For the ABL Sursum 3B16UM
Page 21
SWITCHING DEVICES LISTED CIRCUIT BREAKERS AC according to UL 489 and CSA-22.2 No. 5-09 · Technical Data Product Range UL
Characteristic *
C
D
Application
Lighting Wiring protection Control circuits Business equipment appliances Motors with low inrush current
Transformers Power supplies Heaters Motors with high inrush current Reactive loads
Number of poles
1 - 3; 1 + N; 3 + N
Standards
UL 489 and CSA-22.2 Nr. 5-09
Interrupting capacity
10 kA
Back-up fuse ≤ 10 kA interrupting capacity none
Rated voltage AC 50/60 Hz 0.3 - 32 A
277 / 480 V
Rated voltage AC 50/60 Hz 40 - 63 A
240 V
Test currents
Rated current range
0.3 - 63 A
0.3 - 63 A
Thermal not tripping I1 (A) > 1 h
1.05 x In
1.05 x In
Thermal tripping I2 (A) < 1 h
1.35 x In
1.35 x In
Electromagnetic not tripping I4 (A) > 0.1 s
5 x In
10 x In
Electromagnetic tripping I5 (A) < 0.1 s
10 x In
16 x In
Reference calibration temperature of the thermal tripping threshold
40 °C Influence of the ambient temperature on the thermal release threshold: Decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5 % per 10 °C difference in temperature
Frequency range of the electromagnetic trip
16 2/3 to 60 Hz With higher frequencies, the electromagnetic tripping threshold increases by approximately a factor of 1.1 at 100 Hz; 1.2 at 200 Hz; 1.3 at 300 Hz; 1.4 at 400 Hz; 1.5 for DC
Ambient temperature
-25 °C to +55 °C
Storage temperature
-40 °C to +70 °C
Device depth according to DIN 43880
68 mm
Mechanical life
10,000 switching cycles (ON / OFF)
Protection cover
Finger safe and safe to back of hand according to DIN EN 50274, VDE 0660-514
Degree of protection acc. EN / IEC 60529
IP20
Installation position any
Mounting
DIN-rail according to DIN EN 60715 35 mm
Lockability
The handle can be secured against manual switching in the on and off position by a lead seal
Climatic resistance
Humid heat constant according to DIN EN 60068-2-78 Humid heat cycle according to DIN EN 60068-2-30
Vibration resistance
> 15 g according to DIN EN 60068-2-59 during a load with I1
Resistance to mechanical shocks
25 g 11 ms
* Other switching devices in B and Z characteristics available on request
Interrupting capacity acc. to IEC 60947-2, DIN EN 60947-2
CHARACTERISTIC
C, D
1pole
0,3 - 63 A
240 V
15 kA
2pole / 3pole
0,3 - 32 A
415 V
15 kA
2pole / 3pole
40 - 63 A
415 V
10 kA
FILE E 329510
21
Page 22
SWITCHING DEVICES LISTED CIRCUIT BREAKERS DC according to UL 489 and CSA-22.2 No. 5-09 · Technical Data Product Range DL
C
Application
Lighting Wiring protection Control circuits Business equipment appliances Motors with low inrush current
Number of poles
1 and 2
Standards
UL 489 and CSA-22.2 Nr. 5-09
Interrupting capacity
10 kA none
Rated voltage DC 1-pole
125 V
Test currents
Back-up fuse ≤ 10 kA interrupting capacity Rated voltage DC 2-pole
250 V
Rated current range
0.3 - 63 A
Thermal not tripping I1 (A) > 1 h
1.05 x In
Thermal tripping I2 (A) < 1 h
1.35 x In
