2
PRG.2
PRG.2
PRG.2
Execution
Non-execute
Execution
Non-execute
PRG.3
PRG.3
PRG.3
PRG.3
Execution
Execution
Non-execute
Non-execute
End processing
End processing
End processing
End processing
(Update I/O data)
(Update I/O data)
(Update I/O data)
(Update I/O data)
Link of program with RUN signal Link of program-2 and -3 with RUN signal can be selected from the CPU operation mode parameters. If "LINK" is selected and applicable program stops, RUN signal turns OFF linked with the program and all other programs stop simultaneously. Link with RUN signal (by parameter setting)
(4)
RUN signal status at program stopping
Program-1
Program-2
Program-3
Program-1
Program-2
Program-3
Link (fixed)
Link
Link
OFF
OFF
OFF
Link (fixed)
Non-link
Link
OFF
Continued
OFF
Link (fixed)
Link
Non-link
OFF
OFF
Continued
Link (fixed)
Non-link
Non-link
OFF
Continued
Continued
Execution of SFC program The SFC program is executed after the main program of each program. START
Main program
SFC program
END
3-19
Page 53
3.2.4 Inter-program data utilization As mentioned in the foregoing subsection, the PC3JG can execute three different sequence programs maximum in the given order. These program data can be utilized mutually for each program without special setting. (1)
Data area separate mode The basic area data are independent from each other every each program. On the other hand, the I/O area and extended area data are common to each program. (1-1) Basic area PRG.2
PRG.3
START
START
START
M100
M100
Y200
Y200
X000
· · ·
· · ·
· · ·
P2-M100
PRG.1
P2-M110
=H P3-D0000L=12h
Sequence program
EM0000
X000
EM0000
· · ·
· · ·
· · ·
END
END
END
PEND
PEND
PEND
X000 Y200
I/O area
Basic area data
M100
M100
M100 M110
M100 D0000
Extended area data
EM0000
Where data area in other program is specified, P* representing program No. ( P1=Program-1, P2=program-2, P3= Program-3) is prefixed to each program address. EX.
P2- M100 : M100 of program-2 P3-D0000L: D0000L of program-3 (Byte below D0000)
3-20
Page 54
(1-2) I/O area and extended area PRG.2
PRG.3
START
START
START
M100
M100
Y200
Y200
X000
· · ·
· · ·
· · ·
P2-M100
PRG.1
M100
=H P3-D0000L=12h
Sequence program
EM0000
X000
EM0000
· · ·
· · ·
· · ·
END
END
END
PEND
PEND
PEND
X000 Y200
I/O area M100
Basic area data
M100
M100 M110
D0000
Extended area data
(2)
P2-M110
EM0000
Data area single mode The data area in each program is common to other programs. PRG.2
PRG.3
START
START
START
M100
M200
Y200
Y200
X000
· · ·
· · ·
· · ·
M100
PRG.1
M300
=H D0000L=12h
Sequence program
EM0000
X000
EM0000
M310
· · ·
· · ·
· · ·
END
END
END
PEND
PEND
PEND
I/O area
X000 Y200
Basic area data
M100 M200 M300 M310 D0000
Extended area data
EM0000
3-21
Page 55
(3) PC2 compatible mode Under this mode the number of programs is limited to one program (Program-1). No extended area is available as the data area. PRG.1 START
Sequence program
· · ·
M200
M100
M200 =H D0000L=12h
· · · END PEND
I/O area
X000 Y200
Basic area data
M100 M200 D0000
3-22
Page 56
3.2.5
I/O module setting I/O 64 points for signal I/O points (16/16) and for control I/O 32 points (16/16) are equipped at rack No. 0 and slot No. 0 as standard. Setting data for I/O module in rack No. 0 and slot No. are following. I/O module setting of rack No. 0 and slot No.
