Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 1 of 2

Industrial Power Supplies TIS Series, 50–600 Watt, pages 1 to 6

Pages 1 to 6 of 12

The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Traco Power TIS 75-124 and Traco Power TIS 150-124

Page 1

Industrial Power Supplies TIS Series, 50–600 Watt

CB

Features ◆ Switch mode power supplies for

(LVD)

DIN-rail mount

Scheme

UL 60950-1 UL 508 UL 1604

◆ 6 power ranges with 2, 3, 6, 12, 20 and 24 A output current (24 VDC models)

◆ Selectable 115/230 VAC input ◆ Very low ripple and noise ◆ EMI complies with EN 61000-6-3 and EN 61000-6-4

◆ Operating temp. range –25°C to +70°C ◆ For system operation available with built-in functions: RED: Redundancy module for N+1

Systems with true current sharing SIG: Signal module with AC-power fail, power good signal and external On/Off control UDS: DC-UPS module for uninter ruptable battery backed-up power systems

◆ Worldwide safety approvals incl. class I, div. 2 location

◆ Easy snap-on mount on DIN-rails or chassis mount

◆ 3-year product warranty

The switching power supplies of the TIS series have been particularly designed for applications in industrial process control systems and with machine tools. Excellent specifications and high immunity against electrical disturbances guarantee reliable power for sensitive loads in rugged industrial environments. With the help of optional function modules specific requirements for system applications can be easily realized with a standard model. With the UDS module the power supplies can be extended to a perfect DC-UPS with automatic battery- backup. This function is very often required in applications where a time delayed shutdown of a system is necessary. To monitor and control the power supply a signal module can be installed. For parallel operation with active power sharing a redundancy option is available. This flexibility makes the TIS series power supplies a cost effective solution for many industrial applications.

Models Order Code (includes terminal plugs) TIS 50-112 TIS 50-124 TIS 75-112 TIS 75-124 TIS 75-148 TIS 150-124 TIS 150-148 TIS 300-124 TIS 300-148 TIS 300-172 TIS 500-124-115 TIS 500-124-230 TIS 600-124 TIS 600-148 TIS 600-172 http://www.tracopower.com

Input Voltage nom. 115–240 VAC universal input

Output Power max. 50 W

115/230 VAC selectable

75 W

115/230 VAC selectable

150 W

115/230 VAC selectable

300 W

115 VAC 230 VAC

500 W 500 W

115/230 VAC selectable

600 W

Output Voltage nom. 12 VDC 24 VDC 12 VDC 24 VDC 48 VDC 24 VDC 48 VDC 24 VDC 48 VDC 72 VDC 24 VDC 24 VDC 24 VDC 48 VDC 72 VDC

Output Current max. 3.5 A 2.0 A 6.0 A 3.0 A 1.5 A 6.0 A 3.0 A 12.0 A 6.0 A 4.2 A 20.0 A 20.0 A 24.0 A 12.0 A 8.5 A

Page 1 of 12

Page 2

Industrial Power Supplies TIS

50–600 Watt

Input Specifications Input voltage range TIS 50:

TIS 75, 150, 300, 600:

TIS 500-124-230.

TIS 500-124-115:

93 – 264 VAC 93 – 132 VAC / 187 – 264 VAC 187 – 264 VAC 93 – 132 VAC

Input frequency 47 – 63 Hz Input current at full load (typ.) at 115 VAC

TIS 50: 0.85 A

TIS 75: 1.3 A

TIS 150: 2.7 A

TIS 300: 4.9 A

TIS 500: 6.0 A

TIS 600: 7.0 A Recommended circuit breaker, TIS 50: characteristic C TIS 75: or fuse, slow blow typ TIS 150:

TIS 300:

TIS 500:

TIS 600:

at 230 VAC 0.50 A 0.75 A 1.6 A 2.9 A 4.3 A 5.0 A

5.0 A 5.0 A 10.0 A 15.0 A 15.0 A 20.0 A

Output Specifications Output voltage adj. range 12 VDC models:

24 VDC models:

48 VDC models:

72 VDC models:

12 – 14 VDC 24 – 28 VDC 48 – 52 VDC 60 – 76 VDC

Regulation

– Input variation 0.2 % – Load variation (10–90%) TIS 50, TIS 75, TIS 150: 1.0 % TIS 300, TIS 500, TIS 600: 0.3 % (2.0 % in parallel operation) Ripple and noise (20MHz bandwidth) <50 mV pk-pk Electronic short circuit protection current limitation at 110 % typ.

