For the ABL Sursum 3B16UM
Page 31
SWITCHING DEVICES MANUAL MOTOR CONTROLLER according to UL 508 and CSA-22.2 No.14 UM Product Range, B, C, D,G, E and Z Characteristic B, C and D also acc. to IEC 60898-1, DIN EN 60898-1, VDE 0641-11 (B, C, D Characteristic 0.3 - 25 A)
RATED CURRENT IN A
CHARACTERISTIC B ITEM NO.
PACKING UNIT
3Z03UM
450
4
3Z05UM
450
4
3Z075UM
450
4
D ITEM NO.
G ITEM NO.
E ITEM NO.
Z ITEM NO.
3-pole 0.3
3C03UM
3D03UM
3G03UM
3E03UM
0.5
3C05UM
3D05UM
3G05UM
3E05UM
0.75
3C075UM
3D075UM
3E075UM
0.8
FILE E137938
WEIGHT G / EACH
C ITEM NO.
3G08UM
1
3B1UM
3C1UM
3D1UM
3G1UM
3E1UM
3Z1UM
450
4
1.6
3B1.6UM
3C1.6UM
3D1.6UM
3G1.6UM
3E1.6UM
3Z1.6UM
450
4
2
3B2UM
3C2UM
3D2UM
3G2UM
3E2UM
3Z2UM
450
4
2.5
3B2.5UM
3C2.5UM
3D2.5UM
3G2.5UM
3E2.5UM
3Z2.5UM
450
4
3
3B3UM
3C3UM
3D3UM
3G3UM
3E3UM
3Z3UM
450
4
3.5
3B3.5UM
3C3.5UM
3D3.5UM
3G3.5UM
3E3.5UM
3Z3.5UM
450
4
4
3B4UM
3C4UM
3D4UM
3G4UM
3E4UM
3Z4UM
450
4
5
3B5UM
3C5UM
3D5UM
3G5UM
3E5UM
3Z5UM
450
4
6
3B6UM
3C6UM
3D6UM
3G6UM
3E6UM
3Z6UM
450
4
3C8UM
3D8UM
3G8UM
3E8UM
3Z8UM
450
4
3C10UM
3D10UM
3G10UM
3E10UM
3Z10UM
450
4
450
4
8 10
3B10UM
12
3G12UM
3Z12UM
13
3B13UM
3C13UM
3D13UM
3G13UM
3E13UM
3Z13UM
15
3B15UM
3C15UM
3D15UM
3G15UM
3E15UM
3Z15UM
16
3B16UM
3C16UM
3D16UM
3G16UM
3E16UM
3Z16UM
450
4
20
3B20UM
3C20UM
3D20UM
3G20UM
3E20UM
3Z20UM
450
4
25
3B25UM
3C25UM
3D25UM
3G25UM
3E25UM
3Z25UM
450
4
30
3B30UM
3C30UM
3D30UM
3G30UM
3E30UM
3Z30UM
32
3B32UM
3C32UM
3D32UM
3G32UM
3E32UM
3Z32UM
450
4
40
3B40UM
3C40UM
3D40UM
3G40UM
3E40UM
3Z40UM
450
4
50
3B50UM
3C50UM
3D50UM
3G50UM
3E50UM
3Z50UM
450
4
60
3B60UM
3C60UM
3D60UM
3G60UM
3E60UM
450
4
63 *
3B63UM
3C63UM
3D63UM
3G63UM
3E63UM
450
4
ITEM NO.
WEIGHT G / EACH
PACKING UNIT
N63UM
150
5
* 63 A without UL approval
RATED CURRENT IN A
RATED VOLTAGE VOLT AC
TEST CURRENTS * ELECTROMAGNETIC NOT TRIPPING I4 A
TRIPPING I5 A
Neutral switch – for mounting instructions please consult page 39 0.3 - 63
277/480
400
700
* additional electromagnetic protection
FILE E137938
31
Page 32
ACCESSORIES FOR SWITCHING DEVICES
Manual Motor Controller and Supplementary Protectors according to UL 508 and CSA-22.2 No.14 for Product Ranges UM and UR
Accessory Installation Instructions Applies to N...UM and FA...UM: The accessory devices N...UM and FA...UM can be installed on the right or left. Installation: 1. Flick the blue switches of all devices to the “OFF” position 2. Remove the grey cover from switching device and attachment 3. Insert the drive plate between switching device and N...UM or FA...UM 4. Insert the connecting pin into the switch (insertion depth approx. 7mm) 5. Attach switching device to N...UM or FA...UM 6. Tighten the connecting srews (observe the the correct srew length)
5. 6. 7mm
1.
