5.6 Error message
Lowest two digits errorcode
The error codes ,the error messages and the error informations are displayed on the PC3JD ,PC3JG , PC3JG-P. The error codes are displayed on the PC3JB ,PC3JB-G , PC3JB-GP. The lower 2 digits are displayed on the PC3JL. Other CPU has no display function.
Error message
13 ER#:0013
Error content
ER#:0*21
21 MEM.PARITY ERROR Program memory sum check error ER#:0022
22 BATTERY ALARM ER#:0023
Auxiliary
ER#:0*24
24 UNDEFINED CODE ER#:0025
25 NO IC-CARD information
PRG:* PC :****
Program number sum
Undefined command
ER#:0026
Memory error
ER#:0027
Memory card battery voltage drop
27 IC-CARD BAT. ALM ER#:0028
28 IC-CARD DATA ERR ER#:0*31 SCAN TIME OVER ER#:0322 RAM card data
Memory card data error
PRG:* INITIAL
Scan time over
PRG:* MAIN
PRG:ALL
Program number (ALL in case of total.) Main and initial
System RAM abnormal
ER#:0035 System control SYSTEM CPU ERROR abnormal ER#:0036 transfer processor
36 WORD CPU ERROR
Word processor error
ER#:0037 BIT CPU ERROR
Bit processor clock error
37
Program number
No m memory card
26 IC-CARD READ ERR
35
PRG:*
Battery voltage drop
23 PARAMETER ERROR check error
32 SYSTEM
Detailed information content
Power down
POWER DOWN
31
Error information
ER#:0038
38 BIT CPU PWR.DOWN Bit processor power down ER#:0039
39 SYSTEM INT.ERR. ER#:003A
3A ADDR. CONV.ERR. 3B
ER#:003B BIT CPU ACK ERR ER#:003C
3C SYSTEM I/O ERR. 41
ER#:0041 RACK NO.F USED ER#:0042
42 I/O PARAM.ERROR ER#:0043
43 I/O MODULE ERR.1 ER#:0044
44 BUS PARITY ERR. ER#:0045
45 RACK NO. ERROR ER#:0046
46 I/O ADDRESS ERR. ER#:0047
47 I/O POWER DOWN ER#:0048
48 MODULE VERIFY ER
System interrupt abnormal Address conversion error Bit processing processor no response I/O port abnormal I/O rack F using I/O module abnormal parameter RACK:*
I/O module abnormal I/O address bypass parity error
I/O address overlap
ER#:004B
4B I/O MODULE ALARM ER#:0*71
71 FUNCTION ERROR 1 ER#:0*72
72 STACK OVERFLOW ER#:0*73
73 END NOT EXECUTE ER#:0022
74 START NOT EXEC. ER#:0*75
Rack
RACK:*,*
Rack (Duplicated two)
RACK:* SLOT:* RACK:*
Rack Slot
I/O power source power down I/O table collate error
ER#:0049
ER#:004A
Rack Slot
I/O rack No. overlap
49 RACK ADDR. ERROR I/O address setting abnormal 4A RACK VERIFY ERR.
Rack Slot
SLOT:* RACK:* SLOT:* RACK:*
Rack Slot
I/O table verifying error I/O module alarm Application command error 1 User program stack over No end command No start command
75 MADTER CONT REE. Master control error
PRG:* PC :**** PRG:*
PRG:* SER:****
Program number Program counter and serial number (alternately displayed) Program number
PRG:*
Program number
PRG:*
Program number
NEST
NO MC
MC : ***
MCR: ***
NO MCR NO. ERR Classification (nest over, without MC and MCR and number not agreed) MC : *** MC : *** Display either MC No. or MCR No. depending on classification
5-10
Page 71
Lowest two digits errorcode
Error message
76 ER#:0*76 LABEL ERROR 77 78 79 7A 7B 7C
PRG. PARAM. ERR. ER#:0*78 FUNCTION ERROR 2 ER#:0*79 FOR - NEXT ERROR ER#:0*7A
ER#:0*7B
ER#:0*7C
PRG. FORMAT ERR. FUNC. I/O OVER 2 ER#0082
82 I/O PARAM. ERROR ER#0083
83 INT. MODULE OVER ER#:0084
84 I/O MADULE ERR.2 ER#:0*85
85 LINK PARAM. ERR. ER#:0*86
86 LINK ALARM ER#:0088
88 FUNC. I/O OVER 1 ER#:0089
89 FUNC. I/O ALARM ER#:008A
8A INT. MODULE ERR.
