Programmable Controller TOYOPUC PC3JG-P-CPU TIC-6088 / PC3JG-CPU TIC-6125 Operation Manual, pages 60 to 69

Pages 60 to 69 of 387: 4. Test Run; 5. Error Alarm

The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Toyopuc OUT-15 and Toyopuc OUT-18

Page 60

4 Test Run 4.1 Check Items before test run Parameters setting · Each parameter set correctly?

Battery · Battery connector connected perfectly? · Battery fully charged ?

I/O cables · Inter-base I/O cables connected exactly ?

4

Rack No. selector switch · Selector module rack No. is set ? · Rack No. free from doubling ? · Rack No. "F" set ?

I/O address selector switch · I/O addresses of selector module are set as specified ? · I/O address free from doubling ? · I/O address not exceed "3F" ?

Module mounting · Each module is securely mounted ? · I/O points not exceed 2048 points ? · Communication link module not exceed 15 ?

Fuse · Free from blown and damage ?

Wiring to terminal block · Cables are connected correctly to each terminal ? · Cable size proper ? · Each terminal free from screw loose ?

4-1

Page 61

5 Error Alarm 5.1 Error ranks Error ranks are mainly classified as follows. WARNING ············ Run further continued. This error rank does not cause system down, but would lead to system down if the error state is left as is. RUN lamp and RUN display on status message display remain unchanged as usual. MINOR ERROR ············ Run further continued Errors which are caused mainly by user program or incorrect setting by user and which are not considered as cause of serious affect on the system even if the sequence program is not stopped immediately. RUN lamp and RUN contact are remained unchanged as ON. MAJOR ERROR ············ Run stop Errors which are caused mainly by system hardware and for which further continued operation of the system is considered to be difficult. Once error of this rank occurred, the sequence program run is stopped and RUN lamp and RUN contact turn OFF simultaneously.

5-1

5

Page 62

5.2

Display of abnormality (1) E/A lamp (red) is lit when CPU is abnormal. Error code is displayed in “Operation state monitor” mode of message display. Also error message can be confirmed at “Error code monitor” mode in message display. Monitoring example of operation state

(Note) Pay attention at following items. LED display at important error will be as following: · Run lamp is turn out and E/A lamp is lit (A pattern) in LED display when ordinal important abnormality is happened. (pattern A). RUN E/A

(Always is lighting)

· Run lamp is light out and ERR lamp flickers (B pattern) when such important abnormal as communication is incapable. In this case error code cannot be read out. Sometimes error code is not stored at special register for error information output. RUN E/A LED display will be following when abnormality is light. · RUN lamp and E/A lamp light. RUN E/A : Light out

: Light on

5-2

Page 63

5.3 DISPLAYED ERRORS TABLE Error items

LED lamps

Error code

POWER

RUN

Error reset

E/A

Special relay Power Reset re-throw IN

Power source

POWER DOWN

0013

Battery

BATTER VOLTAGE LOW

0022

PROGRAM MEMORY SUM CHECK ERROR SUBSIDIARY INFM SUM CHECK ERROR

0#21

VC2 V01

0#23

VC2 V01

UNDEFINED COMMAND

0#24

VC9 V01

SYSTEM CONTROL PROCESSOR ERROR SEQUENCE WORD PROCESSOR ERROR SEQUENCE PROCESSOR CLOCK ERROR SEQUENCE PROCESSOR POWER DOWN

0035

VC0 V01

Memory

CPU

VC1 V01 -

-

VF0 V03

0036

-

-

(0037)

-

-

(0038)

-

-

-

-

SYSTEM RAM ERROR

(0032)

-

SYSTEM INTERRUPT ERROR ADDRESS CONVERSION ERROR SEQUENCE PROCESSOR NO RESPONSE

0039

-

VC0 V01

003A

-

VC0 V01

(003B)

-

-

-

I/O PORT ERROR

(003C)

-

-

-

SEQUENCE PROCESSOR ERROR

(00A1)

-

-

RAM DATA ERROR

00A2

RTC ERROR

00A3

COMMAND PROCESS PROGRAM ERROR COMMAND PROCESS PROGRAM ALARM SYSTEM PROGRAM ERROR

00A4

SYSTEM PROGRAM ALARM

00A7

SEQUENCE PROCESSOR NO RESPONSE

(00A8)

SEQUENCE RAM ERROR

00A9

SYSTEM PARAMETER ALARM BACKUP MEMORY WRITE ERROR

00AA 00AB

VCA V01

BATTERY CIRCUIT ERROR

00AC

VC0 V01

DATA ERROR

00AD

DATA ERROR UNCHECK

00AE

-

-

VCB V03

CLOCK UNSET

00AF

-

-

VF5 V03

VC2 V01 -

-

VC2 V01

00A5

-

-

00A6

#:0~3 0= System related error 1 ~ 3= Program related errors Displaying corresponding program Nos. This is 1 in the case of PC2 interchange mode.