Mounting screw 34 mm (see accessories page 25)
4. 3.
6.
24 mm
2.
Neutral switch/ Shunt trip
Switching device
Neutral switch/ Shunt trip
Applies to H...UM: The auxiliary contact H...UM can only be installed on the right. Installation: 1. Flick the blue switches of both devices to the “OFF” position 2. Remove the grey cover from the switching device 3. Attach switching device to H...UM 4. Insert the connecting screws and fasten them by a 90° clockwise turn 5. After installation, close and open the switch to check correct operation Applies to all switching devices ...UM, N63UM and FA...UM: The load and mains can be connected into either the top or bottom terminals (line/load reversible). Design of the terminals · Optical detection of screw position · Increased breaking resistance if the screwdriver becomes jammed · Universal connecting terminals, suitable for connecting all known cable lugs, such as ring or forked cable lugs and pin terminals · Ring cable lugs can be connected by opening the flap and removing the connecting screw · Can also be used for applications that require ring cable lugs (e.g. nuclear power stations) · DIN EN 50274, VDE 0660-514 compliant protection against contact with live parts is fully guaranteed 32
Auxiliary contact
3. 4. 1.
2. Switching device
Auxiliary contact
Box terminal for · solid conductors · flexible conductors with or without cable lug
Screw terminal for forked cable lug
Screw terminal for ring cable lug (ring tongue)
90°
Page 33
ACCESSORIES FOR SWITCHING DEVICES
Manual Motor Controller and Supplementary Protectors according to UL 508 and CSA-22.2 No.14 for Product Ranges UM and UR
Auxiliary contact FILE E137938
CONTACTS
ITEM NO.
WEIGHT G / EACH
PACKING UNIT
1 auxiliary contact
1NO
H10UM
35
10
2 auxiliary contacts
1NO + 1NC
H11UM
40
10
3 auxiliary contacts
1NO + 2NC
H12UM
45
10
3 auxiliary contacts
2NO + 1NC
H21UM
45
10
MODULE
TYPE OF CONTACT
1/2 1/2 1/2 1/2
14
12
24
H10UM
H11UM
22 12
34
H12UM
11
12
24
H21UM
33
23
13
34
21
33 11
23
11
Standards
Acc. to IEC 60947-5-1, DIN EN 60947-5-1, VDE 0660-200, UL 508
Rated operating currents
10 A /240 V AC 3 A / 110 V DC 1 A / 220 V DC
Minimum contact load
1 mA at 24 V DC
Conductor cross sections Type of conductor *)
min.
max.
Single wire Stranded wire
1.0 mm2 (AWG18) 1.0 mm2 (AWG18)
2.5 mm2 (AWG14) 1.5 mm2 (AWG16)
Stranded wire with ferrule
1.0 mm2 (AWG18)
1.5 mm2 (AWG16)
Torque max. 0.8 Nm (7 lb.in)
*) Stripped length 8 - 9 mm
Shunt trip
MODULE
RATED OPERATING VOLTAGE
MAX. OPERATING CURRENT AT UN (T < 10 MS)
ITEM NO.
WEIGHT G / EACH
PACKING UNIT
5
FILE E137938
1
12 V UC
1.3 A
FA12UM
105
1
24 V UC
0.6 A
FA24UM
105
5
1
48 - 74 V UC
0.2 A
FA48UM
105
5
1
110 - 240 V UC, 415 V AC
0.25 A at 110 V
FA110UM
105
5
ITEM NO.
WEIGHT G / EACH
PACKING UNIT
EASS
2
10
0.5 A at 240 V 0.58 A at 277 V
Activation lock
DIMENSION DRAWING FA..UM, N63UM
33
Page 34
BUSBARS FOR SWITCHING DEVICES MANUAL MOTOR CONTROLLER according to UL 508 and CSA-22.2 No.14 for Product Ranges UM and MA...UM
CROSS SECTION (MM 2) FILE E205412
BUSBAR CURRENT START OF BUSBAR/ MIDDLE INFEED
MODULES/ PHRASES
WEIGHT G / EACH
PACKING UNIT
SB.U1
300
1
ITEM NO.
