For the United Electric Controls H400-126

Page 1

4 0 0 S er i e s

4 0 0 Se r i e s

Pressure, Vacuum, Differential Pressure AND Temperature SWITCHES features • 1, 2 & 3 switch outputs • Epoxy-coated enclosure designed to meet enclosure type 4X • Wide variety of pressure sensors and materials • Setting via reference dial or hex screw adjustment • FM approved • Adjustable Ranges: "WC ranges: 300 "wc vacuum to 250 “wc pressure (-746,7 to 622,3 mbar) Pressure: 30 “Hg Vac to 6000 psi (-1,0 to 413,7 bar) Differential Pressure: 1"wcd to 200 psid (2.5 mbar to 13,8 bar) Temperature: -180 to 650 °F (-117.8 to 343.3 °C)

LEADERS IN SAFETY, ALARM & SHUTDOWN

4 0 0 - B - 0 8

Page 2

4 0 0 Se r i e s

400 S e ri e s overview features

The 400 Series is a versatile family of vacuum, pressure, differential pressure and temperature switches for applications that require single or multiple switching capabilities. Dual and triple switch versions provide multi-output for alarm and shutdown, pre-alarm and alarm, high/low limit or level staging functions.

• UL listed and cUL certified.

A wide variety of microswitch and process connection options, along with a weather-tight enclosure, make the 400 Series an ideal choice for most ordinary location applications. Its worldwide use is assured with approvals and certifications to agency standards.

• Optional ATEX or GOST intrinsic

Widely used throughout the process industries, the 400 Series provides threshold protection and control for many critical functions. Typical installations are found in industrial gas production, energy generation including pumps, turbines and compressors, pulp and paper, and water and wastewater treatment.

FM approved.

• CE compliant to low voltage directive and pressure equipment directive. safety compliance.

• One, two or three switch outputs may be separated up to 100% of range.

• Wide variety of available options and pressure sensor modules.

• Most models available for immediate delivery.

Reference scale, for types B, E & H with option M321

Differential Pressure Model with M210 Option - Dial Indication

Enlarged View

Temperature Model with Remote Bulb & Capillary and M321 option Gasketed Lexan® Window

Dual Switch, Low Water Column Differential Pressure Model

Lexan® is a registered trademark of Sabic Innovative Plastics 2 w w w

. u e o n l i n e . c o m

4 0 0 - B - 0 8

Page 3

400 Series specifications Storage temperature

-65 to 160°F (-54 to 71°C)

Ambient TEMPERATURE limits

-40 to 160°F (-40 to 71°C); set point typically shifts less than 1% of range for a 50°F (28°C) ambient temperature change

Set point repeatability

Temperature models: ± 2% of full scale range Pressure: models 126-376, 520-535, 540-547, 570-572, S126B-S164B: ± 2% of full scale range; models 440-457, 550-559: ± 1% of full scale range; models 610-614: ± 3% of full scale range

Shock

Set point repeats after 15 G, 10 millisecond duration

Vibration

Set point repeats after 2.5 G, 5-500 Hz

Enclosure

Die cast aluminum, epoxy powder coated, gasketed, captive cover screws

Enclosure classification

Designed to meet enclosure type 4X requirements

Switch output

One, two or three SPDT switches, may be separated up to 100% of range except models 521-524, 531-534: 50%; models 520, 525, 530, 535, 570-572: 30%; switches may be wired “normally open” or “normally closed”

Electrical rating

15 A 125/250/480 VAC resistive. Electrical switches have limited DC capabilities. Consult factory for additional information.

Weight

Approx. 3 to 7.5 lbs.; varies with model

Electrical connection

One 3/4” NPT and two 7/8” diameter knockouts

Pressure connection

All models 1/4” NPT (female) except models S126B-S164B, 520-535: 1/2” NPT (female); models 540-547: 1/8" NPT (female)

Temperature assembly

‘E’ types use the same assemblies as ‘F’ types, however, range spans are limited due to use of reference dials Bulb and capillary: 6 feet 304 stainless steel Immersion stem: models 120 &121: nickel-plated brass; optional 316L stainless steel available

Fill

Temperature Models: Model 1BS: solvent filled; models 2-8: non-toxic oil filled

Temperature deadband

Type F typically 1% and type E, B & C typically 2% of range under laboratory conditions (70°F ambient circulating bath at rate of 1/2°F per minute change)