Electromagnetic not tripping I4 (A) > 0.1 s
7 x In
Electromagnetic tripping I5 (A) < 0.1 s
14 x In
Reference calibration temperature of the thermal tripping threshold
40 °C Influence of the ambient temperature on the thermal release threshold: Decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5 % per 10 °C difference in temperature
Ambient temperature
-25 °C to +55 °C
Storage temperature
-40 °C to +70 °C
Device depth according to DIN 43880
68 mm
Mechanical life
10,000 switching cycles (ON / OFF)
Protection cover
Finger safe and safe to back of hand according to DIN EN 50274, VDE 0660-514
Degree of protection acc. EN / IEC 60529
IP20
FILE E 329510
22
Characteristic
Installation position any
Mounting
DIN-rail according to DIN EN 60715 35 mm
Lockability
The handle can be secured against manual switching in the on and off position by a lead seal
Climatic resistance
Humid heat constant according to DIN EN 60068-2-78 Humid heat cycle according to DIN EN 60068-2-30
Vibration resistance
> 15 g according to DIN EN 60068-2-59 during a load with I1
Resistance to mechanical shocks
25 g 11 ms
Page 23
SWITCHING DEVICES LISTED CIRCUIT BREAKERS according to UL 489 and CSA-22.2 No. 5-09 · Technical Data Product Ranges UL and DL
DIMENSION DRAWINGS PRODUCT RANGES UL AND DL
FILE E 329510
1-pole
2-pole
3-pole
TECHNICAL DATA Conductor cross sections Box terminal bottom Type of conductor *) Single wire max. 35 mm2 (AWG2)
Stranded wire
35 mm2 (AWG2) 25 mm2 (AWG3)
Stranded wire with ferrule
16 mm2 (AWG6)
Multiple wire
Box terminal top min. 1.0 mm2 (AWG18)
max. 25 mm2 (AWG3)
16 mm2 (AWG6)
25 mm2 (AWG3) 16 mm2 (AWG6)
1.0 mm2 (AWG18) 1.0 mm2 (AWG18)
min. 1.0 mm2 (AWG18) 16 mm2 (AWG6) 1.0 mm2 (AWG18)
16 mm2 (AWG6)
1.0 mm2 (AWG18)
Busbar cable lug up to 3 mm thickness up to 1.5 mm thickness
Combined, conductor and busbar or cable lug up to 35 mm2 and up to 2 mm thickness not possible
Torque max. 2.5 Nm (22.2 lb.in)
*) Stripped lengths: 12 - 14 mm at the bottom, 10 - 12 mm at the top ( ) values in brackets = measurement units for North America Copper conductor with sheath insulation for 60/75 °C Internal Resistance for Product Ranges UL and DL Rated current [A]
Trip characteristic C [Ohm]
D [Ohm]
0.3
16.8620
16.8620
0.5
6.8540
6.0009
1.0
1.7000
1.7560
1.6
0.5870
0.5870
2.0
0.4190
0.4190
3.0
0.2020
0.2020
4.0
0.1090
0.1090
5.0
0.0654
0.0654
6.0
0.0528
0.0491
8.0
0.0278
0.0240
10
0.0216
0.0187
12
0.0084
0.0085 0.0085
13
0.0084
15/16
0.0085
0.0076
20
0.0067
0.0064
25
0.0050
0.0041
30/32
0.0032
0.0027
40
0.0025
0.0022
50
0.0019
0.0018
60/63
0.0018
0.0017
23
Page 24
SWITCHING DEVICES LISTED CIRCUIT BREAKERS according to UL 489 and CSA-22.2 No. 5-09 · Characteristic Product Ranges UL and DL
FILE E 329510
Product Range UL
1,05-1,35xIN
60 40
10
10 4
1
1
10
10
4
4
1
1
0,4
0,4
C
D
C
10 -1
Seconds
4x10 -2 10 -2 4x10 -3 10 -3
10 -2 4x10 -3
1
2
3
4 5 6
8 10
16 20
C and D characteristic AC UL
40
10 -3
100
1
2
Tripping time t
Minutes
10
8 10
16 20
40