3.2.6
Allocated point
Module identification code
PC3JG
64 points
3E
PC3JG-P
64 points
3F
Rack No. and slot No. at the time link parameter setting Total two ports are equipped as standard; one is port for CMP link (computer link) or PC link or SN-I/F, the other port for DLNK-M2. Rack No. and slot No. when setting the link parameter set CMP link(computer link) or PC link as a rack No. built-in and slot No. standard; DLNK-M2 as a rack No. and slot No.0. Link No. can freely be changed. When you use it as SN-I/F, please give rack number and slot number as un-setting up. Link module setting Link
Link No.
Rack No.
Slot No.
Module name
CMP PC
Random
Built-in (F)
Standard (0)
Computer link PC link
DLNK
Random
0
0
DLNK-M2
(Note1) If built-in lack No., standard slot No. is not made setting, SN-I/F is selected. In the case of PC2 compatible mode, it can be used as computer link. (Note2)Even when not using built-in DLNK-M2, a link module needs to be set up. It is necessary to choose 「Do not」 to slave in a detailed setup of a link parameter. (Note3)Please turn on the terminal switch when using it as SN-I/F. When you do not use it as SN-I/F, please turn OFF.
3-23
Page 57
3.2.7
Program creating sequence The creating sequence is mainly classified into two cases; one case that sequence program is not pre-created and another case that it is already pre-created.
(1) Case that sequence program is not pre-created: STEP-1
Set CPU operation mode by the peripheral equipment.
STEP-2
Set parameters by the peripheral equipment and execute PROGRAM CLEAR in the peripheral equipment.
STEP-3
STEP-4
STEP-5
Start program creation.
Write the sequence program (program + parameters) in CPU. Set the current time on the built-in clock by the peripheral equipment.
STEP-6
Set necessary data (data register, etc.) by the peripheral equipment.
STEP-7
Store the sequence program (program + parameters) in FDD, etc.
(2) Case that sequence program is already pre-created:
STEP-1
Read the sequence program (program + parameters) into the peripheral equipment from FDD, etc.
STEP-2
Check the parameters on the peripheral equipment and set them as necessary.
STEP-3
Write the sequence program (program + parameters) in CPU.
STEP-4
Set the current time on the built-in clock by the peripheral equipment.
STEP-5
Set necessary data (data register, etc.) by the peripheral equipment.
STEP-6
Store the sequence program (program + parameters) in FDD, etc.
3-24
Page 58
3.2.8
Automatic setting of I/O modules and link parameters
I/O modules and link parameters can be set automatically in CPU . For setting, follow the sequence given below.
STEP-1
With the power switch kept OFF, shift "RESET/START" switch to " START" and press the same switch with finger so as not to return.
START
RESET
RESET/START switch
STEP-2
Turn ON the power switch.
STEP-3
This completes automatic setting of I/O modules and link parameters. If error is detected at this stage, ERR lamp lights.
STEP-4
If no error, the sequence is put in RUN by RESET/START switch.
3-25
Page 59
I/O module and link parameter set value (Automatic setting by CPU) Item Set value Identification Rack No. 0 and slot No. 0:3F of I/O module Other: as actually installed Allocation of I/O module (0~E rack and 0~7 slot) Allocation Rack No. 0 and slot No. 0:64 points of I/O point Other: as actually installed Program 1 Lack No. 0 and slot No. 0 Link 1-1 High speed remote I/O Lack No. built-in and slot No. option
Link parameter *1
( Link 1-2 ~ Link1-8 )
As actually Installed *2
Program 2 ( Link2-1 ~ Link2-8 ) Program 3 ( Link 2-1 ~ Link 2-8 ) *1 Only such name setting as lack No., slot No. and link module is implemented. *2 Built-in link is allocated to link 1-1. Built-in DLNK is allocated as high-speed remote I/O. Set DLNK-M2 using peripheral equipment. Lack No. and slot No. are allocated from link 1-2 in program 1 in the order of their smaller number. They are also allocated to link 2- # in program 2 when actual installed link number exceeds 8. However they are allocated to link 3- # in program 3 when CPU operation mode having no program 2 is selected. No allocation is made for the link that is exceeded link number 8 when CPU operation mode having neither program 2 nor program 3 is selected.
3-26