Quick Reference Guide

ABB Kent-Taylor MICRO-SCAN™ 200 Controller

ABB Kent-Taylor

ASEA BROWN BOVERI

Page 2 read from a scan by OCR; it may hold reading errors

DISPLAYS AND ENTRIES

The MICRO-SCAN 200 generates display prompts to make set-up and operation fast and easy. The appearance of specific prompts depends upon input selection, output form, and operating configuration. Refer to appropriate instruction manual for details.

[A] up key: Selects YES response. Increases value or level.

[v] down key: Selects no response. Decreases value or level.

scroll key: Depress to enter level or move through prompts.

Main Secondary

Description and Valid Ent Display Disp. Entry seription a a v

AC. FAIL _ Diagnostic message. Starting point at start-up. See back cover for other diagnostic messages.

LEU.1 dSPL. LEVEL 1, DISPLAY. Point of entry.

XXX XXX Process value and set-point or output display, or totalized value display.

X.X.X X XXX Alarm status (see back cover)

r-SP. Remote set-point (d-SP must be no);

no, remote set-point not required, YES, remote set-point active. d-SP. Dual set-point (r-SP must be no);

no, dual set-point not required, YES, dual set-point active.

bAL XXX Balance. Difference between remote/ local or dual/ocal set-point values. dEbL no Digital Input enable. YES = enable.

totL dSPL _ Totalizer status.* rA_P SoAK. Ramp/soak status.

CodE xxx Access code required for tune or configure entry to other levels. nee “**See instructions for description of ramp/soak reset (rS.rS), ramp/soak skip (rS.Sk), or totalizer reset (r.tot).

AUto tUnE Auto tune procedure. See instructions. LEU.2 tUnE LEVEL 2, TUNE. Point of entry. All except heat/cool dGAP Differential gap; 0 to span value. P.b nd Proportional band; 0.1 to 999.9%.

Page 3 read from a scan by OCR; it may hold reading errors

Main Secondary _pescription and Valid Entr Display Disp. Entry escriplion a ame eniny

Intr YES, integral response; reset enabled, no, no reset action. lrAt. Integral ratio value; 0.1 to 120 rpt/min. En YES, manual reset enabled (Intr = no}, no, no manual reset action. _rSt Manual reset value; 0 to 100.0%. driu Derivative rate; 0 to 999.9 sec. rAto Ratio function; 0 to 99.99. bIAS Bias function;, 999 to 9999. d.bnd Dead band (position proportioning); 2.0 to 50.0%. CY Ct Cycle time; 1.0 to 300.0 sec. Heat/cool control bnd.H. Proportional band heat; 0.1 to 999.9%. bnd.c. Proportional band cool; 0.1 to 999.9%. | nur.H. Integral (reset) value heat; 0.1 to 120 rpt/min. I nur.C. Integral (reset) value cool; 0.1 to 120 rpt/min. Cros Heat/cool output crossover; 0.1 to 99.9%. HHYS Crossover transition band width; 0 to crossover value in % output. oHYS Crossover output off hysteresis; + 25.0 value in % output. C Y.t.H. Cycle time heat; 1.0 to 300.0 sec. C Y4+4.C. Cycle time cool; 1.0 to 300.0 sec.

LEU.3 ALrS. LEVEL3, ALARMS. Point of entry. d!ISP ALrS&S._ Display alarms. Point of entry. ALri SEt Alarm 1 set. Point of entry.

tYPE H.PrC - High process (L.PrC+3 to 9999) L.PrC - Low process ( - 999 to H.PrC, 3) H.dEU - High deviation (0.1 to 9999) L.dEU - Low deviation (0.1 to 9999) H.oUt - High output (10 to oP.HI) L.oUt - Low output (oP.Lo to oP.HI) nonE - No alarm setting

HEAt YES, output alarm trip-point value in heat band, no, value is in cool band. triP Alarm trip-point value (see type).

PrtyY Alarm priority; 1 or 2 (1 is high priority).

Page 4 read from a scan by OCR; it may hold reading errors

Main =‘ Secondary Description and Valid Entr Display Disp. Entry P y

HY St. Alarm hysteresis value; 0 to 1000 = dead band value in engineering units.

ALr2 SEt Alarm 2 set. Point of entry. See ALr.1.

ALr3 SEt Alarm 3 set. Point of entry. See ALr.1.

ALr4 SEt Alarm 4 set. Point of entry. See ALr.1.

rELY SEt Relay set. Point of entry.

rLYA SEt Relay A set. Point of entry.

CntlL rELY Control relay not InSt Relay not installed rLYb SEt Relay b set. Point of entry.

rACt Relay action; nonE, ALrsS, r§, totL.

tACt Relay trip action; Alarm set 1, 2, 3, 4, or any combination of 1 through 4.

rLYyc SEt Relay C set. Point of entry. See rLY.b.

ACk- ALrS.. Alarm acknowledge. Point of entry.

ACk.1 YES, relay follows alarm action, no, relay doesn't follow alarm action.

AC k2 YES, alarm relay latches until acknowledged, no, no latching.

LEU.4 HI.Lo LEVEL 4, HIGH/LOW. Point of entry.

o P.H I Output high limit; 10.0 to 100.0% relay output span. 10.0 to 110.0% mA out- put span.

