FA-M3 Basic Modules (Base, Power Supply, CPU Modules and ROM Packs) General Specifications, pages 1 to 10

Pages 1 to 10 of 38

The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Yokogawa F3PU20 and Hirata F3PU20

Page 1

<<Contents>> <<Index>>

General Specifications

FA-M3 Basic Modules (Base, Power Supply, CPU Modules and ROM Packs)

Contents F3BU04-0N, F3BU06-0N, F3BU09-0N, Base Modules ................................................... 3 F3BU13-0N, F3BU16-0N F3PU10-0N, F3PU10-0S, F3PU20-0N, Power Supply Modules...................................... 4 F3PU20-0S, F3PU30-0N, F3PU16-0N, F3PU26-0N, F3PU36-0N F3SP21-0N

Sequence CPU Module ..................................... 9

F3SP25-2N

Sequence CPU Module ................................... 11

F3SP28-3N

Sequence CPU Module ................................... 13

F3SP28-3S

Sequence CPU Module ................................... 15

F3SP35-5N

Sequence CPU Module ................................... 17

F3SP38-6N

Sequence CPU Module ................................... 19

F3SP38-6S

Sequence CPU Module ................................... 21

F3SP53-4H

Sequence CPU Module ................................... 23

F3SP53-4S

Sequence CPU Module ................................... 25

F3SP58-6H

Sequence CPU Module ................................... 27

F3SP58-6S

Sequence CPU Module ................................... 29

F3SP59-7S

Sequence CPU Module ................................... 31

F3BP20-0N

BASIC CPU Module ........................................ 33

F3BP30-0N

BASIC CPU Module ........................................ 35

RK10, RK30, RK50

ROM Packs ..................................................... 37

RK33, RK53, RK73, RK93

ROM Packs ..................................................... 38

Yokogawa Electric Corporation

GS 34M6C01-01E 1st Edition: April, 1997 6th Edition: April, 2004

Page 2

This page is a scan with no text; see it in the PDF.

Page 3

3

<<Content>> <<Index>>

General Specifications

F3BU04-0N, F3BU06-0N, F3BU09-0N, F3BU13-0N, F3BU16-0N Base Modules

„ General FA-M3 base modules serve as the base for accommodating various modules. FA-M3 base modules are available in 4-, 6-, 9-, 13- and 16-slot versions. Choose an appropriate base module according to the target system requirements. There are no differences between main units and sub-units.

„ Specifications F3BU04-0N

F3BU06-0N

F3BU09-0N

F3BU13-0N

F3BU16-0N

4

6

9

13

16

3

5

8

12

15

Number of slots Number of I/O slots* Current consumption Weight (g) *:

■ Model and Suffix Codes Model F3BU04 F3BU06 F3BU09 F3BU13 F3BU16

50mA(5V DC) 140g

200g

310g

420g

550g

Number of I/O slots that can be used with a single CPU module.

Suffix Code -0N -0N -0N -0N -0N

Style Code

Option Code, - - - - - - - - - Description 4 slots (excluding slots for power supply) 6 slots (excluding slots for power supply) 9 slots (excluding slots for power supply) 13 slots (excluding slots for power supply) 16 slots (excluding slots for power supply)

„ External Dimensions Unit: mm 16 slots (F3BU16-0N) 13 slots (F3BU13-0N) 9 slots (F3BU09-0N) 6 slots (F3BU06-0N) 4 slots (F3BU04-0N)

5 mounting holes (for M4 mounting screw) 9.6

85 100

10.5 88.8

4.5 Mounting width: W3

(When mounted on module surface)

Base Modules

Full width W1

F3BU04-0N F3BU06-0N F3BU09-0N F3BU13-0N F3BU16-0N

147 205 322 439 527

7.5 Mounting width: W4 Mounting width: W2 Full width: W1

Mounting width W2 W3 W4 138 - - 196 - - 313 138 - 430 196 - 517 138 313

All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation

Note: - Make sure that the total current consumption of the modules to be installed does not exceed the current capacity of the power supply module. - The F3BU16-0N module cannot be mounted on a DIN rail. - The signal ground of the main unit is attached to the metal chassis of the base modules.

