Page 21

Pulse output The pulse output module performs independent single-axis simple-position control of a servo motor or stepping motor, which is combined with a pulse-input type motor driver. ● Operation mode control, - Pulses are output until reaching to the command position. signal positioning, - At the stop command ON, pulses are decreased and then stopped. This operation can be performed by a travel completion signal or an external signal using together with positioning control., - Speed change at real-time is possible. of command pulse amount, - Pulse are output at the amount of command. The amount of command pulse can be changed at a real-time., - Pulses are output at a step of 1, 10, 100, 1000 pulses.

Others ・Backlash compensation ●

・Setting of current position

Model

・Teaching

PC10G / PC3J

Name

PULSE OUTPUT

Type

THK-5109

No.of control axes

1

Position command range

-134,217,728-134,217,727 pulse

Acceleration pattern

Trapezoidal

Feed rate

(1-8192) ×30pps (max 245,730pps)

Output

No.of points

2

Signals

Forward pulse, reverse pulse

Rated load voltage

5−24VDC

Max. load current

50mA/signal

Input

No.of points Signals

7 Origin, near origin, +limit, −limit, external positioning signal, in position, operable

Rated load voltage

24V DC (5V input possible for origin, in position)

Rated input current

10mA

*AS-i is an open network of AS-international (AS-i association).

20

Page 22

TOYOPUC-PC10/PC3J

High-performance analog input

8 channels and 16-bit high resolution are available (using PC10 mode)

Very high precision ±0.3% (using PC10 mode)

Very high conversion speed at 60 μ sec/channel (using PC10 mode) Model

PC10G / PC3J

Name

AD10

Type

TCK-6529

Mode Analog input range

PC10 mode

Conventional I/O mode

−10〜+10V、0〜+10V、 0〜+5V、+1〜+5V、 0〜20mA、4〜20mA

0〜+10V、0〜+5V、 +1〜+5V、 0〜20mA、4〜20mA

Digital output

User range

16 Bit With Sign

Extended I/O mode −10〜+10V、0〜+10V、 0〜+5V、+1〜+5V、 0〜20mA、4〜20mA

12 Bit Binary

16 Bit With Sign

Resolution

1/32000

1/24000

1/4000

1/32000

1/24000

Total accuracy

±0.3%

±1.5%

±0.4%

±0.3%

±1.5%

Conversion speed

60 μs/channel

Number of channels

8 channels

Range selection

Settings for every channel

4 channels

3 channels All channel same

Input impedance

Voltage 1M ohm Current 250 ohms

Maximum input

Voltage±15V Current ±30mA

Wire length

Less than 30m (to avoid noise influence , please shorten as much as possible.)

Isolation

Insulation by an isolator (between a PLC-analog input) Non-isolation between analog input channels.

I/O Address Occupied I/O point by link parameters by mounting positions (I/O handling).

0 point

64 points

Analogue output An analog output module will be arranged depending on output specifications. Analogue output 2channels/module

●

Resolution 1/4095

●

Conversion speed 2.5mS

●

Voltage output or current output selectable

●

Model

PC10G / PC3J

Description

Analogue output

Name

DA-1

DA-2

Type

THK-7931

THK-7932

Input Output Conversion speed No.of channels Resolution Overall accuracy Power supply

12-bit binary data/channel 1〜5V

4〜20mA

0〜10V 2.5ms 2 Full scale/4095 ±1%FS

External power supply 24VDC±10%, internal power supply 5VDC

Max.input, Max.output

Voltage output 10V (External load 670Ω or over) , current output 20mA (Extenal load 400Ω or less)

I/O points occupied

21

User range

32 points

Page 23

High-speed counter This module enables counting and comparison of high speed input that cannot be tracked by the counter command and input module of PLC.

●

CT10 has improved the function of the conventional high speed counter module and had been made to support RoHS.

●

Supports 2 channels

●

Supports differential inputting (RS422).

●

Supports high speed pulse of max. 8 Mpps.