SUITABLE END CAP ITEM NO.
Busbars pin type acc. to UL and CSA 1-phase 18
80/130
57
1-phase 1-pole switching device + auxiliary contact 18
80/130
37/1
SB.U1H
280
1
80/130
19/3
SB.U3
800
1
SB.U8
SB.U3H
1020
1
SB.U8
AK.U1
35
1
SB.U9
0.6/3
1 strip = 5 pieces
3-phase 18
3-phase 3-pole switching device + auxiliary contact 25
100/180
16/3
Power feed terminals 6 - 35
115
Protection cover for UL and CSA busbars
34
Page 35
BUSBARS for Manual Motor Controllers, Product Ranges UM and MA...UM
CROSS SECTION (MM 2)
BUSBAR CURRENT START OF BUSBAR/ MIDDLE INFEED
MODULES/ PHRASES
WEIGHT G / EACH
PACKING UNIT
SB16010
250
50
ITEM NO.
SUITABLE END CAP ITEM NO.
Busbars fork type without UL and CSA approval 1-phase 12
65/110
56/1
1-phase 1-pole switching device + auxiliary contact 24
90/150
37/1
SDO.124
200
50
63/100
28/2
SB26010
390
20
SB.A5
22/2
SB26216
310
20
SB.A2
2-phase and 1-phase + N 10
2-phase 2-pole switching device + auxiliary contact 16
80/130
3-phase 10
63/100
4/3
SB31210
84
25
SB.A1
10
63/100
19/3
SB36010
420
20
SB.A1
16
80/130
19/3
SB36016
675
20
SB.A2
SB36316
630
20
SB.A2
36/1
SDO.316
500
20
SB.A2
14/4
SB46016
835
15
SB.A3
SB718U
500
20
SB.A2
3-phase 3-pole switching device + auxiliary contact 16
80/130
16/3
3-phase 1-pole switching device + auxiliary contact 16
80/130
4-phase and 3-phase + N 16
80/130
Busbars pin type without UL and CSA approval 3-phase 16
80/130
19/3
35
Page 36
SWITCHING DEVICES MANUAL MOTOR CONTROLLER according to UL 508 and CSA-22.2 No.14 · Technical Data Product Range UM
Characteristic
B
C
D
E
G
Z
Application
Lighting Circuits control Wiring protection Business equipment Appliances
Lighting Circuits control Wiring protection Business equipment
Transformers Power supplies Reactive load Motors (high inrush current)
Transformers Power supplies Motors (high efficiency)
Lighting Circuits control Wiring protection Transformers Solenoid Motors (general)
Wiring protection Semiconductor protection General electronics
Number of poles
1 - 3; 1 + N; 3 + N
Standards
IEC 60898-1, DIN EN 60898-1, VDE 0641-11, UL 508, CSA-22.2 No.14
Interrupting capacity Current limiting class see data sheet for use in the USA, Canada and Europe (page 38) 3
3
Max. back-up fuse see data sheet for use in the USA, Canada and Europe (page 38)
Rated voltage AC
277 / 480 V 1-pole 42 V and 2-poles 80 V in serial connection of both poles (up to 25 A rated current)
Rated voltage DC L/R = 4 ms Rated current range
Test currents
Appliances Motors (low inrush current)
1-pole 24 V and 2-poles 60 V in serial connection of both poles (30 A - 60 A rated current) 1 - 63* A
0.3 - 63* A
0.3 - 63* A
0.3 - 63* A
0.3 - 63* A
0.3 - 50 A
Thermal not tripping I1 (A) > 1 h
1.13 x In
1.13 x In
1.13 x In
1.05 x In
1.05 x In
1.05 x In
Thermal tripping I2 (A) < 1 h