GS 34M6C01-01E

July 1, 2003-00

Page 4

4

<<Content>> <<Index>>

General Specifications

F3PU10-0N, F3PU10-0S, F3PU20-0N, F3PU20-0S, F3PU30-0N, F3PU16-0N, F3PU26-0N and F3PU36-0N Power Supply Modules Note: F3PU30-0N and F3PU36-0N are not UL certified.

General FA-M3 power supply modules supply power to the FA-M3 Range-free Multi-controllers. One power supply module is required for each FA-M3 base module. The F3PU10-0N is used for the F3BU04-0N and F3BU06-0N base modules. The F3PU20-0N and F3PU26-0N are used for the F3BU09-0N, F3BU13-0N and F3BU16-0N base modules.

Specifications Specification Item

F3PU10-0N / F3PU10-0S*1

Supply voltage Supply voltage fluctuation range Power consumption

F3PU20-0N / F3PU20-0S*1

F3PU30-0N

F3PU26-0N

100-240 V AC, single phase, 50/60 Hz

24 V DC

85-264 V AC, 50/60 Hz ±3 Hz

15.6-31.2 V DC

35 VA

85 VA

100 VA

15.4 W

20 A max.(120 V AC,Ta=25°C) 45 A max.(240 V AC,Ta=25°C)

Inrush current

F3PU36-0N

33.1 W

46.2 W

20A max. 31.2 V DC, Ta=25°C

Rated output voltage Rated output current

F3PU16-0N

5 V DC 2.0 A

4.3 A

6.0 A

2.0 A

4.3 A

6.0 A

Insulation resistance

500 V DC 5 MΩ or more between external AC terminals and FG terminal

500 V DC 5 MΩ or more between external DC terminals and FG terminal

Dielectric strength

1500 V AC for 1 minute between external AC terminals and FG terminal

1500 V AC for 1 minute between external DC terminals and FG terminal

Allowable momentary power failure time Noise immunity External dimensions *2 Weight

20 ms Noise level: 1500 Vp-p when measured by a noise simulator having a 1 µs of noise pulse width, 1 ns of rise time, and 25 Hz to 60 Hz of repetition frequency. 28.9(W) × 100(H) × 83.2(D) mm

58(W) × 100(H) × 83.2(D) mm

58(W) × 100(H) × 126.1(D) mm

28.9(W) × 100(H) × 83.2(D) mm

58(W) × 100(H) × 83.2(D) mm

58(W) × 100(H) × 126.1(D) mm

190g

320g

380g

190g

320g

380g

*1:

F3PU10-0N (respectively F3PU20-0N) and F3PU10-0S (respectively F3PU20-0S) have the same dimensions, internal circuitry and other characteristics, except that F3PU10-0N (respectively F3PU20-0N) uses M3.5-screw terminals while F3PU10-0S (respectively F3PU20-0S) uses M4-screw terminals.

*2:

Excluding protrusions (see external dimensions for details).

All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation

GS 34M6C01-01E Apr. July12, 1, 2004-00 2003-00

Page 5

5

<< Content >> <<Index>>

Components and Functions PU10-0N / PU10-0S RDY PU 10-0N

PU20-0N / PU20-0S

RDY indicator (green) Lit when the power supply module is normal.

POWER

RDY PU 20-0N

POWER

FAIL signal (contact output) Contact ratings: 24 V DC, 0.3 A FAIL OUTPUT FAIL1

During normal operation

During system and power failure

Between FAIL1 and COM

Open

Closed

Between FAIL2 and COM

Closed

Open

COM

FAIL2 FG

FAIL OUTPUT FAIL1

COM

FAIL2

FG: Class D grounding (JIS Class 3 grounding)