Application command error 2 PRG:* (special module) PC :****
ER#:00A1
FOR - NEXT error
PC :****
ER#:00A2 ER#:00A3
A3 CLOCK ERROR
PC :****
PC :****
Program counter Classification (without return and no call)
PC :****
Program counter
PC :****
L ****
**** parameter RACK:*
Special module abnormal
L ****
Detail classification ( note 1), Label number
Excessive modules
No.
Rack Slot
SLOT:* of interrupt
RACK:* SLOT:* PRG :* Link parameter abnormal LINK:* PRG :* Link communication abnormal LINK:*
Rack Slot
Special module abnormal
Program Link number Program Link number
Special module number over Link module abnormal allocation RACK:*
Rack (built-in link: L1and L2 = F, DLNK = 0) Slot (built-in link: L1and L2 = F, DLNK = 0)
SLOT:*
External interrupt error processing
RAM data abnormal
Command processing portion program alarm
ER#:00A6 ER#:00A7
A7 SYSTEM PROG. ALM ER#:00A8 SEQ. CPU ACK ERR ER#:00A9
RAM
ER#:00AA SYSTEM PARM. ALM ER#:00AB
AB FLASH WRITE ERR ER#:00AC
AC BATT.CIRCUIT ERR ER#:00AD
AD DATA ERROR ER#:00AE NO CHECK DATA ER ER#:00AF
PC :****
Special module allocation over
ER#:00A5
AF CLOCK NOT SET
Program counter and serial number (alternately displayed)
PRG. END execution
Command processing portion program abnormal
A6 SYSTEM PROG. ERR
AE
Program number
SER:****
RTC abnormal
A5 SEQ.CPU PRG. ALM
AA
PRG:*
NO RET NO CALL
****
ER#:00A4 SEQ.CPU PRG. ERR
A9 SEQUENCE
Classification (without label and start/number out of range) Label number (either jump, call or extended label is displayed.)
STD LIB STD LIB USR LIB USR LIB Classification (Standard library, User Library)
Sequence
A2 RPM DATA ERROR
A8
START
EL****
NO NEXT NO FOR NEST ERR ADR. ERR Classification (without NEXT and FOR, nest and address over)
A1 SEQUENCE CPU ERR processor abnormal
A4
NO ERR
Parameter set value abnormal
Library call error
LIB CALL ERROR
ER#:0081
NO S***
Detailed information content
RETI error
RETI ERROR
81
NO L***
RET error
RET ERROR
7D
Error information
Label table error
ER#:0*77
ER#:0*7D
Error content
System program abnormal System program alarm Sequence processing processor no response Sequence RAM abnormal System parameter alarm Backup program writing error memory
Battery circuit abnormal Data abnormal Data abnormality confirmed.
is not
Clock is not set.
Mark “ # ” in error message column is error number and mark “ * “ is program number. note 1 : NOT ENB : It is not Library-enabled LIB RUN : Library is already executed. (Library was called from inside the library) NO. ERR : Label Number is outside the scope NO LABEL : Label Life is over NO. ERR : Label Number is not matching NO START : SYS415 is not there PRG ERR : It is not useable program number MODE ERR : It is not useable operation pattern
5-11
Page 72
5.7 Counteraction against CPU error This Chapter is to help maintenance men search true cause(s) and take proper counteraction/corrective action against it, when an equipment using TOYOPUC-PC3JG fails to work normally due to somewhat cause. All maintenance men concerned are requested to read carefully the contents of other Chapters and Sections in this manual and the Programming Manual, before reading this Chapter, in order to fully know the functions of PC3JG and the programming procedure.
Kinds of error causes Main causes which result in abnormal operation (generally operation stop) of the lines controlled can be mainly classified as follows by each devices. (1) Trouble of input and output devices (limit switch, solenoid valve, etc.) (2) Fault of control circuits (program) (3) Trouble of TOYOPUC itself (a) Trouble of I/O Module (b) Trouble of CPU Module (c) Trouble of I/O cable This Chapter describes the troubles and causes in item-(2) and -(3). Trouble-shooting (1) Items to be first checked 1. Do two or more errors occur or not simultaneously? If the error code display unit displays different error codes alternately at 2-sec interval, it shows simultaneous occurrence of two or more errors. In such a case, check the time of error occurrence from the register data wherein error information is stored, and perform troubleshooting in the order from firstly occurred error. 2. Check the error-related information. Check the error-related information and the time of error occurrence using an peripheral device and use them as an reference information for trouble-shooting.
