The text of a manual · part 1 of 4
FA-M3 Basic Modules (Base, Power Supply, CPU Modules and ROM Packs) General Specifications, pages 1 to 10
Pages 1 to 10 of 38
The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Yokogawa F3PU20 and Hirata F3PU20
Page 1
<<Contents>> <<Index>>
General Specifications
FA-M3 Basic Modules (Base, Power Supply, CPU Modules and ROM Packs)
Contents F3BU04-0N, F3BU06-0N, F3BU09-0N, Base Modules ................................................... 3 F3BU13-0N, F3BU16-0N F3PU10-0N, F3PU10-0S, F3PU20-0N, Power Supply Modules...................................... 4 F3PU20-0S, F3PU30-0N, F3PU16-0N, F3PU26-0N, F3PU36-0N F3SP21-0N
Sequence CPU Module ..................................... 9
F3SP25-2N
Sequence CPU Module ................................... 11
F3SP28-3N
Sequence CPU Module ................................... 13
F3SP28-3S
Sequence CPU Module ................................... 15
F3SP35-5N
Sequence CPU Module ................................... 17
F3SP38-6N
Sequence CPU Module ................................... 19
F3SP38-6S
Sequence CPU Module ................................... 21
F3SP53-4H
Sequence CPU Module ................................... 23
F3SP53-4S
Sequence CPU Module ................................... 25
F3SP58-6H
Sequence CPU Module ................................... 27
F3SP58-6S
Sequence CPU Module ................................... 29
F3SP59-7S
Sequence CPU Module ................................... 31
F3BP20-0N
BASIC CPU Module ........................................ 33
F3BP30-0N
BASIC CPU Module ........................................ 35
RK10, RK30, RK50
ROM Packs ..................................................... 37
RK33, RK53, RK73, RK93
ROM Packs ..................................................... 38
Yokogawa Electric Corporation
GS 34M6C01-01E 1st Edition: April, 1997 6th Edition: April, 2004
Page 2
Page 3
3
<<Content>> <<Index>>
General Specifications
F3BU04-0N, F3BU06-0N, F3BU09-0N, F3BU13-0N, F3BU16-0N Base Modules
„ General FA-M3 base modules serve as the base for accommodating various modules. FA-M3 base modules are available in 4-, 6-, 9-, 13- and 16-slot versions. Choose an appropriate base module according to the target system requirements. There are no differences between main units and sub-units.
„ Specifications F3BU04-0N
F3BU06-0N
F3BU09-0N
F3BU13-0N
F3BU16-0N
4
6
9
13
16
3
5
8
12
15
Number of slots Number of I/O slots* Current consumption Weight (g) *:
■ Model and Suffix Codes Model F3BU04 F3BU06 F3BU09 F3BU13 F3BU16
50mA(5V DC) 140g
200g
310g
420g
550g
Number of I/O slots that can be used with a single CPU module.
Suffix Code -0N -0N -0N -0N -0N
Style Code
Option Code, - - - - - - - - - Description 4 slots (excluding slots for power supply) 6 slots (excluding slots for power supply) 9 slots (excluding slots for power supply) 13 slots (excluding slots for power supply) 16 slots (excluding slots for power supply)
„ External Dimensions Unit: mm 16 slots (F3BU16-0N) 13 slots (F3BU13-0N) 9 slots (F3BU09-0N) 6 slots (F3BU06-0N) 4 slots (F3BU04-0N)
5 mounting holes (for M4 mounting screw) 9.6
85 100
10.5 88.8
4.5 Mounting width: W3
(When mounted on module surface)
Base Modules
Full width W1
F3BU04-0N F3BU06-0N F3BU09-0N F3BU13-0N F3BU16-0N
147 205 322 439 527
7.5 Mounting width: W4 Mounting width: W2 Full width: W1
Mounting width W2 W3 W4 138 - - 196 - - 313 138 - 430 196 - 517 138 313
All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation
Note: - Make sure that the total current consumption of the modules to be installed does not exceed the current capacity of the power supply module. - The F3BU16-0N module cannot be mounted on a DIN rail. - The signal ground of the main unit is attached to the metal chassis of the base modules.