●

Model

PC10G/PC3J

Name

CT10

Type

TCK-6856

Mode Applied PLC model No. of channels Counting input Signal level

PC10 Mode

Conventional high speed counter mode

PC10G

PC10G/ PC3J

2

1

1-phase addition/subtraction 2-phase addition/subtraction 2-phase phase difference (Multiplications of 1, 2 and 4)

DC input Differential input

Counting speed (Max.)

Counting range No. of comparison points Comparison output I/O points occupied

24 / 12 / 5V RS-422 8 Mpps during differential input (2-phase, multiplication 4) 200 kpps during DC input (2-phase, multiplication 4) 32 bit without symbol 32 bit with symbol Internal: 8 points at all CH External: 8 points shared by CH 1 and 2

Does not support 50 kpps during DC input 24 bit without symbol 24 bit with symbol Internal: 8 points External: 6 points

ON when the value in within preset comparison range. 0 point

Non-polar 64 points

22

Page 24

TOYOPUC-PC10/PC3J Configuration Input module

Base (Use the specific base for PC2 JS/JR) DC24V IN-22H

IN-SW

THK- 6831

THK-5977

8-slot base (2) THR-2872

8-slot base

THR-2766

6-slot base

THR-2813

4-slot base

THR-2775

2-slot base

THR-2814

Output module TRIAC

Independent Relay contact

TRIAC

TRIAC

Relay contact

Transistor Transistor Transistor Transistor (−)common (+)common (−)common (+)common

FET (−) common

FET (+) common

Input/output module I/O-328G

THK-6905

I/O-329G

THK-6410

Communication module Multi-link ML10

High-speed PC link HPC-LINK

High-speed remote High-speed remote I/O Master station I/O Satellite station RMT-I/O S RMT-I/O M

TCU-6903

I/O branch module

Selector base

Serial I/O SIO

2PORT-EFR

I/O cable

8-slot selector base

THR-5643

6-slot selector base

THR-5644

4-slot selector base

THR-5645

THU-6404

Special module Analogue input AD10

Analogue output DA1-DA2

Pulse output PULSE-OUT

High-speed counter CT10

TCK-6856

23

Motion controller MCML

TCI-6721

Motion controller MCSSC

TCI-6805

Page 25

PC10G

Peripheral equipment

Windows 2000/XP/Vista/7

PC10G-CPU TCC-6353

PLC built into a robot controller with PCI bus

PC10P dedicated extension module

USB* connection

USB* connection

PC10P-CPU TCC-6372

TOYOPUC BUS-EXP (EXPANDED BUS) TCU-6367

PlusBUS-EX Printer

CPU module of PC3JX and PC3JX-D (Purchased on the market)

*Recommended USB cable

PC3JX TCC-6901

Elecom-made USB2-FS05 USB2-FS15 USB2-FS3 UC2-BN07BK UC2-BN10BK UC2-BN15BK UC2-BN20BK UC2-BN30BK UC2-BN50BK

PC3JX-D TCC-6902

Selector module

0.5m 1.5m 3.0m 0.7m 1.0m 1.5m 2.0m 3.0m 5.0m

Power module

24

Page 26

Board type PLC

Board type PLC TOYOPUC-Plus

Evolving in line with change, from manual to semiautomatic, then on to fully-automatic equipment The ideal board-type PLC for built-in application. ■ It is possible to configure everything from the independent control of manual equipment to the decentralized control of fully-automatic equipment. ■

Achieving the simple configuration of equipment control TOYOPUC-Plus, being only the size of a postcard, works away diligently behind-the-scenes. By having TOYOPUC-Plus built in to your operation panel, a simple control system with an equipment control function is possible. Functions can be built freely depending on screen data and sequence programs, and external devices can be connected through communication. Connection with the upper server/PCs Ethernet*

Connection with other equipment/processes FL-net*

Connection with remote I/O FL Remote/EtherCAT*/DeviceNet*

An example of a PLC box installed separately from the operation panel

PC/CMP/SN-I/F

*Ethernet is a registered trademark of Fuji Xerox. *FL-net is the controller level network (OPCN-2) stipulated by JEMA (The Japan Electrical Manufacturers' Association) *EtherCAT is a registered trademark of Beckhoff Automation GmbH. *DeviceNet is a registered trademark of Open DeviceNet Vendor Association Inc. *CC-Link is a registered trademark of Mitsubishi Electric Corporation. *MECHATROLINK is a registered trademark of MECHATROLINK Association. *SSCNET is a registered trademark of Mitsubishi Electric Corporation.