1.45 x In
1.45 x In
1.45 x In
1.35 x In
1.35 x In
1.35 x In
Electromagnetic not tripping I4 (A) > 0,1 s
3 x In
5 x In
10 x In
14 x In
8 x In
2 x In
Electromagnetic tripping I5 (A) < 0,1 s
5 x In
10 x In
16 x In
18 x In
10 x In
3 x In
Reference calibration temperature of the thermal tripping threshold
30° C + 5° C
20° C + 5° C
Influence of the ambient temperature on the thermal release threshold: Decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5% per 10°C difference in temperature
Frequency range of the electromagnetic trip
16 2/3 to 60 Hz With higher frequencies, the electromagnetic tripping values threshold increases by approximately a factor of 1.1 at 100 Hz; 1.2 at 200 Hz; 1.3 at 300 Hz; 1.4 at 400 Hz; 1.5 for DC
Ambient temperature
-25 °C to +55 °C
Storage temperature
-40 °C to +70 °C
Device depth according to DIN 43880
68 mm
Mechanical life
10,000 switching cycles (ON / OFF)
Protection cover
Finger safe and safe to back of hand according to DIN EN 50274/ VDE0660-514, BGV A3
Insulation group acc. to DIN/VDE 0110
C at 250 V AC B at 400 V AC
Degree of protection acc. to EN/IEC 60529
IP20
Installation position any
Mounting
DIN-rail according to DIN EN 60715 35 mm
Lockability
The handle can be secured against manual switching in the on and off position by a lead seal
Climatic resistance
Humid heat constant according to DIN EN 60068-2-78 Humid heat cycle according to DIN EN 60068-2-30
Vibration resistance
> 15 g according to DIN EN 60068-2-59 during a load with I1
Resistance to mechanical shocks
25g 11ms
* 63 A without UL approval
FILE E137938
36
Page 37
SWITCHING DEVICES MANUAL MOTOR CONTROLLER according to UL 508 and CSA-22.2 No.14 · Technical Data Product Range UM
Conductor cross sections Box terminal bottom Type of conductor *) Single wire max. 35 mm2 (AWG2)
Stranded wire
35 mm2 (AWG2) 25 mm2 (AWG3)
Stranded wire with ferrule
16 mm2 (AWG6)
Multiple wire
Box terminal top min. 1.0 mm2 (AWG18)
max. 25 mm2 (AWG3)
16 mm2 (AWG6)
25 mm2 (AWG3) 16 mm2 (AWG6)
1.0 mm2 (AWG18) 1.0 mm2 (AWG18)
min. 1.0 mm2 (AWG18) 16 mm2 (AWG6) 1.0 mm2 (AWG18) 1.0 mm2 (AWG18)
16 mm2 (AWG6)
Busbar cable lug up to 3 mm thickness up to 1.5 mm thickness
Combined, conductor and busbar or cable lug up to 35 mm2 and up to 2 mm thickness not possible
Torque max. 2.3 Nm (20 lb.in)
*) Stripped length: bottom 12 - 14 mm, top 10 - 12 mm
FILE E137938
1-pole
2-pole
3-pole
37
Page 38
SWITCHING DEVICES MANUAL MOTOR CONTROLLER according to UL 508 and CSA-22.2 No.14 · Technical Data Product Range UM
Interrupting capacity and maximum back-up fuse according to UL 508 and CSA-22.2 No.14 Characteristic
B; C; D; E; G and Z
Standards
UL 508 and CSA-22.2 No.14 Maximum rated voltage V
Rated current
Interrupting capacity
Number of poles
A kA
1/1+N