GS 34M6C01-01E
July 1, 2003-00
Page 4
4
<<Content>> <<Index>>
General Specifications
F3PU10-0N, F3PU10-0S, F3PU20-0N, F3PU20-0S, F3PU30-0N, F3PU16-0N, F3PU26-0N and F3PU36-0N Power Supply Modules Note: F3PU30-0N and F3PU36-0N are not UL certified.
General FA-M3 power supply modules supply power to the FA-M3 Range-free Multi-controllers. One power supply module is required for each FA-M3 base module. The F3PU10-0N is used for the F3BU04-0N and F3BU06-0N base modules. The F3PU20-0N and F3PU26-0N are used for the F3BU09-0N, F3BU13-0N and F3BU16-0N base modules.
Specifications Specification Item
F3PU10-0N / F3PU10-0S*1
Supply voltage Supply voltage fluctuation range Power consumption
F3PU20-0N / F3PU20-0S*1
F3PU30-0N
F3PU26-0N
100-240 V AC, single phase, 50/60 Hz
24 V DC
85-264 V AC, 50/60 Hz ±3 Hz
15.6-31.2 V DC
35 VA
85 VA
100 VA
15.4 W
20 A max.(120 V AC,Ta=25°C) 45 A max.(240 V AC,Ta=25°C)
Inrush current
F3PU36-0N
33.1 W
46.2 W
20A max. 31.2 V DC, Ta=25°C
Rated output voltage Rated output current
F3PU16-0N
5 V DC 2.0 A
4.3 A
6.0 A
2.0 A
4.3 A
6.0 A
Insulation resistance
500 V DC 5 MΩ or more between external AC terminals and FG terminal
500 V DC 5 MΩ or more between external DC terminals and FG terminal
Dielectric strength
1500 V AC for 1 minute between external AC terminals and FG terminal
1500 V AC for 1 minute between external DC terminals and FG terminal
Allowable momentary power failure time Noise immunity External dimensions *2 Weight
20 ms Noise level: 1500 Vp-p when measured by a noise simulator having a 1 µs of noise pulse width, 1 ns of rise time, and 25 Hz to 60 Hz of repetition frequency. 28.9(W) × 100(H) × 83.2(D) mm
58(W) × 100(H) × 83.2(D) mm
58(W) × 100(H) × 126.1(D) mm
28.9(W) × 100(H) × 83.2(D) mm
58(W) × 100(H) × 83.2(D) mm
58(W) × 100(H) × 126.1(D) mm
190g
320g
380g
190g
320g
380g
*1:
F3PU10-0N (respectively F3PU20-0N) and F3PU10-0S (respectively F3PU20-0S) have the same dimensions, internal circuitry and other characteristics, except that F3PU10-0N (respectively F3PU20-0N) uses M3.5-screw terminals while F3PU10-0S (respectively F3PU20-0S) uses M4-screw terminals.
*2:
Excluding protrusions (see external dimensions for details).
All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation
GS 34M6C01-01E Apr. July12, 1, 2004-00 2003-00
Page 5
5
<< Content >> <<Index>>
Components and Functions PU10-0N / PU10-0S RDY PU 10-0N
PU20-0N / PU20-0S
RDY indicator (green) Lit when the power supply module is normal.
POWER
RDY PU 20-0N
POWER
FAIL signal (contact output) Contact ratings: 24 V DC, 0.3 A FAIL OUTPUT FAIL1
During normal operation
During system and power failure
Between FAIL1 and COM
Open
Closed
Between FAIL2 and COM
Closed
Open
COM
FAIL2 FG
FAIL OUTPUT FAIL1
COM
FAIL2
FG: Class D grounding (JIS Class 3 grounding)
FG
LG: Connected to FG and grounded LG
LG
Power supply N
100-120V AC
100-240V AC
L
N
L
INPUT 100 - 240VAC
INPUT100 -240VAC
YOKOGAW A
YOKOGAWA
F3PU10-0N
F3PU20-0N
RDY indicator (green) Lit when the power supply module is normal
RDY
POWER
PU30-0N
FAIL signal contact output Contact ratings: 24 V DC, 0.3 A
Between FAIL 1 and COM Between FAIL 1 and COM
During normal operation Open Closed
During system and power failure Closed Open
FAIL OUTPUT FAIL1
COM
FAIL2
FG: Class D grounding (JIS Class 3 grounding) LG: Connected to FG and grounded
FG LG N
Power supply 100-240V AC
L INPUT 100-240V AC
`
F3PU30-0N
All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation
GS 34M6C01-01E Apr. July12, 1, 2004-00 2003-00
Page 6
6
<< Content >> <<Index>>
RDY indicator (green) Lit when the power supply module is normal.