New and former errors in Error History Error 0 New Error 7 Former
(2) How to proceed with "Trouble-Shooting" Analyze causes in reference to Para. 5-7-1 "Self-Diagnosis Items and Presumed Causes" or Para. 5-7-2 "Error Check Flow Chart". when not restoring after trouble-shooting, check the installation of CPU module and I/O module, and check the connection of I/O cables. If not restoring yet, exchange CPU modules, selector modules, power modules, I/O modules, I/O cables or bases. gProcedure of CPU module exchange
Please do the exchange work according to the following procedures when you exchange CPU module as a result of the troubleshooting. ! The backup of the program + parameter and register (other data if necessary) is taken from the PC3JG module. " The power supply is turned off. #The wiring for the PC3JG module is removed, and the PC3JG module is detached. $ A new PC3JG module is prepared, the battery is connected, and the switch is set. % The new PC3JG module is mounted, and wiring is returned like being original it. & The power supply is turned on. ' The program + parameter and register (other data if necessary) to backup by ! are written in a new PC3JG module. ( Time is set.
5-12
Page 73
5.7.1 Error code
Self-diagnosis items and presumed (possible) causes Error
Description
Presumed (possible) main causes
Counteractions, corrective actions
13 POWER DOWN
Drop of 5V power voltage (1) AC input voltage out of the rated range in CPU module Drop of (2) Trouble of power module 5V power voltage in CPU (3)Instantaneous interruption of AC power module
(1)Input the rated voltage. (2)Replace the power module. (3)Turn ON the RESET - START switch or re-switch ON the power.
21 PROGRAM MEMORY SUM CHECK ERROR
Unmatching of program area data to sum check data
(1) Program memory was rewritten due to affect by external over noise, etc. (2) Trouble of memory element
(1)Rewrite program (2)Replace CPU module.
(1) Lithium battery is dead. (2) Lithium battery is not connected.
(1)Replace the lithium battery. (2)Connect the lithium battery.
22 BATTERY VOLTAGE Voltage of lithium battery DROP for memory back-up is weak.
5-13
23 ATTENDANT INFOR- MATION SUM CHECK ERROR 24 UNDEFINED INSTRUCTION
Unmatching of parameter (3) Program memory was rewritten due to area data to check sum affect by external over-noise, etc. data (4) Trouble of memory element
(1)Rewrite parameter (2)Replace CPU module.
Undefined command was (1)Write-processing was interrupted due to (1) Rewrite program detected while sequence disconnection of the connecting cable while (2) Revise and rewrite program. program is in run. program is being written by the programmer. (3) Rewrite program. (2)Undefined command existed in writing (4) Replace CPU module. program by CPU Link. (3) Program memory was rewritten due to affect by external over-noise, etc. (4) Trouble of memory element 25 NO MEMORY CARD With no memory card (1) Bad installation of the memory card. (1) Install the memory card securely. mounted, a transfer of (2) The memory card is not installed in the (2) Install the memory card or switch to the data from the memory memory card run mode. internal memory run mode. card to the CPU was attempted. 26 MEMORY CARD After data is transferred (1) Bad installation. (1) Install the memory card securely. DATA TRANSFER from the memory card to ERROR the CPU, a verifying error occurred.
Page 74
Error code
Error
Description
Presumed (possible) main causes
Counteractions, corrective actions
5-14
27 MEMORY CARD The voltage of lithium (1) The lithium battery is dead. BATTERY VOLTAGE battery in the RAM card is (2) The lithium battery is not mounted. DROP low. (3) The memory card is not mounted securely.
(1) Replace the lithium battery. (2) Mount the lithium battery securely. (3) Mount the memory card securely.
28 MEMORY CARD DATA ERROR
A sum check error is found in the data in the memory card.
(1) The data on the memory card is destroyed. (2) Bad installation of the memory card.
(1) Rewrite to the memory card. (2) Install the memory card securely.
35 SYSTEM CPU ERROR
Abnormally long processing time in System Control Processor
(1) Overrun of System Control Processor due to affect by external over-noise, etc. (2) Trouble of CPU module
(1) Turn ON the RESET - START switch or re-switch ON the power. (2) Replace CPU module.
36 WORD CPU ERROR Abnormally long (1) Overrun of System Control Processor processing time in Word due to affect by external over-noise, etc. Processor (2) Trouble of CPU module
(1) Turn ON the RESET - START switch or re-switch ON the power. (2) Replace CPU module.
