The text of a spec sheet · part 2 of 10
Switching Devices according to UL489, UL508 and UL1077, pages 11 to 20
Pages 11 to 20 of 92
The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the ABL Sursum 3B16UM
Page 11
Reykjavik
Helsinki
Representatives throughout Europe: Belgium Denmark Estonia Finland France Greece Great Britain Ireland Italy Latvia Lithuania Luxemburg
Rud Tallinn
Norrkoping
Netherlands Norway Austria Poland Portugal Romania Sweden Switzerland Slovakia Spain Czech Republic Hungary
Riga
Moscow
Vilnius
Kopenhagen
Minsk
Dublin Watford
Wijk bij Duurstede
Brussels Luxembourg Holtzheim Spreitenbach Milan
Warsaw Kiev Prague Bratislava Vienna
Budapest Bucharest Sofia
Barcelona Lisbon
Athens
Shanghai New Dehli
Taiwan International representatives:
Bangkok Ho-Chi-Minh-City Singapore
Auckland
Egypt Argentina Azerbaijan Bolivia Bosnia Herzegovina Chile China Georgia India Iceland Canada Croatia Morocco
Mexico New Zealand Russia Singapore South Africa Taiwan Thailand Ukraine USA Venezuela United Arab Emirates Vietnam Belarus
11
Page 12
1
Functional form • Modern design • User-friendly ergonomics • Easy-to understand product designation • Clearly legible ON/OFF labelling
3
UL Circuit breakers in an uniform and modern design
4
Extensive application possibilities • Three product ranges for circuit protection, manual motor controlling and supplementary protection applications • AC and DC versions available • European and North American standard tripping characteristics with the widest range of nominal ratings
Rated current Characteristic
Circuit diagram
Rated voltage
Approval
No. of Poles Rated breaking capacity
Approval for heating devices, refrigerating systems, air-conditioning systems Product range
2
Compact design offering maximum wiring space • With 105 mm installation height one of the smallest circuit breakers according to UL489 • With 89,3 mm the smallest UL508 manual motor controller • The same small dimensions of 89,3 mm for UL1077 supplementary protector
• UL489 AC, 0.3 - 63 A, 1-pole/2-pole/3-pole UL product range characteristics AC: B, C, D, Z DC, 0.3 - 63 A, 1-pole/2-pole DL product range characteristic C
UL489 Height only 105 mm
12
UL508 UL1077 Height only 89,3 mm
• UL508 0.3 - 63 A, 1-pole/2-pole/3-pole acc. to UL508 and CSA-22.2 No.14 UM product range, B, C, D,G, E and Z characteristic B, C and D up to 25 A also acc. to IEC 60898-1, DIN EN 60898-1, VDE 0641-11 • UL1077 0.5 - 63 A, 1-pole/2-pole/3-pole acc. to UL1077 and CSA-22.2 No.235 UR product range characteristic B, C, and D
Page 13
Switching Devices from ABL SURSUM have a lot to commend them
5
Complete Product System • Full range of accessories for UL489 Circuit breakers • Common line of accessories for UL508 and UL1077 Product lines • Full range of auxiliary switches • Shunt trip and neutral pole can be added on the left and the right side
Auxiliary contact
Neutral switch
Shunt trip
Lock-off/ Lock-on device
Touch protection caps
File E 335632
6
Professional labeling System with a marking window Blank perforated labels available for one pole, two pole and three pole windows for convenient circuit indication
7
Standard dual connection method for all three product ranges • Box clamp terminal (line load reversible) • for solid and flexible conductors Top: 18-3AWG (1,0 mm2 - 25 mm2) Bottom: 18-2AWG (1,0 mm2 - 35 mm2) • for busbars Unique way of connecting for convenient connection of all types of cable lugs (ring tonque and fork cable lugs)
1 module
2 modules
3 modules
13
Page 14
Busbars available for UL489 device
Busbars available for UL508 and UL1077 device
Extensive application possibilities • Extensive application possibilities • Three product ranges for circuit protection, manual motor controlling and supplementary protection applications • AC and DC versions available • European and North American standard tripping characteristics with the widest range of nominal ratings