100
10
1
1
10
10
4
4
1
1
0,4
0,4
10 -1
10 -1
10 -2
Product Range DL
1,05-1,35xIN
4
4x10 -2 ln = 12 - 63 A
60 40
4
4x10 -2 10 -2 4x10 -3
4x10 -3
1
2
3
4 5 6 7 8 10 1 4
20
40
Multiple of rated current C characteristic DC UL
24
4 5 6
C and D characteristic AC UL
Seconds
Minutes Seconds ln = 0,3 - 10 A
Product Range DL
1,05-1,35xIN
3
Multiple of rated current
60 40
10 -3
D
4x10 -2
Multiple of rated current
Tripping time t
Product Range UL
1,05-1,35xIN
60 40
4
10 -1
Seconds
Tripping time t
Minutes
Minutes
Tripping time t ln = 0,3 - 10 A
100
10 -3
1
2
3
4 5 6 7 8 10 14
20
40
Multiple of rated current C characteristic DC UL ln = 12 - 63 A
100
Page 25
25
Page 26
Page 27
UL 508 UL 508 AND CSA-22.2 NO. 14 COMPLIANT SWITCHING DEVICES
UL 508 and CSA-22.2 compliant manual motor controllers are considered as control equipment without short circuit protection function. Our range of UL 508 motor controllers in the Miniature Circuit Breaker (MCB) design offers a convenient installation solution with both single and double pole versions available especially for single phase motors. They are "Suitable as Motor Disconnect" and can be used for "Motor Starting Across the Line". With its wide range of trip characteristics it also offers the best possible protection in some specific applications. The "Z" type offers the best protection for electronic devices, semiconductors and components with low surge current and resistance capabilities. Our range offers 1, 2 and 3 pole devices, available as UL types G and E, as well as IEC types B, C, D, and Z. In combination with the typical nominal ratings of both standards we can offer the best possible protection for each application. Our system offers the most convenient solutions for applications up to 25 A, for which our devices are both IEC and UL approved. In combination with our UL approved busbar technology, installation can be easily adapted for compliance with both standards. It offers OEMs the opportunity to broadly standardize their electrical installation independently of the location where the equipment will be used later. 27
Page 28
SWITCHING DEVICES MANUAL MOTOR CONTROLLER according to UL 508 and CSA-22.2 No.14
EUROPEAN-TYPE OF BUSBAR WIRING TESTED AND APPROVED FOR UL (AT LEAST ONE MOTOR CONTAINED IN THE CIRCUIT) FILE E137938
Power feed terminals 1.5 to 35 mm2
Busbars 18 and 25 mm2
Protection cover for busbars
UL-APPROVED ACCESSORIES File E137938
Activation lock
Switching devices 1-pole to 3-pole Neutral switch can be mounted Characteristic: B, C, D, E, G and Z Rated currents: 0.3 to 63 A (63 A without UL approval)
Auxiliary contact
Shunt trip
28
Page 29
SWITCHING DEVICES MANUAL MOTOR CONTROLLER according to UL 508 and CSA-22.2 No.14 UM Product Range, B, C, D,G, E and Z Characteristic B, C and D also acc. to IEC 60898-1, DIN EN 60898-1, VDE 0641-11 (B, C, D Characteristic 0.3 - 25 A)
RATED CURRENT IN A
CHARACTERISTIC B ITEM NO.
C ITEM NO.
D ITEM NO.
G ITEM NO.
E ITEM NO.
