Manual · ABL Sursum
ABL Switching Devices in compliance with UL 489, UL 508 and UL 1077
Manual78 pagesPDF 6.5 MB
Product catalog of ABL Sursum switching devices: UL 489 circuit breakers, UL 508 manual motor controllers such as the 3B16UM, UL 1077 protectors.
What this file really is
The old site listed this file as a manual for the ABL Sursum 3B16UM. The file is the ABL switching devices product catalog covering many breaker, motor controller and protector ranges, not a user manual for the 3B16UM.
Filed under · 1 model
Filed under these models in the old catalog
Summary
What is in it
ABL catalog of switching devices built to UL 489, UL 508 and UL 1077. It presents the UL and DL circuit breaker ranges (AC and DC), the UM, MA and MS manual motor controller ranges, and the UR supplementary protector range, each with product range tables, accessories, busbars and technical data, plus wiring diagrams for European and North American practice and an item number directory. The 3B16UM appears in the UM product range tables.
Its parts
- ABL Switching Devices Worldwide
- The Winning Features of ABL Switching Devices
- UL 489, UL 508 and UL 1077 Overview
- Wiring Diagram
- Switching Devices acc. to UL 489 and CSA-22.2 No. 5-09
- Switching Devices acc. to UL 508 and CSA-22.2 No. 14
- Switching Devices acc. to UL 1077 and CSA-22.2 No. 235
- Item Number Directory
From the manual
Key facts from this manual
Each line names its page in the PDF.
This is an ABL SURSUM catalog of switching devices to UL 489, UL 508 and UL 1077: UL and DL circuit breakers, UM, MA and MS manual motor controllers, UR supplementary protectors, accessories and busbars. The site files it under the 3B16UM, a 3-pole UM manual motor controller with characteristic B and a 16 A rated current. It gives item numbers, accessories, technical data and tripping curves for choosing and installing these devices.
- 3B16UM
- 3B16UM: 3-pole UM manual motor controller, characteristic B, 16 A rated current; 450 g each, packing unit 4 p. 31
- Device type
- Manual motor controller to UL 508 and CSA-22.2 No.14 in miniature circuit breaker design; Suitable as Motor Disconnect and for Motor Starting Across the Line p. 27
- Rated voltage AC
- 277 / 480 V p. 36
- B trip values
- Characteristic B: thermal 1.13 x In not tripping (> 1 h), 1.45 x In tripping (< 1 h); electromagnetic 3 x In not tripping, 5 x In tripping (< 0.1 s) p. 36
- Standards
- The catalog states IEC 60898-1, DIN EN 60898-1, VDE 0641-11, UL 508 and CSA-22.2 No.14; UL File E137938 p. 36
- Temperature
- Ambient -25 °C to +55 °C; storage -40 °C to +70 °C p. 36
- IEC interrupting capacity
- 2-pole and 3-pole, 480 V, 0.3 - 60 A: 10 kA, maximum back-up fuse 160 A (EN and IEC) p. 38
- Mounting
- 35 mm DIN rail (DIN EN 60715), any position; depth 68 mm, height 89.3 mm p. 6, 36
- Life, enclosure
- 10,000 switching cycles (ON / OFF); IP20 p. 36
- Terminals
- Line/load reversible box clamps: top 18-3AWG (1.0 - 25 mm2), bottom 18-2AWG (1.0 - 35 mm2); torque max. 2.3 Nm (20 lb.in) p. 7, 37
- Auxiliary contacts
- H10UM (1NO), H11UM (1NO + 1NC), H12UM (1NO + 2NC), H21UM (2NO + 1NC); rated 10 A /240 V AC, 3 A / 110 V DC p. 33
- Shunt trips
- FA12UM (12 V UC), FA24UM (24 V UC), FA48UM (48 - 74 V UC), FA110UM (110 - 240 V UC, 415 V AC) p. 33
- Neutral switch, lock
- N63UM neutral switch; EASS activation lock p. 31, 33
What this manual walks you through
- Choosing a 3-pole UM device by characteristic and rated current p. 31
- Installing auxiliary contacts, shunt trips and neutral switches p. 32
- Matching the trip characteristic to the application p. 36
- Interrupting capacity and back-up fuses p. 38
- Reading the tripping curves for the B, C, D and G characteristics p. 41
- Conductor sizes and stripping lengths for the terminals p. 37
- Internal resistance by rated current and characteristic p. 38
Good to know
- UL 508 manual motor controllers are control equipment without a short circuit protection function. p. 27
- 63 A ratings have no UL approval. p. 31
- The H...UM auxiliary contact can only be installed on the right of the switching device. p. 32
- Thermal trip values fall at higher ambient temperature, by about 5% per 10°C. p. 36
- Types B, C and D up to 25 A are also compliant with IEC 60898-1, DIN EN 60898-1 and VDE 0641-11. p. 7
Questions this manual answers
What are the ratings of the 3B16UM?
It is a 3-pole UM manual motor controller with characteristic B and a 16 A rated current, for 277 / 480 V AC. p. 31, 36
At what current does a characteristic B UM device trip magnetically?
It does not trip electromagnetically at 3 x In and trips at 5 x In within 0.1 s. p. 36
Does the 3B16UM give short circuit protection?
No. The catalog says UL 508 and CSA-22.2 manual motor controllers are control equipment without a short circuit protection function. p. 27
Which shunt trips fit ABL Sursum UM devices?
FA12UM (12 V UC), FA24UM (24 V UC), FA48UM (48 - 74 V UC) and FA110UM (110 - 240 V UC, 415 V AC). p. 33
What wire sizes do the UM terminals take?
Top terminals take 18-3AWG (1.0 - 25 mm2) and bottom terminals 18-2AWG (1.0 - 35 mm2). p. 7
The whole text · 8 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file