37 BIT CPU CLOCK ERROR
(1) Turn ON the RESET-START switch or reswitch ON the power. (2) Replace CPU module.
38 BIT CPU POWER DOWN 32 SYSTEM RAM ERROR
System clock in the bit (1) The bit processor mis-operated due to processor over-counted in affect by external over- noise, etc. excess to the specified (2) Trouble of CPU module. time. Bit processor detected (1) The bit processor mis-operated due to power-down signal. affect by external over-noise, etc. (2) Trouble of CPU module. CPU module is unable to (1) The system RAM was written due to read correctly the data affect by external over-noise, etc. written in System RAM. (2) Trouble of CPU module. "Factor-unknown (1) External over-noise was input. interrupt" was input in the (2)Improper installation of CPU module system control processor. External I/O address (1) Failure of CPU module. conversion is incorrect.
39 SYSTEM INTERRUPTION ERROR 3A ADDRESS CONVERSION ERROR 3B BIT CPU, NO The bit processor does ACKNOWLEDGEME not respond to request NT from the system control processor.
(1) Trouble of CPU module
(1)Turn ON the RESET-START switch or reswitch ON the power. (2) Replace CPU module. (1) Turn ON the RESET-START switch or reswitch ON the power. (2) Replace CPU module. (1)Turn ON the RESET - START switch or reswitch ON the power. (2) Exactly install CPU module. (1) Replace the CPU module. (1) Replace CPU module.
Page 75
Error code
Error
3C I/O PORT ERROR 41 45
46
5-15
47
48 4A
Description
Presumed (possible) main causes
Counteractions, corrective actions
Improper I/O port data in (1) Trouble of CPU module (1) Replace CPU module. the system control processor I/O RACK F USED Rack No. selector SW on (1) Setup error (1) Re-set Rack No. selector switch to other Selector Module than "F". is set to "F". I/O RACK NO. The rack No. selector (1) Wrong setting. (1) Clear the overlap in the settings of the OVERLAP switch on the I/O power rack No. selector switch. module is set at 0 or overlapped with another rack No. I/O ADDRESS Interference exists (1)I/O ADDRESS selector switch on the (1)Set I/O ADDRESS selector switch OVERLAP between address area selector module is mis-set. properly. which is occupied by one I/O rack and other address area which is occupied by other I/O rack . I/O POWER (1)Input the rated voltage. Drop of 5V power voltage (1)AC input voltage out of rated voltage SUPPLY POWER (2)Keep the setup sum of power at additional I/O Rack range was input in the power module. DOWN side. (2)Over-current consumption of I/O module consumption of I/O module on the base within the rated output current range. installed on the base (3)Trouble of power module in additional I/O (3)Replace power module. (4)Unify the CPU power source and I/O rack unit (4)Additional I/O rack power is not switched power source to same line. ON despite that the power of CPU rack unit (5)Turn ON the RESET-START switch or reswitch ON the power. is switched. (6)Install a power module on additional I/O (5)Instantaneous interruption of AC input power was detected at additional I/O Rack Rack side and wire 5V cable. side only. (6)Power module is not installed on additional I/O Rack side and, in addition, 5V cable not wired. I/O TABLE The actual-install (1)Parameter mis-setup (1) Set parameter correctly. VERIFYING ERROR condition of I/O module (2)Faulty mounting of CPU or selector or I/O (2) Exactly mount the module. differs that set up as module (3) Mount proper I/O module. parameter. (3)Wrong I/O module mounted. (4) Set rack No. correctly. (4)Rack No. of selector module was mis-set. (5) Exactly wire I/O cable. (5)I/O cable wired improperly.
Page 76
Error code
Error
43 I/O MODULE ERROR
4B I/O MODULE ALARM
Description
Presumed (possible) main causes
Error occurred in high (1) Fuse blown in Output module. function unit (high speed (2)Error occurred in high function module. counter, etc.) which occupies output module or I/O address. Error occurred in I/O (1) Fuse blown in Output module. module.
Counteractions, corrective actions (1)Replace fuse. (2)Reset ERROR in reference to the individual instruction manual for each module. (1)Replace fuse.