Differential pressure indicator (option M210)

Differential pressure indication available J400K, J402K models 147-S157B; accuracy approximately 1-1⁄2% mid 50% of range, 3% at ends; window is plexiglass and gasketed; indicator may be field adjusted for approximately ±1% accuracy at any set point within range

4 0 0 - B - 0 8 w w w

. u e o n l i n e . c o m 3

Page 4

4 0 0 Se r i e s

400 S e ri e s approvals UNITED STATES AND CANADA Type 400 & 402 UL Listed, cUL Certified Pressure: UL 508; CSA C22.2 No. 14, file # E42272 Temperature: UL 873; CSA C22.2 No. 24, file # E10667 Type 403 UL Recognized, cUL Recognized Pressure: UL 508; CSA C22.2 No. 14, file # E42272 Temperature: UL 873; CSA C22.2 No. 24, file # E10667 All Types FM Approved Pressure: Class 3510 Temperature: Class 3545 EUROPE ATEX Directive (94/9/EC) II 1 G Ex ia IIC T6 Ga (OPTIONAL – code M405) Tamb = -50°C to +60°C UL International DEMKO A/S (N.B.# 0539) Certificate # DEMKO 11 ATEX 1105621X Rev. 0 EN 60079-0, 60079-11 & 60079-26 Low Voltage Directive (LVD) (2006/95/EC) Compliant to LVD Products rated lower than 50 VAC and 75 VDC are outside of the scope of the LVD Pressure Equipment Directive (PED) (97/23/EC) Compliant to PED Products rated below 7.5 PSI are outside the scope of PED RUSSIA Gosgortechnadzor Permit (OPTIONAL – code M406) 0ExiaIICT6 Tamb = -50˚C to +60˚C NANIO CCVE Certification Center Certificate # ROSS US.GB05.Bo2933 GOST R 51330.0, 51330.1, 51330.10 & 51330.14

4 w w w

. u e o n l i n e . c o m

4 0 0 - B - 0 8

Page 5

400 Series pressure model chart Type J400, single switch output with internal hex screw adjustment Type J402, dual switch output with internal hex screw adjustment Type J403, triple switch output with internal hex screw adjustment Model

Adjustable Set Point Range

Deadband

Low end of range on fall; High end of range on rise

Deadband doubles for 2 and 3 switch types

“wc

“wc mbar mbar

Over Range Pressure*

Proof Pressure** psi psi bar bar

Buna-N diaphragm and O-Ring with epoxy coated aluminum 1/2” NPT (female) pressure connection, large 0.72” orifice for clean-out purposes. Other wetted materials available, see pg. 12; Option M449 recommended 520† 521† 522† 523† 524† 525†

300 Vac to 0 10 Vac to 10 50 Vac to 50 0.5 to 5.0 2.5 to 50 10 to 250

-746,7 to 0 -24,9 to 24,9 -124,5 to 124,5 1,2 to 12,4 6,2 to 124,5 24,9 to 622,3

0.2 to 12 0.1 to 1 0.1 to 5 0.1 to 0.3 0.1 to 2 0.1 to 10

0,5 to 29,9 0,2 to 2,5 0,2 to 12,4 0,2 to 0,7 0,2 to 5,0 0,2 to 24,9

200 200 200 200 200 200

13,8 13,8 13,8 13,8 13,8 13,8

400 400 400 400 400 400

27,6 27,6 27,6 27,6 27,6 27,6

Welded 316L stainless steel diaphragm and 1/2” NPT (female) pressure connection, large 0.72” orifice for clean-out purposes; Option M449 recommended 530† 531† 532† 533† 534† 535†

300 Vac to 0 10 Vac to 10 50 Vac to 50 0.5 to 5.0 2.5 to 50 10 to 250

-746,7 to 0 -24,9 to 24,9 -124,5 to 124,5 1,2 to 12,4 6,2 to 124,5 24,9 to 622,3

0.2 to 15 0.1 to 1 0.1 to 6 0.1 to 0.3 0.1 to 2.5 0.1 to 10 psi bar psi

(unless noted)

(unless noted)

(unless noted)

0,5 to 37,3 0,2 to 2,5 0,2 to 14,9 0,2 to 0,7 0,2 to 6,2 0,2 to 24,9

50 50 50 50 50 50

3,4 3,4 3,4 3,4 3,4 3,4

100 100 100 100 100 100

6,9 6,9 6,9 6,9 6,9 6,9 bar psi bar psi bar

(unless noted)