VF5 V03 VC2 V03 VC2 V01

-

-

VC2 V03 -

-

VC0 V01 -

-

VC2 V01/V02

/

/

5-3

VC2 V03

: Lighting : Flashing Note: Occasionally error code is not stored. : Turn out (OFF) : Finally depending on parameter " running status against occurred” But the left (RUN OFF) is set before shipping.

Page 64

LED lamps

I/O

Error code

I/O RACK F USED

0041

-

VC8

V01

I/O RACK NO. OVERLAP

0045

-

VC8

V01

I/O ADDRESS OVERLAP

0046

-

VC8

V01

I/O POWER DOWN

0047

VC1

V01

I/O TABLE VERIFICATION ERROR

0048 004A

VE0

V01/V02

I/O MODULE ERROR

0043

-

VC7

V01

I/O MODULE ALARM

004B

-

VC7

V03

0042

-

VC5

V01

0049

-

VC8

V01

0044

-

VC3

V01

SCAN TIME OVER APPLIED COMMAND ERROR 1 USER PROGRAM STACK-OVER

RUN

E/A

/

0#31

/

VE1 *1 V01/V02

0#71

/

VE2 *2 V02/V01 VC9 *3

V01

0#73

VC9 *3

V01

NO START COMMAND

0#74

VC9

*3

V01

MASTER CONTROL ERROR

0#75

VC9 *3

V01

APPLIED COMMAND ERROR 2 (For special module )

0#78

FOR-NEXT ERROR

0#79

VC9 *3

V01

RET ERROR

0#7A

VC9 *3

V01

0#7B

VC9

*3

V01

LIBRARY CALL ERROR

0#7C

VE2

*2

V02/V01

PRG , END EXECUTE

0#7D

VC9 *3

V01

0#76

VC6

*4

V01

0#77

VC6

*4

V01

RETI ERROR

LABEL TABLE ERROR User setting

POWER

0#72

NO END COMMAND

User program

Special relay

Error items

I/O MODULE PARAMETER ERROR I/O ADDRESS SETTING ERROR I/O ADDRESS BUSPARITY ERROR

I/O bus

Error reset Power re-throw Reset IN

PARAMETER SETUP VALUE ERROR

/

/

#:0~3 0= System related error 1 ~ 3= Program related errors Displaying corresponding program Nos. This is 1 in the case of PC2 interchange mode.

(

/ /

: Lighting : Turn out (OFF) : Finally depending on parameter " running ) status against occurred” But the left (RUN OFF) is set before shipping.

*1 Program-1 ~ -3 : VE8 ~ VEA *3 Program-1 ~ -3 : VD0 ~ VD2

5-4

VE2 *2 V02/V01

*2 Special relay every each program *4 Program-1 ~ -3 : VD8 ~ VDA

Page 65

LED lamps Error items

Error code

SPECIAL MODULE OVER-ALLOCATION SPECIAL MODULE PARAMETER ERROR EXCESSIVE NO. OF INTERRUPT MODULES SPECIAL MODULE NUMBER OVER

RUN

E/A

0081

-

0082

Special relay

VC8

V01

VC5

V01

0083

-

VC8

V01

0088

-

VC8

V01

SPECIAL MODULE ERROR

0#84

VC4

V01

LINK PARAMETER ERROR

0#85

-

V03

0089

VF2

V03

0#86

-

V03

EXTERNAL INTERRUPT ERROR

008A

VC4

V01

NC COMMUNICATION ALARM 1

0#8B

-

V03

NC COMMUNICATION ALARM 2

0#8C

-

V03

2-PORT RAM ALARM

0#8D

-

V03

COMMUNICATION DATA VERIFICATION ALARM 1

0#8E

-

V03

NO MEMORY CARD

0025

VCA

V01

0026

VCA

V01

VF1

V03

VCA

V01

Special module LINK MODULE ALLOCATION ERROR LINK COMMUNICATION ERROR

Memory card

POWER

Error reset Power Reset re-throw IN

MEMORY CARD TRANSFER ERROR MEMORY CARD BATTERY VOLTAGE DROP

DATA

MEMORY ERROR

DATA

CARD

0027

-

0028

#:0~3 0= System related error 1 ~ 3= Program related errors Displaying corresponding program Nos. This is 1 in the case of PC2 interchange mode.

(

5-5

/ /

-

: Lighting : Turn out (OFF) : Finally depending on parameter " running ) status against occurred” But the left (RUN OFF) is set before shipping.