42 I/O MODULE PARAMETER ERROR 49 I/O ADDRESS SETUP ERROR
5-16
Occupied-point parameter (1)Faulty mounting of I/O module (1) Exactly mount I/O module. value in I/O module is (2)Trouble of I/O module (2) Replace I/O module. error. (3) Trouble of base module (3) Replace base module. Setup I/O address (1) Allocated I/O address exceeds "1FF". (1) Change I/O address allocation. exceeds the specified (2) Trouble of I/O ADDRESS selector SW on (2) Replace the selector module. value. selector module. 44 I/O ADDRESS BUS Parity error of address (1) Faulty connection of I/O cable (1) Exactly connect I/O cable. PARITY ERROR bus was detected in (2) Disconnection of I/O cable (2) Replace I/O cable. selector module. (3) Address data changed due to affect by (3) Turn ON the RESET- START SW or external over-noise, etc. re-switch ON the power. 31 SCAN TIME OVER Execution time in (1) Improper scan time timer value in (1) Re-set scan time timer value to proper sequence program parameter value. exceeded the scan time (2) Processing time over of sequence (2) Revise sequence program. timer value which was set program (3) Revise sequence program. up in parameter. (3) Infinite loop structure exists on midway of sequence program. 71 APPLICATION Operand value of applied (1) Operand value of applied command and (1) Revise sequence program. INSTRUCTION command and operation operation result are out of the respective (2) Revise sequence program or data. ERROR 1 result are out of the specified ranges. respective specified (2) Different form of operation data (BCD, ranges. BIN) 72 USER PROGRAM STACK-OVER
Stack area for sequence program is short. (Stack for sub- routine and interrupt) 73 END INSTRUCTION No END command was NOT EXECUTED executed while START command is executed twice.
(1) User program calls itself within subroutine.
(1) Revise sequence program.
(1) No END command in sequence program (1) Add END command. (2) Two or more START commands are (2) Unify START commands into one contained in sequence program. command. (3) Program is such a structure as jumps (3) Revise sequence program. END command.
Page 77
Error code
Error
Description
Presumed (possible) main causes
Counteractions, corrective actions
5-17
74 START END command was (1) No START command is contained in (1) Add START command. INSTRUCTION NOT executed without sequence program. (2) Revise sequence program. EXECUTED executing START (2) Program is such a structure as jumps command. START command. 75 MASTER CONTROL How to use MC command (1) Nesting of master control exceeds 16 (1) Keep the nesting within 16 multiple. ERROR and MCR command is multiple. (2) Use MC command and MCR commandin wrong. (2) MC command and MCR command are pair. not a pair. 78 APPLICATION Applied command can not (1) Applied command was executed for the (1) Mount special I/O module. INSTRUCTION be executed normally for slot wherein applicable special I/O module is (2) Replace special I/O module. ERROR 2 special I/O module. not mounted. (2) Trouble of special I/O module 79 FOR-NEXT ERROR FOR - NEXT command or (1) FOR command or FORN command are (1) Use FOR command or FORN command how to use FOR- NEXT available, but no NEXT command is and NEXT command in pair. are wrong. available. (2) Use FOR command or FORN command (2) NEXT command is available, but neither and NEXT command in pair. FOR command nor FORN command (3) Keep the nesting within 128 multiple. available. (3) FOR-NEXT command or nesting of FOR-NEXT command exceeds 128 multiple. 7A RET ERROR How to use CALL (1) CALL command is available, but (1) Use CALL command and RET command command or RET corresponding RET command not available. in pair. command is wrong. (2) RET command is available, but (2) Use CALL command and RET command corresponding CALL command not available. in pair. The configuration of the 7B RETI error (1) The RETI instruction is not found at the (1) Add the RETI instruction. sequence interrupt program end of the sequence interrupt program. (2) Delete the RETI instruction. is wrong. (2) The RETI instruction is used in the program other than the sequence interrupt program. Error during FB (Library) Call (1) It is not Library-enabled Revise sequence program. 7C LIBRARY CALL ERROR (2) Library is already under execution. (Library was called from inside the library) (3) Label Number is outside the scope (4) Label Life is over (5) Label Number is not matching (6) SYS415 is not there (7) It is not useable program number (8) It is not useable operation pattern (9) The user library is used when program capacity in P2 is 32Kw or more. The standard library is used when program capacity in P3 is 32Kw or more.*1
Page 78
Error code
Error
Description
7D PRG. END EXECUTION
PEND command executed.