277
0.3 - 10
10
70 A
1/1+N
277
12 - 60
10
4 x In
Interrupting capacity at rated voltage Ambient temperature 40 °C
Back-up fuse for group installations
Maximum back-up fuse A
2/3/3+N
480
0.3 - 10
10
70 A
2/3/3+N
480
12 - 60
10
4 x In
1/1+N
277
0.3 - 10
10
800 A
1/1+N
277
12 - 60
5
800 A
2/3/3+N
480
0.3 - 10
10
800 A
2/3/3+N
480
12 - 60
5
800 A
Interrupting capacity and maximum back-up fuse according to EN and IEC Characteristic
B; C; D; E; G and Z
Standards
IEC 60947-2, DIN EN 60947-2, VDE 0660-101 B, C and D characteristic acc. to IEC 60898-1, DIN EN 60898-1, VDE 0641-11 Maximum rated voltage V
Rated current
Interrupting capacity
Number of poles
A kA
Maximum back-up fuse A
1 /1+N
277
0.3 - 60
10
160
2/3/3+N
480
0.3 - 60
10
160
Interrupting capacity at rated voltage
Internal Resistance for Product Ranges UM and UR Rated current [A]
Trip characteristic] B [Ohm]
C [Ohm]
D [Ohm]
G [Ohm]
E [Ohm]
0.3
16.8620
16.8620
16.862
14.52000
31.5060
0.5
6.8540
6.0009
6.854
5.92000
10.2460 5.3920
3.0540
3.0540
3.054
2.70000
1.0
1.7000
1.7000
1.7560
1.756
1.48000
2.6910
1.6
0.5870
0.5870
0.5870
0.587
0.57400
0.9440
0.75/0.8
2.0
0.4190
0.4190
0.4190
0.419
0.40500
0.8900
2.5
0.2950
0.2950
0.2950
0.295
0.26900
0.4290
3.0
0.2020
0.2020
0.2020
0.202
0.18600
0.3460
3.5
0.1390
0.1390
0.1390
0.139
0.13900
0.1790
4.0
0.1090
0.1090
0.1090
0.109
0.10600
0.1620
5.0
0.0654
0.0654
0.0654
0.0654
0.05900
0.1050
6.0
0.0528
0.0528
0.0491
0.0491
0.04600
0.0823
0.0278
0.0240
0.0333
0.03040
0.0371
0.0216
0.0187
0.0211
0.02020
0.0278
0.0084
0.00724
0.0151 0.0151
8.0 10
0.0216
12 13
0.0113
0.0084
0.0085
0.0084
0.00724
15/16
0.0085
0.0085
0.0076
0.0076
0.00731
0.0114
20
0.0067
0.0067
0.0064
0.0064
0.00582
0.0075
25
0.0050
0.0050
0.0041
0.0046
0.00411
0.0050
30/32
0.0032
0.0032
0.0027
0.003
0.00272
0.0032
40
0.0025
0.0025
0.0022
0.0022
0.00212
0.0022
50
0.0019
0.0019
0.0018
0.0019
0.00184
0.0020
60/63 *
0.0018
0.0018
0.0017
0.00179
0.00172, * 63 A without UL approval
FILE E137938
38
Z [Ohm]
Page 39
SWITCHING DEVICES MANUAL MOTOR CONTROLLER according to UL 508 and CSA-22.2 No.14 · Technical Data Product Range UM
Ampere rating and horsepower rating 1 phase FLA and LRC horsepower conversion table; use FLA and LRC ratings where no hp rating ist given Rated current [A] (see Note 1)
Motor nameplate FLA rating [A]
Motor nameplate Starting/ LCR rating [A]
0.30 0.50 0.75
0.30 0.50 0.75
1.80 3.00 4.35
0.80 1.0 1.6
0.80 1.0 1.6
4.8 6.0 9.6
2.0 2.5 3.0
2.0 2.5 3.0
3.5 4.0
Nominal circuit voltage 110 – 120 VAC [hp]
200 VAC [hp]
208 VAC [hp]
220 – 240 VAC [hp]
265 VAC [hp]
277 VAC [hp]
12.0 15.0 18.0
1/6 1/6
1/6 1/6
1/6 1/6 1/4
1/6 1/6 1/4
1/6 1/4 1/3
3.5 4.0
21.0 24.0
1/4 1/4
1/4 1/3
1/4 1/3
1/3 1/3
1/3 1/3
5.0 6.0 8.0
5.0 6.0 8.0
30.0 36.0 48.0
1/6 1/4 1/3
1/3 1/2 3/4