Ho.H | Heat output high limit; 10.0 to 99.9% heat output span.

o P.Lo Output low limit; 0 to oP.HI - - .1 = % relay output span., 10.0 to oP.HI, .1 = % mA output span.

CoH I Cool output high limit; 10.0 to 99.9% cool output span.

$SP-H Local set-point high limit;, 999 to 9999.

SP-L Local set-point low limit;, 999 to 9999.

d.S P.E YES, dual set-point selectable in Level 1. no, dual set-point not enabled.

S P.2.H Dual set-point high value;, 999 to 9999.

S P.2.L Dual set-point low value;, 999 to 9999.

S P.2 Dual set-point start value;, 999 to 9999.

d!/G. InPt Digital input. Point of entry.

Lkot Yes, lockout front panel changes to digital input action, no, disable lockout.

Page 5 read from a scan by OCR; it may hold reading errors

Main Secondary

Descripti id Vali Display Disp. Entry ption and Valid Entry dIFC Function; A.to.__ (auto/manuai), L.to.r (local/remote), F.d.SP (fixed dual set- point), AAACk (alarm acknowledge), rS (ramp/soak), tot (totalizer), or NOtH.

Co Ut YES, Use configured output value when transferring to manual, no does not.

CFod Configured output value; 0 to 100%.

r S.F Ramp/soak fuction; rn.Hd (run/hold), or rn.St (run/stop).

totF Totalizer function; rS.St (reset/start), or St.St (start/stop).

F.S P.1 Fixed dual set-point 1; SP-H to SP-L.

F.S P.2 Fixed dual set-point 2; SP-H to SP-L.

toGL. YES, Set toggling action for A/M, L/R.

dACt Digital action; dir (direct), rEU (reverse).

rA_.P SOAK _ Rampisoak profile. Point of entry.* totL C nF G Totalizer configuration. Point of entry.” rtEn Retransmission output enable. YES or no. Set at no for Hc.d_..

P.U.H | Retransmission process high;, 999 to 9999 (20 mA retransmission output).

P.U.L 0 Retransmission process low; ~999 to 9999 (4 mA retransmission output).

Fo Ut Fault output; 0 to 100% output.

F.PEr Fault detection level % of volt input span (limits:, .05 to 6.45 V,, 48.3 to 193 mV, .02 to 49.6 mA); 0 to 100%.

roPt Recovery Option; __ An, or LASt.

LEU.S5 InPt. LEVELS, INPUT. Point of entry.

In P.H Input high range value; 5.00 to 20.00 mA dc, 10.0 to 150.0 mV dc, or 0.1 to 5.00V de.

In P.L Input low range value; 4.00 to 19.00 mA, 0.0 to 140.0 mV, or 0.00 to 4.90V.

d.P.- - Decimal point; 0., 0.0, 0.00, 0.000 posi-tions (units, tenths, etc.) for mA, mV, V; 0., 0.0 for tC, RTD.

SQ-L Square law; YES, square law linearization of input, no, square root not extracted.

EnGdH Engineering units, high;, 999 to 9999.

EnGl Engineering units, low;, 999 to 9999 (applies only when SQ-L not selected).

Page 6 read from a scan by OCR; it may hold reading errors

Main Secondary Display Disp. Entry

Description and Valid Entry tYPE dEGC

SPAn

A _. b.

rb.t Y src bAL rsrc bSrc nbAL b.bAL

Type thermocouple; J-tC, K-tC, E-tC, r-tC, $-tC, t-tC, b-tC, or n-tC.

Temperature units; YES, selects Celsius, no, selects Fahrenheit.

Span; .001 to 9999 (controller gain calculation; process input span in engineering units is recommended except for a temperature controller gain of 100).

YES, A/M ratio bias station enabled, no, A/M ratio bias station not enabled.

Type of station; rAto, DIAS, r.b. Source (ratio or bias); LoC, rE__. Balance (ratio or bias); StAn, AUto. Ratio source (for r.b.); LoC, rE__. Bias source (for r.b.); LoC, rE_. Ratio balance (for r.b.); StAn, AUto. Bias balance (for r.b.); StAn, AUto.

LEU.6 Enob.l. AUto tUnE tPA S. CPAS. P.U P.__

PdE P.o Ut oUAL SPtk drct ACtG drCt CooL r Uo P.

nS P.E

LEVEL 6, ENABLE. Point of entry. Auto tune enable.*

Tune password; 0 to 9999. Configure password; 0 to 9999.

YES, power up message displayed, no, power up message suppressed.

LASt, power up mode is last mode, __An, power up mode is manual, AUto, power up mode is auto.

Power up output value; LASt, F.VAL.

Fixed output value; 0.0 to output high/ low limit.

YES, activates set-point tracking, no, no set-point tracking.

YES, selects direct control action, no, selects reverse control action.

YES, selects cool relay closed for 100% cool output, no, selects cool relay open for 100% cool output.

YES, selects reverse output (20 to 4 mA), no, selects direct output (4 to 20 mA).

YES, remote set-point selectable in Level 1, no, remote set-point not enabled.