RDY
PU 16-0N
POWER
During normal operation
During system and power failures
Between FAIL1 and COM
Open
Closed
Between FAIL2 and COM
Closed
Open
OUTPUT FAIL1
FAIL OUTPUT FAIL1
COM
FAIL2
FAIL2
FG
POWER
PU26-0N
FAIL signal contact output Contact ratings: 24 V DC, 0.3 A
FAIL
COM
RDY
FG: Class D grounding (JIS Class 3 grounding)
FG
LG: Connected to FG and grounded LG
LG
_
Power supply 24V DC
_
+
+
INPUT 24VDC
INPUT 24VDC
YOKOGAWA
YOKOGAWA
F3PU16-0N
F3PU26-0N
RDY indicator (green) Lit when the power supply module is normal
RDY PU36-0N
FAIL signal contact output Contact ratings: 24 V DC, 0.3 A
Between FAIL 1 and COM Between FAIL 1 and COM
During normal operation Open Closed
During system and power failure Closed Open
POWER
FAIL OUTPUT FAIL1
COM
FAIL2
FG: Class D grounding (JIS Class 3 grounding)
FG
LG: Connected to FG and grounded
LG -
Power supply 100-240V AC
+ INPUT 24V DC
F3PU36-0N
All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation
GS 34M6C01-01E
July 1, 2003-00
Page 7
7
<<Content>> <<Index>>
„ Terminal Dimensions F3PU10-0N / F3PU20-0N
Model and Suffix Codes
F3PU10-0S / F3PU20-0S
M3.5
Model
M4, - -0S, - -0N, - -0S, - F3PU30
-0N, - F3PU16
-0N, - F3PU26
-0N, - F3PU36
-0N, - 7.1mm M8.2mm
M8.2mm F3PU20
„ Examples of Applicable Solderless Terminals Vender
Model
Applicable Conductor
Japan Solderless V1.25-M3 Terminal Mfg. Co., Ltd. AWG22 to 18 Nippon Tanshi Co., Ltd. RAV1.25-3.5 (0.33 to 0.82 mm2) (Copper wire) Japan Solderless V1.25-M4 Terminal Mfg. Co., Ltd. AWG16 to 14 Japan Solderless V2-M4 (1.25 to 2.0 mm2) Terminal Mfg. Co., Ltd. (Copper wire)
Option Code
-0N
F3PU10 7.1mm
Suffix Style Code Code
Description 100-240 V AC, for 4- and 6-slot base modules (M3.5 screws) 100-240 V AC, for 4- and 6-slot base modules (M4 screws) 100-240 V AC, for 9-, 13-, and 16-slot base modules (M3.5 screws) 100-240 V AC, for 9-, 13-, and 16-slot base modules (M4 screws) 100-120 V AC, for 9-, 13-, and 16-slot base modules 24 V DC, for 4- and 16-slot base modules 24 V DC, for 9-, 13-, and 16-slot base modules 24 V DC, for 9-, 13-, and 16-slot base modules
Applicable Modules and Crimping Torque F3PU10-0N F3PU10-0S F3PU20-0N F3PU20-0S F3PU30-0N F3PU36-0N May not be used 0.8N • m 1.2N • m
„ External Dimensions Unit: mm
F3PU10-0N, F3PU10-0S, F3PU16-0N
83.2
F3PU20-0N, F3PU20-0S, F3PU26-0N
28.9
83.2
58
2
2
100
100
All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation
July12, 1, 2004-00 2003-00 GS 34M6C01-01E Apr.