UL
Product Range
DL
UM **
UR **
Standards
UL489
UL508
UL1077
UL File
E 329510
E 137938
E 137915
Rated voltage
240 V AC
277 V AC
480 V AC
125 V DC
250 V DC
277 V AC
480 V AC
42 V DC
80 V DC
24 V DC
60 V DC
277 V AC
480 V AC
Number of poles
1 / 1+N* / 2/3/ 3+N*
1 / 1+N*
2/3/ 3+N*
1
2
1 / 1+N*
2/3/ 3+N*
1
2
1
2
1 / 1+N*
2/3/ 3+N*
1-63 A
1-63 A
1-25 A
1-25 A
30-63 A
30-63 A
1-63 A
1-63 A
0.3-63 A
0.3-63 A
0.3-25 A
0.3-25 A
30-63 A
30-63 A
0.3-63 A
0.3-63 A
0.3-63 A
0.3-63 A
0.3-25 A
0.3-25 A
30-63 A
30-63 A
0.3-63 A
0.3-63 A
E - Characteristic
0.3-63 A
0.3-63 A
0.3-25 A
0.3-25 A
30-63 A
30-63 A
G - Characteristic
0.3-63 A
0.3-63 A
0.3-25 A
0.3-25 A
30-63 A
30-63 A
Z - Characteristic
0.3-50 A
0.3-50 A
0.3-25 A
0.3-25 A
30-50 A
30-50 A
B - Characteristic C - Characteristic
40-63 A
0.3-32 A
0.3-32 A
D - Characteristic
40-63 A
0.3-32 A
0.3-32 A
0.3-63 A
* N pole to be mounted separately
14
0.3-63 A
** UL approval up to 60 A
Page 15
Full range of accessories for UL489 , UL508 and UL1077 • Auxiliary switches • Shunt trip and Neutral pole can be added on the left and the right side
Lock-off/ Lock-on device
Neutral switch UL489
Shunt trip UL489
Auxiliary contact UL489
UL489 Listed Circuit Breakers AC Distribution Equipment
Neutral switch UL508 UL1077
Shunt trip UL508 UL1077
UL508 Listed Manual Motor Controller Industriel Control Equipment
Auxiliary contact UL508 UL1077
UL1077 Supplementary Protector
Main Characteristics Listed component Recognized components for supplementary protection only Field wiring Factory wiring Feeder circuit protection Branch circuit protection Control Circuits Functions Short circuit protection Switching function Disconnect function Overload protection Applications Heaters, coolesr, -air conditioning (HACR approval) Protection of outlets Transformers Motor protection Control transformers Resistive load Appliances, Business Equipment General lamps Fuorescent lamps
15
Page 16
Wiring Diagram with Switching Devices acc. to UL489, UL508 and UL1077 Scematics according to European standards
Power Circuit
Power Circuit
Power Circuit
UL489
UL489
Power Circuit
Power Transformer
UL489
UL489
Control Circuit Control Transformer
UL508 or UL1077
Power Transformer
UL508 or UL1077
UL489
UL489
UL508
Pushbutton OFF
Pushbutton OFF
Pushbutton ON
Pushbutton ON
UL508
UL489
UL508
M
M
Sizing of main branch circuit protector according to table 430.52 in NEC® • Dual Element (Time Delay) Fuse Maximum fuse = largest motor FLA x 175 % + FLA of all other motors and general loads in group • Inverse Time Breaker Maximum circuit breaker = largest motor FLA x 250 % + FLA of all other motors and general loads in group (for other fuse/breaker types see table 430.52)
16
General Loads
Heaters
Lamps
Coolers
Fluorescent Lamps Resistive load
Air Conditioner
Motors
Socket Outlets
Blowers
Page 17
Wiring Diagram with Switching Devices acc. to UL489, UL508 and UL1077 Scematics according to North American standards
Power Circuit
UL489
UL489 Power Circuit
Power Transformer
Control Circuit UL489 Control Transformer
Power Transformer UL508 or UL1077
UL489
UL508 or UL1077
UL508
UL489
UL489
UL508 or UL1077
UL508
M
M
Outlet
Fixed mounted cabinet/panel heater (resistive loads)
Sizing of main branch circuit protector according to table 430.52 in NEC® • Dual Element (Time Delay) Fuse Maximum fuse = largest motor FLA x 175 % + FLA of all other motors and general loads in group • Inverse Time Breaker Maximum circuit breaker = largest motor FLA x 250 % + FLA of all other motors and general loads in group (for other fuse/breaker types see table 430.52)
17
Page 18
ABL))SURSUM a Qe ry ce .