FG

LG: Connected to FG and grounded LG

LG

Power supply N

100-120V AC

100-240V AC

L

N

L

INPUT 100 - 240VAC

INPUT100 -240VAC

YOKOGAW A

YOKOGAWA

F3PU10-0N

F3PU20-0N

RDY indicator (green) Lit when the power supply module is normal

RDY

POWER

PU30-0N

FAIL signal contact output Contact ratings: 24 V DC, 0.3 A

Between FAIL 1 and COM Between FAIL 1 and COM

During normal operation Open Closed

During system and power failure Closed Open

FAIL OUTPUT FAIL1

COM

FAIL2

FG: Class D grounding (JIS Class 3 grounding) LG: Connected to FG and grounded

FG LG N

Power supply 100-240V AC

L INPUT 100-240V AC

`

F3PU30-0N

All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation

GS 34M6C01-01E Apr. July12, 1, 2004-00 2003-00

Page 6

6

<< Content >> <<Index>>

RDY indicator (green) Lit when the power supply module is normal.

RDY

PU 16-0N

POWER

During normal operation

During system and power failures

Between FAIL1 and COM

Open

Closed

Between FAIL2 and COM

Closed

Open

OUTPUT FAIL1

FAIL OUTPUT FAIL1

COM

FAIL2

FAIL2

FG

POWER

PU26-0N

FAIL signal contact output Contact ratings: 24 V DC, 0.3 A

FAIL

COM

RDY

FG: Class D grounding (JIS Class 3 grounding)

FG

LG: Connected to FG and grounded LG

LG

_

Power supply 24V DC

_

+

+

INPUT 24VDC

INPUT 24VDC

YOKOGAWA

YOKOGAWA

F3PU16-0N

F3PU26-0N

RDY indicator (green) Lit when the power supply module is normal

RDY PU36-0N

FAIL signal contact output Contact ratings: 24 V DC, 0.3 A

Between FAIL 1 and COM Between FAIL 1 and COM

During normal operation Open Closed

During system and power failure Closed Open

POWER

FAIL OUTPUT FAIL1

COM

FAIL2

FG: Class D grounding (JIS Class 3 grounding)

FG

LG: Connected to FG and grounded

LG -

Power supply 100-240V AC

+ INPUT 24V DC

F3PU36-0N

All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation

GS 34M6C01-01E

July 1, 2003-00

Page 7

7

<<Content>> <<Index>>

„ Terminal Dimensions F3PU10-0N / F3PU20-0N

Model and Suffix Codes

F3PU10-0S / F3PU20-0S

M3.5

Model

M4, - -0S, - -0N, - -0S, - F3PU30

-0N, - F3PU16

-0N, - F3PU26

-0N, - F3PU36

-0N, - 7.1mm M8.2mm

M8.2mm F3PU20

„ Examples of Applicable Solderless Terminals Vender

Model

Applicable Conductor

Japan Solderless V1.25-M3 Terminal Mfg. Co., Ltd. AWG22 to 18 Nippon Tanshi Co., Ltd. RAV1.25-3.5 (0.33 to 0.82 mm2) (Copper wire) Japan Solderless V1.25-M4 Terminal Mfg. Co., Ltd. AWG16 to 14 Japan Solderless V2-M4 (1.25 to 2.0 mm2) Terminal Mfg. Co., Ltd. (Copper wire)

Option Code

-0N

F3PU10 7.1mm

Suffix Style Code Code

Description 100-240 V AC, for 4- and 6-slot base modules (M3.5 screws) 100-240 V AC, for 4- and 6-slot base modules (M4 screws) 100-240 V AC, for 9-, 13-, and 16-slot base modules (M3.5 screws) 100-240 V AC, for 9-, 13-, and 16-slot base modules (M4 screws) 100-120 V AC, for 9-, 13-, and 16-slot base modules 24 V DC, for 4- and 16-slot base modules 24 V DC, for 9-, 13-, and 16-slot base modules 24 V DC, for 9-, 13-, and 16-slot base modules

Applicable Modules and Crimping Torque F3PU10-0N F3PU10-0S F3PU20-0N F3PU20-0S F3PU30-0N F3PU36-0N May not be used 0.8N • m 1.2N • m

„ External Dimensions Unit: mm

F3PU10-0N, F3PU10-0S, F3PU16-0N

83.2

F3PU20-0N, F3PU20-0S, F3PU26-0N

28.9

83.2

58

2

2

100

100

All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation

July12, 1, 2004-00 2003-00 GS 34M6C01-01E Apr.

