Page 1 of FA-M3 Basic Modules (Base, Power Supply, CPU Modules and ROM Packs) General Specifications

Manual · Yokogawa

FA-M3 Basic Modules (Base, Power Supply, CPU Modules and ROM Packs) General Specifications

Manual38 pagesPDF 1.1 MB

General specifications for Yokogawa FA-M3 basic modules: base modules, power supplies such as the F3PU20, CPU modules and ROM packs.

Download the PDF1.1 MB

Covers · 2 models

The models it covers

Summary

What is in it

Yokogawa general specifications for the FA-M3 Range-free Multi-controller basic modules. It gives specifications, model and suffix codes and external dimensions for the F3BU base modules (4 to 16 slots), the F3PU10, F3PU20, F3PU30, F3PU16, F3PU26 and F3PU36 power supply modules, the F3SP sequence CPU modules, the F3BP BASIC CPU modules and the RK ROM packs, with indicators, FAIL contact outputs and error LEDs.

Its parts

  1. Base Modules
  2. Power Supply Modules
  3. F3SP21-0N Sequence CPU Module
  4. F3SP25-2N Sequence CPU Module
  5. F3SP28-3N Sequence CPU Module
  6. F3SP28-3S Sequence CPU Module
  7. F3SP35-5N Sequence CPU Module
  8. F3SP38-6N Sequence CPU Module
  9. F3SP38-6S Sequence CPU Module
  10. F3SP53-4H Sequence CPU Module
  11. F3SP53-4S Sequence CPU Module
  12. F3SP58-6H Sequence CPU Module
  13. F3SP58-6S Sequence CPU Module
  14. F3SP59-7S Sequence CPU Module
  15. F3BP20-0N BASIC CPU Module

From the manual

Key facts from this manual

Each line names its page in the PDF.

Yokogawa general specifications GS 34M6C01-01E for the FA-M3 basic modules, including the F3PU20-0N and F3PU20-0S power supply modules. It also covers base modules F3BU04-0N to F3BU16-0N, power supply modules F3PU10-0N to F3PU36-0N, CPU modules F3SP21-0N to F3SP59-7S, F3BP20-0N and F3BP30-0N, and ROM packs RK10 to RK93. It gives ratings, terminal layouts, model codes and dimensions.

Read for this summary: pages 1 and 3 to 10 of 38.

Device
Power supply module for FA-M3 controllers; one is needed per base module p. 4
Base modules
F3PU20-0N: F3BU09-0N, F3BU13-0N and F3BU16-0N p. 4
Input
F3PU20-0N: 100-240 V AC p. 5
Output voltage
5 V DC rated p. 4
Terminals
F3PU20-0N: M3.5 screw terminals; F3PU20-0S: M4 screw terminals p. 4
FAIL output
Contact output FAIL1, COM, FAIL2, rated 24 V DC, 0.3 A p. 5
FAIL logic
FAIL1 to COM open in normal operation, closed on system or power failure; FAIL2 to COM the reverse p. 5
Indicator
Green RDY LED, lit when the module is normal p. 5
Grounding
FG: Class D grounding (JIS Class 3); LG connected to FG and grounded p. 5
Power failure ride-through
20 ms allowable momentary power failure p. 4
Dielectric strength
1500 V AC for 1 minute between external AC terminals and FG p. 4
Base module sizes
Base modules: 4, 6, 9, 13 or 16 slots p. 3
F3SP21 CPU
F3SP21-0N: sequence CPU for ladder programs, 10 K steps memory p. 9, 10

What this manual walks you through

  • Choosing the power supply module for a base module p. 4
  • Wiring the power input and FAIL signal terminals p. 5, 6
  • Choosing solderless terminals and screw torque p. 7
  • Power supply model and suffix codes p. 7
  • Base module mounting dimensions p. 3
  • Reading the CPU module error LEDs p. 10

Good to know

  • The total current drawn by the installed modules must not exceed the power supply module's capacity. p. 3
  • The F3BU16-0N base module cannot be mounted on a DIN rail. p. 3
  • The F3PU30-0N and F3PU36-0N are not UL certified. p. 4

Questions this manual answers

Which base modules does the F3PU20 power supply fit?

The F3PU20-0N is used with the F3BU09-0N, F3BU13-0N and F3BU16-0N base modules. p. 4

What is the difference between F3PU20-0N and F3PU20-0S?

They are the same apart from the terminals: the -0N has M3.5 screw terminals and the -0S has M4 screw terminals. p. 4

What input voltage does the F3PU20-0N take?

The front panel of the F3PU20-0N is marked for a 100-240 V AC input. p. 5

How does the F3PU20 FAIL output work?

It is a contact output rated 24 V DC, 0.3 A. FAIL1 to COM is open in normal operation and closes on a system or power failure; FAIL2 to COM does the reverse. p. 5

What does the RDY light on the power supply mean?

The green RDY indicator is lit when the power supply module is working normally. p. 5

The whole text · 4 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 3831-38

The file

Revision and size

RevisionGS 34M6C01-01E, 6th Edition: April, 2004
PublisherYokogawa Electric Corporation
Pages38
PDF1.1 MB
TextText from the PDF itself.

The first pages · 3 of 38

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 38
Page 2
Page 2of 38
Page 3
Page 3of 38