Page 66

5.4 Special Register for Error Information Output If error is detected, error code, error related information and error detection time are stored in the special register to store error information. This register of 8-stage shift register structure can register errors up to 8 maximum. When the number of occurred error (stored errors) exceeds 8, the stored error information are cancelled in the order from the first stored information. (See below) The error information stored in this register can be read by the peripheral equipment (PCwin). Register Content Address New

S200 S20A

Former

HOST Error 0 information

SLAVE Error codes

S200 Error-related information 2 Error-related information 4

Error-related information 1 Error-related information 3

S214

Error 1 information

S201

S21E

Error 2 information

S202

S228

Error 3 information

S203

Error detection time (sec)

S232

Error 4 information

S204

Error detection time (min)

S23C

Error 5 information

S205

Error detection time (hour)

S246

Error 6 information

S206

Error detection time (day)

S24F

Error 7 information

S207

Error detection time (month)

S208

Cancel

S209

Error detection time (year) Error detection time (day of week)

Error detection time (day of week)

(Note 1)Error-related information are stored with hexadecimal number. (Note 2)The current time of the built-in clock is stored. The data represents 1bit at 1 digit in BCD code. (EX. "0102" represents "12". ) Year data is represented by lower two digits of AD year and the "day of week" data is represented by 0 ~ 6, which then correspond to Sunday ~ Saturday.

The information stored in this register are not cleared even after ERROR is reset. Where ERROR clear is required, write "0000" in the register using the peripheral equipment (PCwin).

5-6

Page 67

5.5 Error-related Information The information effective to specify error causes and error-resulted units/devices are stored as " Error-Related Information" covering error items forecast. (stored with hexadecimal value.) Error code

Error content

0013 POWER DOWN 0*21

PROGRAM MEMORY SUM CHECK ERROR

0022 BATTERY VOLTAGE LOW 0*23

SUBSIDIARY INFORMATION SUM CHECK ERROR

0*24 UNDEFINED COMMAND 0*25 NO MEMORY CARD

1

Error-related information 2 3

Area classification *

Sum

Sum data Calculated value

-

-

Sum

-

-

Program counter lower

Program counter upper

-

-

-

-

Memory card data, lower

Memory card data, upper

-

MEMORY CARD DATA TRANSFER ERROR MEMORY CARD BATTERY 0*27 VOLTAGE DROP MEMORY CARD DATA 0*28 ERROR

Address lower

Address upper

-

-

-

-

Sum data

Check sum calculated value

-

-

0*31 SCAN TIME OVER

Classification*

-

-

-

0032 SYSTEM RAM ERROR

Classification*

Address lower

Address upper

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

SYSTEM CONTROL PROCESSOR ERROR SEQUENCE WORD 0036 PROCESSOR ERROR SEQUENCE PROCESSOR 0037 CLOCK ERROR SEQUENCE PROCESSOR 0038 POWER DOWN SYSTEM INTERRUPT Classification* 0039 ERROR ADDRESS CONVERSION 003A ERROR SEQUENCE PROCESSOR 003B NO RESPONSE 0035

003C I/O PORT ERROR

-

-

-

-

0041 I/O RACK F USED

-

-

-

-

Rack No. Slot No.

-

-

Rack No. Slot No.

-

-

Rack No.

-

-

-

-

-

-

-

-

-

-

-

0042

I/O MODULE PARAMETER ERROR

0043 I/O MODULE ERROR 0044

I/O ADDRESS BUS PARITY ERROR

0045 I/O RACK NO. OVERLAP 0046 I/O ADDRESS OVERLAP 0047 I/O POWER DOWN 0048

I/O TABLE REFERENCE ERROR

Rack No. Rack No. (1) (2) -

-

Rack No. Slot No.

5-7

*1:Sequence

-

Sum data Calculated value

Remarks

-

Area classification *

-

0*26

-

4

Registere Mounted d data module

*1: Parameter

*1: Initial 2: Main 3: Overall *1: System RAM

* 0 ~ 7:INT0 ~ 7 FF:NMI

Fuse blown, etc.

Page 68

Error code 0049

Error content I/O ADDRESS SETTING ERROR

1

Error-related information 2 3

Rack No.

-

-

Number

004A I/O TABLE VERIFYING ERROR

Rack No. of slots*

Number of slots in the base

004B I/O MODULE ALARM

Rack No. Slot No.

-

APPLIED COMMAND ERROR 1 0*72 USER PROGRAM STACK-OVER 0*73 NO END COMMAND 0*71

Program counter lower

Program counter upper

* Number of slots judged from I/O table -

Fuse blown, etc

Serial No. Serial No. lower upper

-

-

-

-

-

-

-

-

-

-

-

-

0*75 MASTER CONTROL ERROR

Classification*

MC No.