25

Ethernet*/FL-net*/FL Remote/ EtherNetIP/EtherCAT*

Page 27

It can be expanded into a control system suitable for the equipment scale On TOYOPUC-Plus, functions can be added per board. Controlling small scale equipment with a minimal configuration (1 board). TOYOPUC-Plus allows for expansion in the limited space of automatic equipment and configures the ideal control system. TOYOPUC-Plus does not require PLC model changes, but meets fluctuations in production volume with flexibility. An equipment and control configuration example Semi-automatic equipment

Manual equipment Connect actuators and sensors with easy operations and I/Os and controlling.

Connect workpiece loading/unloading robot with communication and add control. Plus CPU

Plus CPU

Plus IO24/16P Plus DLNK-M

+ Add communication for robot and I/O for interlock

Minimal configuration

Fully-automatic equipment

Plus CPU Plus IO24/16P Plus DLNK-M

Connect betweenprocess conveyance equipment with communication and add control. Connect an upper server production control system with communication.

Plus EFR

+ Communication for conveyance Upper server communication added

Communication for robot and I/O for interlock

Achieving visualization of control through an array of functions SFC and FBD functions are equipped as standard, and can be easily operated using the follow-up monitor. *SFC (Sequencial Function Chart), FBD (Fanction Block Diagram)

Achieving a motion control function Achieves max. 16-axis compact motor control.(When mounting two , Plus MCML / MCSSC)

Refer to page 30 for the assembly of the communication board.

CPU board

Expansion I/O module

Memory expansion Ethernet* system communication board (supports EthernetIP)

DeviceNet* communication board

72

90

Ethernet* system communication board (supports EthernetIP)

Plus CLNK-M CC-Link* master communication board

84

84

Motion control board MECHATROLINK*-Ⅲ

Motion control board SSCNETⅢ*

Plus CLNK-S CC-Link* slave communication board

60

Plus EFR2

90

Plus DLNK-M

66

73

Plus EX2

140

Ethernet* system communication board

72.5

70

Plus MCSSC

90

Memory expansion Ethernet* system communication board

72.5

140

140

90

90

Plus MCML

72.5

72.5

Plus IO24/16P

60

Plus EFR

Plus EX Plus CPU

140

Board type (total 11 types)

90

26

Page 28

Compact PLC

Compact PLC TOYOPUC-PCDL

Multiple-purpose distributed control is available using the various communication function in a small size.

Main features

Conventional user-friendly TOYOPUC programming is inherited.

Flexible programming by 3 languages (LD, SFC, FBD) possible.

optimal compact PLC suitable for space-saving distributed control with the communication function.

Flexible system extendibility by abundant communication functions.

Base module

Various modules

(for 2, 3, 5 or 8 slots) - Built-in power supply - DIN rail fixing - A base module for AC power or DC power available

- Input/output module - Analogue module - Extension module

CPU module

Program capacity: 16K words (LD, SFC part) One program (FBD:8K words) Machine information memory: 64KB Communication functions - I/F : RS232C (PCwin) / MODBUS*-RTU (Slave) → A selection from 2 kinds - L1 : FL-net - L2 : (Slave) / Serial I/O (SIO) / PC-LINK / SN-I/F → A selection from 5 kinds

Connection example

PCwin

PC10G-CPU FL-net

SN-I/F

*MODBUS is a registered trademark of AEG Schneider Automation Inc.

27

TOYOPUC-PCS-J

Page 29

TOYOPUC-PCk series

Compact, yet it is applicable to multipurpose usage

PCk05-CPU

PCk06-P-CPU

PCk05-CPU is a micro type PLC with 8-point input and 6-point output.

PCk06-P-CPU is a mixed type PLC of all-in-one design type with 20-point input and 16-point output and module type.

RS 232C port is equipped as a standard feature.

1 slot is arranged for expansion. It is possible to expand to the max. 30 points.

The DeviceNet* slave module is also arranged. It is easy to communicate with various TOYOPUC series.