1/2 1/2 3/4
1/2 1/2 1
1/2 3/4 1
1/2 3/4 1
10.0
10
60.0
2
72.0 75.0
1 1 1/2 1 1/2
1 1/2
12.0 12.5
1 1 1/2 1 1/2
1 1/2
12.0 12.5
1/2 1/2 1/2
2 2
2 2
2 2
13.0 15.0 16.0
13.0 15.0 16.0
78.0 90.0 96.0
1/2 3/4 1
1 1/2 2 2
1 1/2 2 2
2 2 2
2 3 3
2 3 3
20.0 25.0
20.0 25.0
120.0 150.0
1 1/2 2
3 3
3 3
3 3
3 5
3 5
30.0
30.0
180.0
2
3
3
5
5
5
32.0
32.0
192.0
2
3
40.0
40.0
240.0
3
5 7 1/2
5 7 1/2
7 1/2
50.0 60.0
50.0 60.0
300.0 360.0
3 5
5 7 1/2
5 7 1/2 10 10
10 10
10 10
10 15
10
5
Note 1 For AC motor circuit nameplate full load current, AC general-use loads, AC resistance loads, AC incandescent lamp (tungsten) loads, AC electric discharge lamp (ballast) loads Note 2 Conversions per UL 508 Table 45.2 and NFPA-70: National Electrical Code® 2008 Tables 430-248 and 430-251(A)
FILE E137938
39
Page 40
SWITCHING DEVICES MANUAL MOTOR CONTROLLER according to UL 508 and CSA-22.2 No.14 · Technical Data Product Range UM
Ampere rating and horsepower rating 3 phase and 2 phase – 4 wire FLA and LRC horsepower conversion table; use FLA and LRC ratings where no hp rating ist given Nominal circuit voltage Rated current [A] (see Note 1)
Motor nameplate FLA rating [A]
Motor nameplate Starting/ LCR rating [A]
110 – 120 VAC
200 VAC
208 VAC
220 – 240 VAC
440 – 480 VAC
Motordesign
Motordesign
Motordesign
Motordesign
Motordesign
B, C, D [hp]
E [hp]
E [hp]
B, C, D [hp]
E [hp]
B, C, D [hp]
E [hp]
B, C, D [hp]
E [hp]
1/2
1/2
0.30 0.50 0.75
0.30 0.50 0.75
3.0 5.0 7.5
0.80 1.0 1.6
0.80 1.0 1.6
8.0 10.0 16.0
2.0 2.5 3.0
2.0 2.5 3.0
20.0 25.0 30.0
1/2 1/2
1/2 1/2
1/2 1/2
1/2 1/2
1/2 1/2 1/2
1/2 1/2 1/2
3/4 1 1 1/2
3/4 1 1 1/2
3.5 4.0
3.5 4.0
35.0 40.0
1/2 3/4
1/2 3/4
3/4 3/4
3/4 3/4
3/4 3/4
3/4 3/4
2 2
2 2
5.0 6.0 8.0
5.0 6.0 8.0
42.0 50.4 67.2
1/2 1/2 3/4
1/2 1/2 3/4
1 1 2
1 1 2
1 1 2
1 1 2
1 1 1/2 2
1 1 1/2 2
3 3 5
3 3 5
10.0 12.0 12.5
10.0 12.0 12.5
84.0 100.8 105.0
1 1 1/2 1 1/2
1 1 1/2 1 1/2
2 3 3
2 3 3
2 3 3
2 3 3
3 3 3
3 3 3
5 7 1/2 7 1/2
5 7 1/2 7 1/2
13.0 15.0 16.0
13.0 15.0 16.0
109.2 126.0 134.4
1 1/2 2 2
1 1/2 2 2
3 3 3
3 3 3
3 3 3
3 3 3
3 3 5
3 3 5
7 1/2 10 10
7 1/2 10 10
20.0 25.0
20.0 25.0
168.0 210.0
3 3
3 3
5 5
5 5
5 71/2 7 1/2
5 71/2 7 1/2
5 71/2
5 71/2
10 15
10 15
10
10
20
20
10
10
20
20
10
10
30
20
15 20
10 15
30 40
25 30
30.0
30.0
252.0
5
5
5
5
32.0
32.0
268.8
5
5
5
10
40.0
40.0
226.0
10
10
50.0 60.0
282.5 339.0
5 7 1/2
10 7 1/2
50.0 60.0
5 7 1/2
5 7 1/2
10
10
15 15
10 10
15 20
10 10
Note 1: For AC motor circuit nameplate full load current, AC general-use loads, AC resistance loads, AC incandescent lamp (tungsten) loads, AC electric discharge lamp (ballast)loads Note 2: Conversions per UL 508 proposed Tables 45.2 and 45.4 and NFPA-70: National Electrical Code® 2008 Tables 430-249, 430-250 and 430-251B)
FILE E137938
40
B, C, D [hp]