The TRIAC output can be used in AC load only, and due to the TRIACs need to maintain its conductivity, the load current should be larger than the holding current (25mA). Thus, when the load current is smaller than 25mA, virtual load should be connected in parallel with the load current to make the load current larger than the holding current of the TRIAC. Besides, there is a 1mA (AC100V) or 2mA (AC200V) leakage current even if the output circuit of the TRIAC is in the OFF state. Beware of the trace current activating the load, use a virtual resistance connected in parallel with the load to eliminate the affect of the leakage.
The rated current for every TRIAC output point is 0.3A, but never exceed 0.2A in case of multiple points conducted simultaneously in the same common block in order to avoid internal temperature rise and affecting the life span. The rated current for every TRIAC output point is 0.3A, but never exceed 0.2A in case of multiple points conducted simultaneously in the same common block in order to avoid internal temperature rise and affecting the life span.