(constant current, automatic restart) Over voltage protection, trigger point at 140 % typ. Vout nom. Hold-up time 115 VAC 230 VAC

TIS 50 ... TIS 300: min. 25 ms min. 30 ms

TIS 500: min. 20 ms min. 40 ms

TIS 600: min. 15 ms min. 25 ms http://www.tracopower.com

Page 2 of 12

Page 3

Industrial Power Supplies TIS

50–600 Watt

General Specifications Temperature ranges

– Operating (ambient temp.) –25°C to +70°C – Derating above 50°C (122°F) 2 %/K – Storage (non operating) –25°C to +85°C

Humidity (non condensing) 95 % rel. H max. Pollution degree 2 Temperature coefficient 0.02 %/K Switching frequency 80 kHz typ. (pulse width modulation) Efficiency

TIS 50 ... TIS 300: 85 % typ. TIS 500: 90 % typ. TIS 600: 90 % typ.

Isolation according to IEC/EN 60950, UL 60950, UL 508 Reliability, calculated MTBF (MIL-HDBK-217F, at +25°C, ground benign)

TIS 50/75: 450’000 h / 420’000 h TIS 150/300: 420’000 h / 360’000 h TIS 500/600: 340’000 h / 300’000 h

Safety standards IEC/EN 60950-1 (SELV, except 72 VDC models) UL/cUL 60950-1, UL 508, UL/cUL 1604 Safety approvals – CB report for IEC 60950 www.tracopower.com/products/tis-cb.pdf – UL approvals UL/cUL 60950, File e181381 UL/cUL 508, File e210002

UL/cUL 1604, File e213613 not for TIS 50 & 500

(Class I, Div. 2, Groups A, B, C and D hazardous locations)

www.ul.com -> certifications – CSA certificate (UL 60950-1, CSA 60950-1) www.tracopower.com/products/tis-csa.pdf Electromagnetic compatibility (EMC), Emissions EN 61000-6-3 / EN 61000-6-4 – Conducted RI suppression on input EN 55011 class B, EN 55022 class B, FCC part 15, level B – Radiated RI suppression EN 55011 class A, EN 55022 class A, FCC part 15, level A Electromagnetic compatibility (EMC), Immunity EN 61000-6-2 – Electrostatic discharge (ESD) IEC/EN 61000-4-2 – Radiated RF field immunity IEC/EN 61000-4-3 – Electrical fast transient / burst immunity IEC/EN 61000-4-4 – Surge immunity IEC/EN 61000-4-5 – Immunity to conducted RF disturbances IEC/EN 61000-4-6 – Power frequency field immunity IEC/EN 61000-4-8

4 kV/8 kV 10 V/m 2 kV 2 kV/4 kV 10 V 30 A/m

Safety class degree of electrical protection 1 (IEC 536) Case protection IP 20 (IEC 529) Environment

– Vibration IEC 60068-2-6; 1 gn, 200 sweeps, each axis – Shock IEC 60068-2-27; 15 gn, 11 ms, each axis

Enclosure material aluminium (chassis) / zinc plated steel (cover) Mounting (snap-on with self locking spring) for 35 mm DIN-rails as per EN 50022 Connection detachable screw terminal block

(plugs included)

(TIS 600: fixed screw terminal block)

Instruction manual can be downloaded under: www.tracopower.com/products/tis-manual.pdf

All specifications valid at nominal input voltage, full load and +25 °C after warm-up time unless otherwise stated. http://www.tracopower.com

Page 3 of 12

Page 4

Industrial Power Supplies TIS

50–600 Watt

Power Supplies with Redundancy Function With this option a parallel operation of up to 5 units is possible. Decoupling diodes and current share lines allow to build true N +1 redundant systems with active current sharing for all units. This function also includes an alarm relay to signal a single unit failure. This option is available for TIS 150 W, TIS 300 W and TIS 600 W models. Please note: This option cannot be combined with other options.

Models Input Voltage

Output Power

Output Voltage

Output Current max.

nom.

max.

24 VDC

6.0 A

48 VDC

3.0 A

24 VDC

12 A

48 VDC

6.0 A

24 VDC

24 A

48 VDC

12 A

(includes terminal plugs) TIS 150-124 RED

115/230 VAC selectable

TIS 300-124 RED

115/230 VAC

TIS 300-148 RED selectable

TIS 600-124 RED

115/230 VAC

TIS 600-148 RED selectable

115/230VAC

TIS 150-148 RED

L

N

Con1 Pin3

Con1 Pin2

150 W 300 W 600 W

Con2 - Pin3/4

AC

Bus Indicator

DC Con2 - Pin1/2

+Vout 24/48VDC

Order Code

-Vout

Con1 Pin1 I-Sense

V-Sense

Con3 - Pin4

Con3 - Pin3 Con3 - Pin2 Con3 - Pin1

Regulator

Current Shareline

Unit OK Common Unit OK

Unit OK

Specifications Rating per relay contact 60 VDC /0.36 A max.