c16 16 @- ‘4;
AgoviaTTV AC USP 3c 16UL
18
Page 19
Switching Devices according to UL489 and CSA-22.2 No. 5-09
Listed circuit breakers according to UL489 and CSA-22.2 No.5-09 help with the complex selection of the correct type and characteristics compared to traditional fuse installation, and offer a less space-consuming installation solution. Our range of miniature moulded case circuit breakers combined with our factory or field mounted accessories offer enhanced control and monitoring capabilities. Field mounting kits include all parts and instructions to ensure easy installation on site. We supply 1, 2 and 3-pole-type switching devices according to UL489 from 0.3 to 63 Ampere and with C and D characteristics. Furthermore, attachments such as neutral switches, auxiliary contacts and shunt trips are available for this system. All accessories for modern busbar installations are available in accordance with the relevant UL standards.
19
Page 20
Switching Devices Listed Circuit Breakers AC according to UL489 and CSA-22.2 No. 5-09 UL Product Range, AC Version, C and D Characteristics
File E 329510
Rated current voltage
C
D
In A
Volt AC
Article no.
Article no.
0.3 0.5 1 1.6 2 3 4 5 6 8 10 12 13 15 16 20 25
277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480
1C03UL 1C05UL 1C1UL 1C1.6UL 1C2UL 1C3UL 1C4UL 1C5UL 1C6UL 1C8UL 1C10UL 1C12UL 1C13UL 1C15UL 1C16UL 1C20UL 1C25UL
30
277/480
32 40 50 60 63
277/480 240 240 240 240
0.3 0.5 1 1.6 2 3 4 5 6 8 10 12 13 15 16 20 25
Characteristic *
Weight g/each
Packing unit
1D03UL 1D05UL 1D1Ul 1D1.6UL 1D2UL 1D3UL 1D4UL 1D5UL 1D6UL 1D8UL 1D10UL 1D12UL 1D13UL 1D15UL 1D16UL 1D20UL 1D25UL
155 155 155 155 155 155 155 155 155 155 155 155 155 155 155 155 155
12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
1C30UL
1D30UL
155
12
1C32UL 1C40UL 1C50UL 1C60UL 1C63UL
1D32UL 1D40UL 1D50UL 1D60UL 1D63UL
155 155 155 155 155
12 12 12 12 12
277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480
2C03UL 2C05UL 2C1UL 2C1.6UL 2C2UL 2C3UL 2C4UL 2C5UL 2C6UL 2C8UL 2C10UL 2C12UL 2C13UL 2C15UL 2C16UL 2C20UL 2C25UL
2D03UL 2D05UL 2D1Ul 2D1.6UL 2D2UL 2D3UL 2D4UL 2D5UL 2D6UL 2D8UL 2D10UL 2D12UL 2D13UL 2D15UL 2D16UL 2D20UL 2D25UL
310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310
6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
30
277/480
2C30UL
2D30UL
310
6
32 40 50 60 63
277/480 240 240 240 240
2C32UL 2C40UL 2C50UL 2C60UL 2C63UL
2D32UL 2D40UL 2D50UL 2D60UL 2D63UL
310 310 310 310 310
6 6 6 6 6
Rated
1-pole
2-pole
* Also available in B and Z characteristics on request
20