(unless noted)

(unless noted)

316L stainless steel diaphragm and Viton® O-Ring with 316L stainless steel 1/4" NPT (female) pressure connection 5701 5711 5721

0 to 20 0 to 50 0 to 100

0 to 1,4 0 to 3,4 0 to 6,9

0.2 to 4 0.7 to 6 1 to 7

13,8 to 275,8 mbar 48,3 to 413,7 mbar 0,1 to 0,5

20 50 100

1,4 3,4 6,9

225 225 225

15,5 15,5 15,5

3 20 80 “wc 20 30 100 200

0,2 1,4 199,1 mbar 1,4 2,1 6,9 13,8

5 25 5 25 40 125 200

0,3 1,7 0,3 1,7 2,8 8,6 13,8

200 300 500

13,8 20,7 34,5

250 350 575

17,2 24,1 39,6

Welded 316L stainless steel bellows and 1/2” NPT (female) pressure connection S126B S134B S137B S144B S146B S156B S164B

30 ”Hg Vac to 0 30 ”Hg Vac to 20 psi 0 to 80 ”wc 0 to 20 0 to 30 0 to 100 0 to 200

-1 to 0 -1 to 1,4 0 to 199,1 mbar 0 to 1,4 0 to 2,1 0 to 6,9 0 to 13,8

0.2 to 0.9 ”Hg 0.2 to 1.2 ”Hg 2 to 6 ”wc 0.1 to 0.5 0.1 to 0.6 0.2 to 0.8 0.3 to 2

6,8 to 30,5 mbar 6,8 to 40,6 mbar 5 to 14,9 mbar 6,9 to 34,5 mbar 6,9 to 41,4 mbar 13,8 to 55,2 mbar 20,7 to 137,9 mbar

Welded 316L stainless steel bellows and 1/4” NPT (female) pressure connection 358 361 376

0 to 200 0 to 300 0 to 500

0 to 13,8 0 to 20,7 0 to 34,5

1.5 to 8 2 to 9 3 to 12

0,1 to 0,6 0,1 to 0,6 0,2 to 0,8

*Over Range Pressure: The maximum pressure that may be applied continuously without causing damage and maintaining set point repeatability **Proof pressure: The maximum pressure to which a pressure sensor may be subjected, which causes no permanent damage. The unit may require calibration (e.g. start-up, testing). † Model not available on types J400 and J403; actual deadband shown, do not double – switch separation a maximum of 30 - 50% of range. 1 Switch separation of 30% maximum for dual and triple switch units.

4 0 0 - B - 0 8 w w w

. u e o n l i n e . c o m 5

Page 6

4 0 0 Se r i e s

400 S e ri e s pressure model chart Type J400, single switch output with internal hex screw adjustment Type J402, dual switch output with internal hex screw adjustment Type J403, triple switch output with internal hex screw adjustment

Model Adjustable Set Point Range

Deadband

Low end of range on fall; High end of range on rise

Deadband doubles for 2 and 3 switch types psi bar psi

(unless noted)

(unless noted)

bar

Over Range Pressure*

Proof Pressure** psi psi bar bar

(unless noted)

303 stainless steel piston with Buna-N O-Ring and 303 stainless steel 1/4” NPT (female) pressure connection (not recommended for gas service since drying of the O-Ring seal can allow bleeding of medium into the atmosphere) 610 612 614

100 to 1,000 200 to 3,000 500 to 6,000

6,9 to 68,9 13,8 to 206,8 34,5 to 413,7

30 to 150 40 to 250 50 to 400

2,1 to 10,3 2,8 to 17,2 3,4 to 27,6

6,000 6,000 6,000

413,7 413,7 413,7

10,000 10,000 10,000

689,5 689,5 689,5

Brass bellows with nickel-plated brass 1/4” NPT (female) pressure connection; Models 126 and 134 have zinc-plated steel spring exposed to media 126 134 137 144 146 156 164

30 ”Hg Vac to 0 30 ”Hg Vac to 20 psi 0 to 80 ”wc 0 to 20 0 to 30 0 to 100 0 to 200