Instruction manual for RED option can be downloaded under: http://www.tracopower.com/products/tis-red_manual.pdf http://www.tracopower.com

Page 4 of 12

Page 5

Industrial Power Supplies TIS

50–600 Watt

Power Supplies with Powerfail Functions These models provide 3 functions required in many process control system applications: ◆ AC-Powerfail signal (relay contact) ◆ Power Good signal (relay contact) ◆ Remote On/Off

Models Output Power max.

(includes terminal plugs) TIS 150-124 SIG

115/230 VAC

TIS 150-148 SIG selectable

TIS 300-124 SIG

115/230 VAC selectable

TIS 600-124 SIG

115/230 VAC

TIS 600-148 SIG selectable

115/230VAC

TIS 300-148 SIG

L

N

Con1 Pin3

Con1 Pin2

150 W 300 W 600 W

Output Voltage nom.

max.

24 VDC

6.0 A

48 VDC

3.0 A

24 VDC

12 A

48 VDC

6.0 A

24 VDC

24 A

48 VDC

12 A

Con2 - Pin3/4

AC

+Vout

Output OK

DC

Con2 - Pin1/2

Con1 Pin1

Con3 - Pin2

Remote ON/OFF

-Vout

+

Con3 - Pin1

-

Con3 - Pin7 Con3 - Pin6

Mains Fail Detection

Output Current

24/48VDC

Input Voltage

Remote ON/OFF

Order Code

Common AC-Powerfail

Mains OK

(Relay A)

Con3 - Pin5 Con3 - Pin4 Con3 - Pin3

Power Good Detection (Relay B)

Power Good Common Power Good

Power Good

Specifications Power Good signal trigger point models with 24 Vout: >22.8 VDC ±0.5 V relay B closed (pin 4 – pin 3) models with 48 Vout: >45.6 VDC ±1.0 V relay B closed (pin 4 – pin 3)

AC-Powerfail signal Vin <93 resp. <187 VAC relay A closed

(pin 7 – pin 6) Raiting per relay contact 60 VDC /0.36 A max. Remote On/Off

– On short circuit con 3 pin 1 and pin 2 – Off open circuit con 3 pin 1 and pin 2

Instruction manual for SIG option can be downloaded under: http://www.tracopower.com/products/tis-sig_manual.pdf http://www.tracopower.com

Page 5 of 12

Page 6

Industrial Power Supplies TIS

50–600 Watt

DC-UPS-System

In addition to the standard power supply function, these models include a professional battery management system to charge and monitor an external battery. In the event of a power failure the battery is switched automatically and without any interruption to the DC output. Once mains power is available again, the battery is switched off. The backup time is limited only by battery capacity and load. Charge current and voltage can be adjusted to values as required by battery type. Power fail and low battery alarm signals are available via two independent relay contacts. During normal operation the battery status is monitored by periodically loading the battery for a short time. If a cell resistance is high, there is a relay alarm is available. The battery is fully protected under any operational conditions. The power supply is short circuit protected even in battery backup operation but, for safety reasons, the battery should be fitted with a fast blow fuse. Battery mode can be activated by interconnecting pin 7 and 8.

Models Order Code 1) TIS 300-124 UDS

Input Voltage 115/230 VAC

Output Power

Output Voltage

Output Current 2)

max.

nom.

max.

300 W

24 VDC

12 A

600 W

24 VDC

24 A selectable TIS 600-124 UDS

115/230 VAC selectable

1) Includes terminal plugs, does not include batteries 2) reduce max. output current by battery charging current

External Batteries For external batteries we recommend: Two Panasonic LC-R123R4PG in series for 3.4 Ah: www.tracopower.com/products/tsp-panas_034.pdf Two Panasonic LC-R127R2PG1 in series for 7.2 Ah: www.tracopower.com/products/tsp-panas_072.pdf

Mounting Devices for Batteries Order Code: TIS 24-32AF Frame & wiring for two Panasonic LC-R123R4PG batteries TIS 24-70AF Frame & wiring for two Panasonic LC-R127R2PG1 batteries Mounting devices including Batteries on request.

http://www.tracopower.com

Page 6 of 12