Page 8
8
<<Content>> <<Index>>
„ External Dimensions (2/2) Unit: mm
F3PU30-0N
(12.9)
58
58 2
30
2
83.2
RDY
POWER
PU36-0N
POWER
FAIL OUTPUT
FAIL OUTPUT
FAIL1
FAIL1
COM
COM
FAIL2
FAIL2
100
100
PU30-0N
RDY
FG
FG
LG
LG
N L INPUT 100-240V AC
INPUT 24V DC
F3PU30-0N
All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation
F3PU36-0N
GS 34M6C01-01E
July 1, 2003-00
Page 9
9
<<Content>> <<Index>>
General Specifications
F3SP21-0N Sequence CPU Module
„ General The F3SP21 is a CPU module for the FA-M3 Range-free Multi-controllers. It is a CPU module dedicated to process ladder sequences.
„ Features -
-
-
-
-
The high-speed instruction processing capability of the F3SP21 makes it ideal for applications that require high speed and quick response. The use of index qualification and an object ladder language simplifies program design and program maintenance. The module permits reconfiguration of device size and operating mode according to the application in use. Program debugging and maintenance can be easily performed using a rich set of functions such as forced set/reset that takes effect regardless of the result of program execution. The programming tool link port is provided with a personal computer link feature, which allows the F3SP21 to connect to a higher-level computer or display without a personal computer link module. High-reliability design and powerful self-diagnostics are provided. Errors detected during program execution can be logged with predefined messages. Programs and data can be saved on an optional ROM pack. Programs can be protected using a protection feature. When installed in slot 2, 3 or 4, the F3SP21 functions as an add-on sequence CPU module.
„ Components and Functions
SP21-0N
RDY RUN ALM ERR
CPU module maintenance LEDs CPU
„ Specifications Item Control Mode I/O Control Mode Programming Language Number of Basic Instruction Instructions Application Instruction Processing Basic Instruction Speed Application Instruction Program Size Maximum Number of I/O Internal relay Device Size Data register Self-diagnostics Other Features
Current Consumption External Dimensions Weight
Specification Stored program, repetitive operation Refreshing method/direct I/O instruction Structured ladder language, mnemonic language 25 types
PROGRAMMER
227 types 0.18-0.36 µs per instruction From 0.36 µs per instruction
Programming tool interface connector
10 K steps (Can be written to ROM) 2048 points 4096 points 5120 points Memory error, CPU error, I/O error, syntax check, etc. Configuration functions (setting device size, output on error, as well as data lock-up range at power failure) Constant scan function (1 ms to 190 ms) Debugging functions (forced SET/RESET, online edit, scan operation, etc.) Error history function (64 records) Date/clock function (year/month/day/hour/minute/ second/day of week) Program protection functions Writing programs and data to ROM Personal computer link function 350mA(5V DC) 28.9(W)×100(H)×83.2(D) mm * 130g
*: Excluding protrusions (see external dimensions for details).
All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation
GS 34M6C01-01E
July 1, 2003-00
Page 10
10
<<Content>> <<Index>>
„ Error Processing
„ Operating Environment
Errors of different severity levels are indicated by individual LEDs located on the front panel of the CPU module.
This module is compatible with all main CPU module types when used as an add-on CPU.
RDY RUN ALM
ERR
*:
LED (READY) Green (RUN) Green (ALARM) Yellow (ERROR) Red
Meaning Fatal (When off): The hardware cannot run. Examples: CPU error Memory error When lit: A user program is running. Non-fatal (When lit): An error has occurred but the user program can still run. Examples: Power failure Communications error Error (when lit): The user program cannot start or continue execution. Examples: Program error I/O comparison error* I/O module error* Memory error Sequence processor error Instruction processing error* Scan timeout*
You can define the severity of these events as “Non-fatal” or “Error” in the configuration setup.
„ Model and Suffix Codes Model F3SP21
Suffix Code -0N
Style Code, Option Description Code, Memory: 10 K steps
„ External Dimensions Unit: mm
83.2
28.9 2
100
All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation
GS 34M6C01-01E
July 1, 2003-00