-1 to 0 -1 to 1,4 0 to 199,1 mbar 0 to 1,4 0 to 2,1 0 to 6,9 0 to 13,8

0.2” to 0.9 ”Hg 0.2” to 1.2 ”Hg 2 to 6 ”wc 0.1 to 0.5 0.1 to 0.6 0.2 to 0.8 0.3 to 2

6,8 to 30,5 mbar 6,8 to 40,6 mbar 5 to 14,9 mbar 6,9 to 34,5 mbar 6,9 to 41,4 mbar 13,8 to 55,2 mbar 20,7 to 137,9 mbar

3 20 3 20 30 100 200

0,2 1,4 0.2 1,4 2 6,9 13,8

5 25 5 25 40 125 200

0,3 1,7 0,3 1,7 2,8 8,6 13,8

200 300

13,8 20,7

250 350

17,2 24,1

Phosphor bronze bellows with nickel-plated brass 1/4” NPT (female) pressure connection 270 274

0 to 200 0 to 300

0 to 13,8 0 to 20,7

1.5 to 8 2 to 10

0,1 to 0,6 0,1 to 0,7

Buna-N diaphragm and O-Ring with aluminum 1/4” NPT (female) pressure connection and cap; Models 448, 450 & 452 have stainless steel pressure connection and cap 440†† 441††† 442 443 448 449††† 450 451 452 453 454

0 to 2 ”wc 0 to 10 ”wc 0 to 20 ”wc 0 to 80 ”wc 80 “wc Vac to 0 0 to 20 ”wc 30 ”Hg Vac to 0 0 to 80 ”wc 30 ”Hg Vac to 20 psi 0 to 20 0 to 30

0 to 5 mbar 0 to 24,9 mbar 0 to 49,8 mbar 0 to 199,1 mbar -199,1 to 0 mbar 0 to 49,8 mbar -1 to 0 0 to 199,1 mbar -1 to 1,4 0 to 1,4 0 to 2,1

0.07 to 0.25 ”wc 0.15 to 0.4 ”wc 0.2 to 0.6 ”wc 0.5 to 2 ”wc 1 to 3 ”wc 1 to 2 ”wc 0.1 to 0.4 ”Hg 1 to 3 ”wc 0.2 to 1 ”Hg 0.05 to 0.2 0.05 to 0.3

0,2 to 0,6 mbar 0,4 to 1,0 mbar 0,5 to 1,5 mbar 1,2 to 5,0 mbar 2,5 to 7,5 mbar 2,5 to 5,0 mbar 3,4 to 13,5 mbar 2,5 to 7,5 mbar 6,8 to 33,9 mbar 3,4 to 13,8 mbar 3,4 to 20,7 mbar

3 3 3 3 3 3 3 3 20 20 30

0,2 0,2 0,2 0,2 0,2 0,2 0,2 0,2 1,4 1,4 2,1

225 225 225 225 225 225 225 225 225 225 225

15,5 15,5 15,5 15,5 15,5 15,5 15,5 15,5 15,5 15,5 15,5

0,2 0,2 1,4 1,4 2,1 6,9

225 225 225 225 225 225

15,5 15,5 15,5 15,5 15,5 15,5

Teflon® diaphragm and Viton® O-Ring with 316L stainless steel 1/4” NPT (female) pressure connection and cap 550 551 552 553 554 555 6

30 ”Hg Vac to 0 0 to 80 ”wc 30 ”Hg Vac to 20 psi 0 to 20 0 to 30 0 to 100 w w w

-1 to 0 0 to 199,1 mbar -1 to 1,4 0 to 1,4 0 to 2,1 0 to 6,9

0.1 to 0.6 ”Hg 1.5 to 3.5 ”wc 0.2 to 1 ”Hg 0.05 to 0.3 0.1 to 0.4 0.25 to 0.75

3,4 to 20,3 mbar 3,7 to 8,7 mbar 6,8 to 33,9 mbar 3,4 to 20,7 mbar 6,9 to 27,6 mbar 17,2 to 51,7 mbar

3 3 20 20 30 100

. u e o n l i n e . c o m

Teflon® and Viton® are registered trademarks of E.I. DuPont de Nemours and Company

4 0 0 - B - 0 8 †† Model not available on types J402 and J403

††† Model not available on type J403

Page 7

400 Series pressure model chart Type H400, single switch output with internal adjustment via reference dial Type H402, dual switch output with internal adjustment via reference dial Type H403, triple switch output with internal adjustment via reference dial Model