Page 8

8

<<Content>> <<Index>>

„ External Dimensions (2/2) Unit: mm

F3PU30-0N

(12.9)

58

58 2

30

2

83.2

RDY

POWER

PU36-0N

POWER

FAIL OUTPUT

FAIL OUTPUT

FAIL1

FAIL1

COM

COM

FAIL2

FAIL2

100

100

PU30-0N

RDY

FG

FG

LG

LG

N L INPUT 100-240V AC

INPUT 24V DC

F3PU30-0N

All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation

F3PU36-0N

GS 34M6C01-01E

July 1, 2003-00

Page 9

9

<<Content>> <<Index>>

General Specifications

F3SP21-0N Sequence CPU Module

„ General The F3SP21 is a CPU module for the FA-M3 Range-free Multi-controllers. It is a CPU module dedicated to process ladder sequences.

„ Features -

-

-

-

-

The high-speed instruction processing capability of the F3SP21 makes it ideal for applications that require high speed and quick response. The use of index qualification and an object ladder language simplifies program design and program maintenance. The module permits reconfiguration of device size and operating mode according to the application in use. Program debugging and maintenance can be easily performed using a rich set of functions such as forced set/reset that takes effect regardless of the result of program execution. The programming tool link port is provided with a personal computer link feature, which allows the F3SP21 to connect to a higher-level computer or display without a personal computer link module. High-reliability design and powerful self-diagnostics are provided. Errors detected during program execution can be logged with predefined messages. Programs and data can be saved on an optional ROM pack. Programs can be protected using a protection feature. When installed in slot 2, 3 or 4, the F3SP21 functions as an add-on sequence CPU module.

„ Components and Functions

SP21-0N

RDY RUN ALM ERR

CPU module maintenance LEDs CPU

„ Specifications Item Control Mode I/O Control Mode Programming Language Number of Basic Instruction Instructions Application Instruction Processing Basic Instruction Speed Application Instruction Program Size Maximum Number of I/O Internal relay Device Size Data register Self-diagnostics Other Features

Current Consumption External Dimensions Weight

Specification Stored program, repetitive operation Refreshing method/direct I/O instruction Structured ladder language, mnemonic language 25 types

PROGRAMMER

227 types 0.18-0.36 µs per instruction From 0.36 µs per instruction

Programming tool interface connector

10 K steps (Can be written to ROM) 2048 points 4096 points 5120 points Memory error, CPU error, I/O error, syntax check, etc. Configuration functions (setting device size, output on error, as well as data lock-up range at power failure) Constant scan function (1 ms to 190 ms) Debugging functions (forced SET/RESET, online edit, scan operation, etc.) Error history function (64 records) Date/clock function (year/month/day/hour/minute/ second/day of week) Program protection functions Writing programs and data to ROM Personal computer link function 350mA(5V DC) 28.9(W)×100(H)×83.2(D) mm * 130g

*: Excluding protrusions (see external dimensions for details).

All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation

GS 34M6C01-01E

July 1, 2003-00

Page 10

10

<<Content>> <<Index>>

„ Error Processing

„ Operating Environment

Errors of different severity levels are indicated by individual LEDs located on the front panel of the CPU module.

This module is compatible with all main CPU module types when used as an add-on CPU.

RDY RUN ALM

ERR

*:

LED (READY) Green (RUN) Green (ALARM) Yellow (ERROR) Red

Meaning Fatal (When off): The hardware cannot run. Examples: CPU error Memory error When lit: A user program is running. Non-fatal (When lit): An error has occurred but the user program can still run. Examples: Power failure Communications error Error (when lit): The user program cannot start or continue execution. Examples: Program error I/O comparison error* I/O module error* Memory error Sequence processor error Instruction processing error* Scan timeout*

You can define the severity of these events as “Non-fatal” or “Error” in the configuration setup.

„ Model and Suffix Codes Model F3SP21

Suffix Code -0N

Style Code, Option Description Code, Memory: 10 K steps

„ External Dimensions Unit: mm

83.2

28.9 2

100

All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation

GS 34M6C01-01E

July 1, 2003-00