It is a small type PLC with 20-point input and 16-point output.

RS 232C/422/485 ports are equipped as a standard feature.

4 slots are arranged for expansion. It is possible to expand to the max. 100 points.

The DeviceNet slave module is also arranged. It is easy to communicate with various TOYOPUC series.

Rich convenient functions ●

It is possible to communicate with TOYOPUC series, using DeviceNet* Slave module of kDLNK.

●

I/F is possible to connect with PCwin-PCk.

●

Port 2 of PCk06-P-CPU is possible to connect with RS232C/422/485 MODBUS*.

TOYOPUC series

PCk series

RS232C/422/485

DeviceNet*

PCk connection cable PCwin-PCk

DC input specifications Items

Model

Address allocation Rated input voltage Max. input current

PCk05-CPU (TKC-6471) X0〜X2 (high speed input) X3〜X7 (standard input) DC12-24V 6mA (DC12V) 4mA (DC12V) 13mA (DC24V) 8.5mA (DC24V)

PCk06-P-CPU (TKC-6472) X0〜X3 (high speed input) X4〜X13 (standard input) DC12-24V 6mA (DC12V) 4mA (DC12V) 13mA (DC24V) 8.5mA (DC24V)

Output specifications Model Items

Address allocation Rated load voltage Max. load current

PCk05-CPU (TKC-6471) Relay output specifications Y400〜Y405 DC6-27V、AC6〜240V (47〜63Hz) 2A/point, 6A/common

PCk06-P-CPU (TKC-6472) DC output specifications Y400〜Y401 (pulse output) Y402〜40F (standard output) DC12-24V 0.5A/point 1A/point

*DeviceNet is a registered trademark of Open DeviceNet Vendor Association Inc. *MODBUS is a registered trademark of AEG Schneider Automation Inc.

28

Page 30

Specifications PC10, PC3J Series control specifications Model PC10G PC10P PC3JX PC3JX-D Programming method Stored program method Event monitor function by parameter setting Program control method Cyclic operation method Constant period interruption function (1 ms〜) Cyclic operation method Constant period interruption function Input/output control method Image registration method Basic instruction processing speed Contact…0.015μs〜 /instruction Basic command: 0.021 μs (fastest) Application instruction processing speed 0.05μs〜 few μs/instruction 0.08 μs/word Basic instruction 19 instructions + 1 instruction (the inversion output for screen buttons) 19 instructions 20 instructions Timer counter instruction 21 instructions + 1 ms timer, 1s timer 21 instructions 29 instructions Over 700 commands Data type: BIN, BCD, signed BIN 700 instructions or more The operation with the sign Application instruction 450 instructions or more is possible. The floating decimal point is possible. Floating point (single precision, double precision) Size: byte, word, double word 180K words (60K words × 3) (60k words / 60K words 48K words (16K words × 3) 180K words (60K words × 3) / 60K words, 120k words / 60K words, 180K words) + FB library 32K words + FB library 60K words Program capacity + FB library 60K words + Standard library 32K words + Standard library 32K words + Standard library 32K words + User library 32K words + User library 32K words + User library 32K words Memory element CMOS-RAM, Flash EPROM CMOS-RAM, FRAM Battery Rechargeable (Lithium secondary battery: battery longevity 5 years) None 1,024 points No. of external I/O 2048 points (Increase is possible by DeviceNet* and remote I/O 79,872 points 86,016 points 79,872 points (2,048 points × 3 + No. of internal output (4,096 points × 3 + 8,192 points + 65,536 points) 8,192 points + 65,536 points) (2,048 points × 3 + 73,728 points) No. of keep relay 6,400 points (768 points × 3 + 4,096 points) 0.1〜6553.5 sec / 0.01〜655.35 sec 0.1〜6553.5 sec / 0.01〜655.35 sec 0.1〜6553.5 sec / 0.01〜655.35 sec Timer function 0.001〜65.535 sec / 1〜65535 sec total 3,584 points 0.001〜65.535 sec / 1〜65535 sec total 9,728 points total 3,584 points Counter function 1〜65,535 (2,560 points × 3 + 2,048 points) 1〜65,535 (512 points × 3 + 2,048 points) 1〜65,535 (512 points × 3 + 2,048 points) No. of link relay 39,912 points (10,240 points × 3 + 8,192 points) 14,336 points (2,048 points × 3 + 8,192 points) Detection of start-up and start-down 11,776 points (2,560 points × 3 + 4,096 points) 5,632 points (512 points × 3 + 4,096 points) 164K words / 16 bit (12K words × 3 +128K words) 44K words / 16 bit (4K words × Data register Extension buffer register: 256K words / 16 bit 3 + 32K words) Extension buffer 12K words(4K words × 3 + 32K words) Flash register: 4Mbyte flash drive (read only)*1 register: 128K words / 16 bit Link register 6K words / 16 bit (2K words × 3) Equipment data memory 4Mbyte Program comment, SFC data, FB data, I/O diagram, network diagram 4Mbyte *2 Communication (link) module: MAX. 24 Special module installation Communication (link) module: Max 24 sheets, - No number of sheets limitation by the consumption memory amount Unlimited number depending on memory usage SFC ○ Visualization function F B ○ F B ○ Library function Standard ○ User ○ Event monitor function (possible to monitor at the cycle) ○ Compulsion ON/OFF function ○ Scan unit trace function ○ Equipment diagnosis function ○ Diagnostic dummy: 2,048 points 128 histories ○ Maintenance Network diagnosis function ○ support I/O diagram display ○ I/O recorder ○ 512Kbyte (50 points / change point in one cycle → memory of about 40 cycles) ○ Test mode ○ Function to return instantaneously to former program when program change is confirmed ○ Programmer I/F USB (V2.00) 480Mbps L1: FL / ET / F remote M 10Mbps/100Mbps L1:PC/CMP/MODBUS/SIO L1:PC/CMP/MODBUS/SIO Built-in communication L2: FL / ET / F remote M 10Mbps/100Mbps function SIO/SN-IF DLNK-M2 L3: PC/CMP/SN-I/F L3: PCI bus I/F Items