Adjustable Set Point Range

Deadband

Proof Pressure** Scale Division

High end of range on rise Low end of range on fall;

Deadband doubles for 2 and 3 switch types psi bar psi bar psi

(unless noted)

(unless noted)

(unless noted)

(unless noted)

(unless noted)

6,8 to 30,5 mbar 6,8 to 40,6 mbar 5 to 14,9 mbar 6,9 to 34,5 mbar 6,9 to 41,4 mbar 13,8 to 55,2 mbar 20,7 to 137,9 mbar

5 25 5 25 40 125 200

0,3 1,7 0,3 1,7 2,8 8,6 13,8

2 ”Hg 2 ”Hg & 2 psi 5 ”wc 1 1 5 10

0,1 to 0,6 0,1 to 0,6 0,2 to 0,8

250 350 575

17,2 24,1 39,6

10 10 20 bar psi

Welded 316L stainless steel bellows and 1/2” NPT (female) pressure connection S126B S134B S137B† S144B S146B S156B S164B

30 ”Hg Vac to 0 30 ”Hg Vac to 20 psi 0 to 80 ”wc 0 to 20 0 to 30 0 to 100 0 to 200

-1 to 0 -1 to 1,4 0 to 199,1 mbar 0 to 1,4 0 to 2,1 0 to 6,9 0 to 13,8

0.2 to 0.9 ”Hg 0.2 to 1.2 ”Hg 2 to 6 ”wc 0.1 to 0.5 0.1 to 0.6 0.2 to 0.8 0.3 to 2

Welded 316L stainless steel bellows and 1/4” NPT (female) pressure connection 358 361 376

0 to 200 0 to 300 0 to 500

0 to 13,8 0 to 20,7 0 to 34,5

1.5 to 8 2 to 9 3 to 12

Brass bellows with nickel-plated brass 1/4” NPT (female) pressure connection; Models 126 and 134 have zinc-plated steel spring exposed to media 126 134 137† 144 146 156 164

30 ”Hg Vac to 0 30 ”Hg Vac to 20 psi 0 to 80 ”wc 0 to 20 0 to 30 0 to 100 0 to 200

-1 to 0 -1 to 1,4 0 to 199,1 mbar 0 to 1,4 0 to 2,1 0 to 6,9 0 to 13,8

0.2 to 0.9 ”Hg 0.2 to 1.2 ”Hg 2 to 6 ”wc 0.1 to 0.5 0.1 to 0.6 0.2 to 0.8 0.3 to 2

6,8 to 30,5 mbar 6,8 to 40,6 mbar 5 to 14,9 mbar 6,9 to 34,5 mbar 6,9 to 41,4 mbar 13,8 to 55,2 mbar 20,7 to 137,9 mbar

5 25 5 25 40 125 200

0,3 1,7 0,3 1,7 2,8 8,6 13,8

2 ”Hg 2 ”Hg & 2 psi 5 ”wc 1 1 5 10

250 350

17,2 24,1

10 10

Phosphor bronze bellows with nickel plated brass 1/4” NPT (female) pressure connection 270†† 274††

0 to 200 0 to 300

0 to 13,8 0 to 20,7

1.5 to 8 2 to 10

0,1 to 0,6 0,1 to 0,7

Buna-N diaphragm and O-Ring with aluminum 1/4” NPT (female) pressure connection and cap; Models 448, 450 & 452 have stainless steel pressure connection and cap 441† 442† 443† 448† 450†† 452†† 453†† 454††

0 to 10 “wc 0 to 20 “wc 0 to 80 “wc 80 “wc Vac to 0 30 “Hg Vac to 0 30 “Hg Vac to 20 psi 0 to 20 0 to 30

0 to 24,9 mbar 0 to 49,8 mbar 0 to 199,1 mbar -199,1 to 0 mbar -1 to 0 -1 to 1,4 0 to 1,4 0 to 2,1

0.15 to 0.4 “wc 0.2 to 0.6 “wc 0.5 to 2 “wc 1 to 3 “wc 0.1 to .04 “Hg 0.1 to 1 “Hg 0.05 to 0.2 0.05 to 0.3

0,4 to 1,0 mbar 0,5 to 1,5 mbar 1,2 to 5,0 mbar 2,5 to 7,5 mbar 3,4 to 13,5 mbar 3,4 to 33,9 mbar 3,4 to 13,8 mbar 3,4 to 20,7 mbar