MCR No.

-

0*76 LABEL TABLE ERROR

Classification *(1)

Classification *(2)

Label Label No. lower No. upper

0*74 NO START COMMAND

Remarks

4

*1: Nest Over 2: Number unmatching 3: No MCR 4: No MC *1-1: JUMP 2:CALL 3: INTERRUPT 4: START 5:EXTENDED LABEL 2-1: NO LABEL 2:UNMATCH 3: OUT OF NO. RANGE

0*77 PARAMETER SETUP VALUE Parameter No. ERROR APPLIED COMMAND Program 0*78 counter lower ERROR 2

Program counter upper

0*79 FOR-NEXT ERROR

Classification*

Program Program counter lower counter upper

-

*l: NO NEXT 2: NO FOR 3:NEST OVER 4: ADDRESS ERROR

0*7A RET ERROR

Classification*

Program Program counter lower counter upper

-

*1: NO RET 2: NO CALL

0*7B RETI ERROR

Classification *1

Program Program counter lower counter *2 upper*2

-

-

LIBRARY CALL ERROR

Classification *1

Classification *2

ERROR IN LIBRARY

Step No. Step No. lower upper of of calling calling source source

0*7C

0*7D PRG . END EXECUTE

-

-

0081 SPECIAL MODULE ALLOCATION OVER SPECIAL MODULE 0082 Rack No. Slot No. PARAMETER ERROR EXCESSIVE NO.OF INTERRUPT 0083 MODULES -

5-8

-

-

Serial No. Serial No. I/O error with special module lower upper

*1 *2

1:NO RETI 2:NO INTERRUPT Interrupt level in case of no RETI

*1 Error during FB (Library) Call 1: It is not Library-enabled 2 Library is already under execution. (Library was called from inside the library) 3: Label Number is outside the scope 4: Label Life is over Label Label No. lower No. upper 5: Label Number is not matching 6: SYS415 is not there 7: It is not useable program number 8: It is not useable operation pattern A: The library impracticable *2 A: FB library B: User library C:standard library -

-

-

-

-

-

-

-

-

-

No END or RET, RETI commands

Interrupt module: Max. 4 pcs.

Page 69

Error code

Error-related information 2 3 Classification Rack Slot No. * No.

4

Link No.

-

-

-

Link No.

-

-

-

-

-

-

-

Slot No.

-

-

INTERRUP T LAVEL*

-

-

-

008B NC COMMUNICATION ALARM 1

Classificatio n*

NCOK value

PCOK value

-

008C NC COMMUNICATION ALARM 2

Classificatio n*

Refresh 00: Data 01: Command

-

-

1

Write data

Read data

-

Data bus alarm

2

-

-

-

Address bus alarm

Error content

0084 SPECIAL MODULE ERROR 0*85 LINK PARAMETER ERROR LINK COMMUNICATION ERROR SPECIAL MODULE OVER 0088 QUANTITY LINK MODULE 0*89 ALLOCATION ERROR EXTERNAL INTERRUPT 0*8A ERROR 0086

008D 2-PORT RAM ALARM

1

Rack No.

-

008E VERIFICATION ALARM 1

Lower Higher order order of of address address

00A2 RAM DATA ERROR

Classification *

-

-

-

00A3 RTC ERROR

Classification *

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

SEQUENCE PROCESSOR NO RESPONSE

-

-

-

-

00A9 SEQUENCE RAM ERROR

-

-

-

-

Classification *

-

-

-

-

-

-

-

00AC BATTERY CIRCUIT FAULT

-

-

-

-

00AD DATA ERROR

-

-

-

-

00AE DATA ERROR NON-CHECK

-

-

-

-

00AF CLOCK NON-SETUP

-

-

-

-

COMMUNICATION DATA

COMMAND PROCESSOR PROGRAM ERROR COMMAND PROCESSOR 00A5 PROGRAM ALARM SYSTEM PROGRAM Classification 00A6 * ERROR 00A4

00A7 SYSTEM PROGRAM ALARM 00A8

SYSTEM PARAMETER ALARM BACK-UP MEMORY WRITE 00AB ERROR 00AA

5-9

Read data

Remarks *1: ALM 2: CPU DETECT 3: I/O MODULE DETECT

No link parameter setup *FF in case of no cause *1: NCOK is turned on. 2: NCOK keeps turned off for one minute. 3: NCOK is turned off. * 1: PC-to-NC communication stop 2: NC-to-PC communication stop

Write data

* 1: I/F

2: Back-up

*1: ROM

2: RAM

*1: ROM

2: RAM