*1 The range where special instruction is necessary for writing in. *DeviceNet is the registered trademark of Open DeviceNet Vendor Association Inc. *2 PC10P can be equipped with the special module through the use of BUS-EXP (EXPANDED BUS) or Plus BUS-EX.

Compact PLC PCk series control specifications Items

CPU function

Model

Programming method Program control method Program language Input/Output control method Basic instruction processing speed Application instruction processing speed Basic instruction Timer/Counter instruction Application instruction Program capacity Memory device Battery External I/O points Internal output points Keep relay points Timer function

Counter function Link relay points Rising/Downing edge detection External power No. of modules possible to install Installation method I/F Communication function Port 2 Programmer Peripheral software Cable

PCk05-CPU

PCk06-P-CPU Stored program method Cyclic operation method (with sub routine function) LD Image register method Contact 1.3〜2.3μs/instruction, Output 6.8〜34.4μs/instruction Contact 0.37〜0.67μs/instruction, Output 1.82〜9.2μs/instruction 2.4〜several 100μs/instruction 13 kinds 6 kinds More than 110 instructions 2,048 words 7,679 words USB flash drive, RAM Commercial battery CR2354, - - (Battery life: 5 years, however, please replace to a new battery if the system was shut down for 10 days or more.) Input : built-in 8 points + points of mounting modules Input: built-in 20 points + points of mounting modules Output : built-in 6 points (Relay output) + points of mounting modules Output: built-in 16 points (Source output) + points of mounting modules 256 points 512 points 256 points 512 points 128 points, 0.1〜999.9sec./0.01〜99.99sec. 256 points, 0.1〜999.9sec./0.01〜99.99sec. 128 points, 1〜9,999 128 points, 1〜9,999 Input 1,024 points, output 1,024 points 512 points 3,200 words 7,296 words Data register 1 4 DIN rail or set screw (screw size: M4) PCwin-PCk for programmer only RS232C (MODBUS*) RS232C/422/485 (MODBUS*) PCwin-PCk Cable connecting PCk (TKY-6485) *MODBUS is a registered trademark of AEG Schneider Automation Inc.

29