Z ITEM NO.
WEIGHT G / EACH
PACKING UNIT
1-pole 0.3
1C03UM
1D03UM
1G03UM
1E03UM
1Z03UM
150
12
0.5
1C05UM
1D05UM
1G05UM
1E05UM
1Z05UM
150
12
0.75
1C075UM
1D075UM
1E075UM
1Z075UM
150
12
0.8
FILE E137938
1G08UM
1
1B1UM
1C1UM
1D1UM
1G1UM
1E1UM
1Z1UM
150
12
1.6
1B1.6UM
1C1.6UM
1D1.6UM
1G1.6UM
1E1.6UM
1Z1.6UM
150
12
2
1B2UM
1C2UM
1D2UM
1G2UM
1E2UM
1Z2UM
150
12
2.5
1B2.5UM
1C2.5UM
1D2.5UM
1G2.5UM
1E2.5UM
1Z2.5UM
150
12
3
1B3UM
1C3UM
1D3UM
1G3UM
1E3UM
1Z3UM
150
12
3.5
1B3.5UM
1C3.5UM
1D3.5UM
1G3.5UM
1E3.5UM
1Z3.5UM
150
12
4
1B4UM
1C4UM
1D4UM
1G4UM
1E4UM
1Z4UM
150
12
5
1B5UM
1C5UM
1D5UM
1G5UM
1E5UM
1Z5UM
150
12
6
1B6UM
8 10
1B10UM
1C6UM
1D6UM
1G6UM
1E6UM
1Z6UM
150
12
1C8UM
1D8UM
1G8UM
1E8UM
1Z8UM
150
12
1C10UM
1D10UM
1G10UM
1E10UM
1Z10UM
150
12
150
12
12
1G12UM
1Z12UM
13
1B13UM
1C13UM
1D13UM
1G13UM
1E13UM
1Z13UM
15
1B15UM
1C15UM
1D15UM
1G15UM
1E15UM
1Z15UM
16
1B16UM
1C16UM
1D16UM
1G16UM
1E16UM
1Z16UM
150
12
20
1B20UM
1C20UM
1D20UM
1G20UM
1E20UM
1Z20UM
150
12
150
12
25
1B25UM
1C25UM
1D25UM
1G25UM
1E25UM
1Z25UM
30
1B30UM
1C30UM
1D30UM
1G30UM
1E30UM
1Z30UM
32
1B32UM
1C32UM
1D32UM
1G32UM
1E32UM
1Z32UM
150
12
40
1B40UM
1C40UM
1D40UM
1G40UM
1E40UM
1Z40UM
150
12
1Z50UM
50
1B50UM
1C50UM
1D50UM
1G50UM
1E50UM
150
12
60
1B60UM
1C60UM
1D60UM
1G60UM
1E60UM
150
12
63 *
1B63UM
1C63UM
1D63UM
1G63UM
1E63UM
150
12
* 63 A without UL approval
29
Page 30
SWITCHING DEVICES MANUAL MOTOR CONTROLLER according to UL 508 and CSA-22.2 No.14 UM Product Range, B, C, D,G, E and Z Characteristic B, C and D also acc. to IEC 60898-1, DIN EN 60898-1, VDE 0641-11 (B, C, D Characteristic 0.3 - 25 A)
RATED CURRENT IN A
CHARACTERISTIC B ITEM NO.
WEIGHT G / EACH
PACKING UNIT
2Z03UM
300
6
2Z05UM
300
6
2Z075UM
300
6
C ITEM NO.
D ITEM NO.
G ITEM NO.
E ITEM NO.
Z ITEM NO.
0.3
2C03UM
2D03UM
2G03UM
2E03UM
0.5
2C05UM
2D05UM
2G05UM
2E05UM
0.75
2C075UM
2D075UM
2E075UM
2-pole
0.8 1
2G08UM 2C1UM
2D1UM
2G1UM
2E1UM
2Z1UM
300
6
1.6
2C1.6UM
2D1.6UM
2G1.6UM
2E1.6UM
2Z1.6UM
300
6
2
2C2UM
2D2UM
2G2UM
2E2UM
2Z2UM
300
6
2.5
2C2.5UM
2D2.5UM
2G2.5UM
2E2.5UM
2Z2.5UM
300
6
2C3UM
2D3UM
2G3UM
2E3UM
2Z3UM
300
6
2C3.5UM
2D3.5UM
2G3.5UM
2E3.5UM
2Z3.5UM
300
6
3
2B1UM
2B3UM
3.5 FILE E137938
4
2B4UM
2C4UM
2D4UM
2G4UM
2E4UM
2Z4UM
300
6
5
2B5UM
2C5UM
2D5UM
2G5UM
2E5UM
2Z5UM
300
6
6
2B6UM
2C6UM
2D6UM
2G6UM
2E6UM
2Z6UM
300
6
2C8UM
2D8UM
2G8UM
2E8UM
2Z8UM
300
6
2C10UM
2D10UM
2G10UM
2E10UM
2Z10UM
300
6
300
6
8 10
2B10UM
12
2G12UM
13
2B13UM
2C13UM
2D13UM
2G13UM
2E13UM
2Z13UM
15
2B15UM
2C15UM
2D15UM
2G15UM
2E15UM
2Z15UM
16
2B16UM
2C16UM
2D16UM
2G16UM
2E16UM
2Z16UM
300
6
20
2B20UM
2C20UM
2D20UM
2G20UM
2E20UM
2Z20UM
300
6
25
2B25UM
2C25UM
2D25UM
2G25UM
2E25UM
2Z25UM
300
6
30
2B30UM
2C30UM
2D30UM
2G30UM
2E30UM
2Z30UM
32
2B32UM
2C32UM
2D32UM
2G32UM
2E32UM
2Z32UM
300
6
40
2B40UM
2C40UM
2D40UM
2G40UM
2E40UM
2Z40UM
300
6
50
2B50UM
2C50UM
2D50UM
2G50UM
2E50UM
2Z50UM
300
6
60
2B60UM
2C60UM
2D60UM
2G60UM
2E60UM
300
6
63 *
2B63UM
2C63UM
2D63UM
2G63UM
2E63UM
300
6
* 63 A without UL approval
30
2Z12UM