Spec sheet · ABL Sursum
Switching Devices according to UL489, UL508 and UL1077
Spec sheet92 pagesPDF 13 MB
ABL Sursum catalog of DIN-rail circuit breakers, manual motor controllers and supplementary protectors to UL489, UL508 and UL1077, including the 3B16UM.
Covers · 1 model
The models it covers
Summary
What is in it
A product catalog from ABL SURSUM covering its DIN-rail switching devices for North American standards: UL489 circuit breakers (AC and DC), the UM range of UL508 manual motor controllers (which lists the 3B16UM), the MA and MS manual motor controllers, and the UR range of UL1077 supplementary protectors. Each range has product advantages, ordering tables, accessories, busbars and technical data, followed by an article number directory.
Its parts
- Editorial
- ABL SURSUM, the company
- Our representatives worldwide
- Switching devices acc. to UL489 and CSA-22.2 no. 5-09
- Switching devices acc. to UL508 and CSA-22.2 no. 14
- Manual Motor Controller MA
- Manual Motor Controller MS
- Switching devices acc. to UL1077 and CSA-22.2 no. 235
- ABL SURSUM, the product range
- Article number directory
From the sheet
Key facts from this sheet
Each line names its page in the PDF.
This is an ABL SURSUM product catalog of DIN-rail switching devices to UL489, UL508 and UL1077 and the matching CSA standards: circuit breakers, UM and MA manual motor controllers, MS motor controllers, UR supplementary protectors, accessories and busbars. The site files it under the 3B16UM, which appears in the 3-pole table of the UM manual motor controller range. It gives article numbers, accessories and technical data for choosing and installing these devices.
- Device type
- UM range manual motor controller to UL508 and CSA-22.2 No.14, built like a miniature circuit breaker p. 33
- Listing
- 3B16UM appears in the 3-pole table of the UM product range (B, C, D, G, E and Z characteristics) p. 37
- Motor use
- Suitable as Motor Disconnect and for Motor Starting Across the Line p. 33
- Rated voltage AC
- 277 / 480 V p. 42
- Standards
- The catalog states IEC 60898-1, DIN EN 60898-1, VDE 0641-11, UL508 and CSA-22.2 No.14; UL File E137938 p. 42
- Temperature
- Ambient -25 °C to +55 °C; storage -40 °C to +70 °C p. 42
- Mounting
- 35 mm DIN rail (DIN EN 60715), any position; device depth 68 mm p. 42
- Mechanical life
- 10,000 switching cycles (ON / OFF) p. 42
- Enclosure
- IP20 (EN/IEC 60529); finger safe protection cover p. 42
- Terminals
- Line/load reversible box terminals; torque max. 2.5 Nm (22.2 lb.in) p. 39, 43
- Auxiliary contacts
- H10UM (1NO), H11UM (1NO + 1NC), H12UM (1NO + 2NC), H21UM (2NO + 1NC) p. 38
- Shunt trips
- FA12UM (12 V UC), FA24UM (24 V UC), FA48UM (48 - 74 V UC), FA110UM (110 - 240 V UC, 415 V AC) p. 38
- Neutral switch, lock
- N63UM neutral switch, 0.3 - 63 A, 277/480 V AC; EASS lock-off/lock-on device p. 37, 38
What this sheet walks you through
- Choosing a UM device by poles, characteristic and rated current p. 35, 36, 37
- Matching the trip characteristic to the application p. 42
- Mounting auxiliary contacts, shunt trips and neutral switches p. 39
- Short circuit withstand ratings and back-up fuses p. 44
- Ampere and horsepower ratings for motor loads p. 45, 46
- Busbars for the UM range p. 40, 41
- Conductor sizes and stripping lengths for the terminals p. 43
Good to know
- UL508 manual motor controllers are control equipment without a short circuit protection function. p. 33
- 63 A ratings have no UL approval. p. 37
- The H...UM auxiliary contact can only be mounted on the right of the switching device. p. 39
- Thermal trip values fall at higher ambient temperature, by about 5% per 10°C. p. 42
- The fork type busbars have no UL or CSA approval. p. 41
Questions this sheet answers
Can the 3B16UM be used as a motor disconnect?
The catalog states that the UM motor controllers are Suitable as Motor Disconnect and can be used for Motor Starting Across the Line. p. 33
Does the 3B16UM give short circuit protection?
The catalog says manual motor controllers to UL508 and CSA-22.2 are control equipment without the function of short circuit protection. p. 33
Which auxiliary contacts fit ABL Sursum UM devices?
H10UM (1NO), H11UM (1NO + 1NC), H12UM (1NO + 2NC) and H21UM (2NO + 1NC). p. 38
What temperature range is the UM range rated for?
-25 °C to +55 °C ambient, and -40 °C to +70 °C in storage. p. 42
How is a UM manual motor controller mounted?
On a 35 mm DIN rail to DIN EN 60715, in any position. p. 42