Presumed (possible) main causes
Counteractions, corrective actions
(1) No END command is contained in (1) Add END command. sequence program. (2) Add RET or RETI command. (2) No RET or RETI command is contained in subroutine. 76 LABEL TABLE No LABEL command at a (1) JMP command available, but no LABEL (1) Revise sequence program. ERROR selected jump destination command available at the jump destination. (2) Revise sequence program. (2) CALL command available, but no LABEL command at the jump destination. 77 PARAMETER SETUP- Parameter setup value (1) Parameter memory was rewritten due to (1) Rewrite parameter. VALUE ERROR out of the specified range affect by external over- noise. (2) Rewrite parameter. (2) Data out of the specified range was written in writing para-meters by CPU Link. 81 SPECIAL MODULE Total common memory (1) Too many special modules in use (1) Decrease the number of special modules ALLOCATION-OVER capacity of special in use. modules exceeded 60k bytes.
5-18
82 SPECIAL MODULE Abnormal value of PARAMETER ERROR memory capacity parameter in special module
(1) Faulty mounting of special module (2) Trouble of special module (3) Trouble of base
(1) Exactly mount special module. (2) Replace special module. (3) Replace the base.
83 EXCESSIVE NUMBER The number of external (1) The number of external interrupt modules (1) Decrease the number of external OF INTERRUPT, interrupt modules exceeds 4. interrupt modules. MODULES exceeds 4. 84 SPECIAL MODULE Error occurred in special (1) Error occurred in special module. (1) Reset ERROR in reference to the ERROR module. (2) Faulty mounting of CPU or selector individual instruction manual for special module or special module. module. (2) Exactly mount. 85 LINK PARAMETER Error of Link Parameter (1) Error in Link Parameter setup (1) Revise Link parameter. ERROR 86 LINK Error occurred in (1) Error occurred in communication by link (1) Reset ERROR in reference to the COMMUNICATION communication by link module. individual instruction manual for each link ERROR module. module.
Page 79
Error code
Error
Description
Presumed (possible) main causes
Counteractions, corrective actions
5-19
88 EXCESSIVE NO. OF The quantity of special (1) The quantity of special modules in use (1) Decrease the quantity of special modules SPECIAL MODULES modules exceeds 15. exceeds 15. in use. 89 LINK MODULE Error in the first 4 bytes, (1) Error in link module allocation (1) Revise link module allocation ALLOCATION of link module allocation parameters. parameters. ERROR parameters. EXTERNAL (1) The interrupt occurred because of (1) Reset or turn the power on again. The factor of the 8A excessive external noises.. (2) Replace the external interrupt module. INTERRUPT ERROR external interrupt is (2) Failure of the external interrupt module. unknown. NC COMMUNICATION (1)Securely install the NC and PC A communication alarm (1)Improperly installed NC or PC module 8B ALARM 1 (2)Failure of NC or PC module modules. occurred between NC (2)Replace the NC and PC modules. and PC. NC COMMUNICATION (1)Securely install the NC and PC A communication alarm (1)Improperly installed NC or PC module 8C ALARM 2 (2)Failure of NC or PC module modules. occurred between NC (2)Replace the NC and PC modules. and PC. 2-PORT RAM (1)Securely install the NC and PC An alarm occurred to the (1)Improperly installed NC or PC module 8D ALARM modules. address bus or data bus (2)Failure of NC or PC module (2)Replace the NC and PC modules. of the 2-port RAM. COMMUNICATION DATA Alarm in verification of (1)Improperly installed NC or PC module (1)Securely install the NC and PC 8E VERIFICATION ALARM 1 (2)Failure of NC or PC module modules. written data (2)Replace the NC and PC modules. Abnormality is generated (1)Malfunction is occurred due to excessive (1)Reset and start or re-close power SEQUENCE A1 in sequence processing PROCESSOR noise from outside. source. processor. ERROR (2) Failure of CPU module. (2)Replace CPU module. RAM DATA ERROR A2 RAM data is broken. (1) RAM data is broken due to excessive (1)Reset and start or re-close power noise from outside. source. (2) Failure of CPU module. (2)Replace CPU module. RTC ERROR A3 Abnormality is generated (1)Malfunction is occurred due to excessive (1)Reset and start or re-close power at RTC. noise from outside. source. (2) Failure of CPU module. (2)Replace CPU module. COMMAND (1) Program at command processing A4 Abnormality is generated (1)Reset and start or re-close power source. PROCESSOR portion is broken due to excessive noise at command processing (2)Replace CPU module. PROGRAM ERROR from outside. portion. (2) Failure of CPU module. A5
COMMAND PROCESSOR PROGRAM ALARM
Program recovery is executed.
(1) Battery is not charged enough. (2) Malfunction is occurred due to excessive noise from outside. (3) Failure of CPU module.
(1) Reset and start or re-close power source. (2) Replace CPU module.