225 225 225 225 225 225 225 225

15,5 15,5 15,5 15,5 15,5 15,5 15,5 15,5

0.5 “wc 1 “wc 5 “wc 5 “wc 2 “Hg 2 “Hg & 2 psi 1 1

**Proof pressure: The maximum pressure to which a pressure sensor may be subjected, which causes no permanent damage. The unit may require calibration (e.g. start-up, testing). † Model not available on types H402 and H403 †† Model not available on type H403

4 0 0 - B - 0 8 w w w

. u e o n l i n e . c o m 7

Page 8

4 0 0 Se r i e s

400 S e ri e s pressure model chart Type H400, single switch output with internal adjustment via reference dial Type H402, dual switch output with internal adjustment via reference dial Type H403, triple switch output with internal adjustment via reference dial

Model

Adjustable Set Point Range

Deadband

Proof Pressure** Scale Division

Low end of range on fall; High end of range on rise

Deadband doubles for 2 and 3 switch types psi bar psi bar

(unless noted)

(unless noted)

(unless noted)

(unless noted)

psi bar psi (unless noted)

Teflon® diaphragm and Viton® O-Ring with 316L stainless steel 1/4” NPT (female) pressure connection and cap 550†† 552†† 553†† 554†† 555††

30 “Hg Vac to 0 30 “Hg Vac to 20 psi 0 to 20 0 to 30 0 to 100

-1 to 0 -1 to 1,4 0 to 1,4 0 to 2,1 0 to 6,9

0.1 to 0.6 “Hg 0.2 to 1 “Hg 0.05 to 0.3 0.1 to 0.4 0.25 to 0.75

3,4 to 20,3 mbar 6,8 to 33,9 mbar 3,4 to 20,7 mbar 6,9 to 27,6 mbar 17,2 to 51,7 mbar

225 225 225 225 225

15,5 15,5 15,5 15,5 15,5

2 “Hg 2 “Hg & 2 psi 1 1 5

**Proof pressure: The maximum pressure to which a pressure sensor may be subjected, which causes no permanent damage. The unit may require calibration (e.g. start-up, testing). † Model not available on types H402 and H403 †† Model not available on type H403 differential pressure model chart Type J400K, single switch output with internal hex screw adjustment Type J402K, dual switch output with internal hex screw adjustment Model

Adjustable Set Point Range

Deadband

Low end of range on fall: High end of range on rise

Deadband doubles for 2 switch types psid bar psi

(unless noted)

(unless noted)

(unless noted)

mbar

Working Pressure*** psi

Proof Pressure** bar psi bar

30 ”Hg Vac to 100 30 ”Hg Vac to 180

-1 to 6,9 -1 to 12,4

300 300

20,7 20,7

30 ”Hg Vac to 100 30 ”Hg Vac to 150

-1 to 6,9 -1 to 10,3

180 180

12,4 12,4

30 ”Hg Vac to 225 30 ”Hg Vac to 225 30 ”Hg Vac to 225

-1 to 15,5 -1 to 15,5 -1 to 15,5

225 225 225

15,5 15,5 15,5

Welded 316L stainless steel bellows and 1/2” NPT (female) pressure connections S147B S157B

3 to 30 10 to 100

0,2 to 2,1 0,7 to 6,9

0.5 to 2 0.5 to 3

34,5 to 137,9 34,5 to 206,8

Brass bellows with nickel-plated brass 1/4” NPT (female) pressure connections 147 157

3 to 30 10 to 100

0,2 to 2,1 0,7 to 6,9

0.5 to 2 0.5 to 3

34,5 to 137,9 34,5 to 206,8

Buna-N diaphragm and O-Ring with aluminum 1/4” NPT (female) pressure connections 455 456 457

5 to 80 ”wcd 2 to 20 3 to 30

12,4 to 199,1 mbar 0,1 to 1,4 0,2 to 2,1

1 to 4 ”wc 0.1 to 0.3 0.1 to 0.4

2,5 to 10 6,9 to 20,7 6,9 to 27,6

***Working Pressure Range: The pressure range within which two opposing sensors can be safely operated and still maintain set point adjustability.

8 w w w

. u e o n l i n e . c o m

4 0 0 - B - 0 8