The text of a manual · part 1 of 8
ABL Switching Devices in compliance with UL 489, UL 508 and UL 1077, pages 1 to 10
Pages 1 to 10 of 78
The original document is the PDF (6.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the ABL Sursum 3B16UM
Page 1
ABL
SWITCHING DEVICES
IN COMPLIANCE WITH UL 489, UL 508 AND UL 1077 - MAY 2017
Page 2
THE ORIGINAL. SINCE 1933.
Page 3
SWITCHING DEVICES UL 489, UL 508 AND UL 1077
ABL SWITCHING DEVICES WORLDWIDE
4
THE WINNING FEATURES OF ABL SWITCHING DEVICES
6
UL 489, UL 508 AND UL 1077 OVERVIEW
8
WIRING DIAGRAM European and american standard
10
SWITCHING DEVICES ACC. TO UL 489 AND CSA-22.2 NO. 5-09
12
Circuit Breaker UL, Product Range AC Produktreihe DL, Product Range DC Accessories Busbars Technical data
14 16 17 19 21
SWITCHING DEVICES ACC. TO UL 508 AND CSA-22.2 NO. 14
26
Manual Motor Controller UM Product Range UM Accessories Busbars Technical Data
28 32 34 36
Manual Motor Controller MA Product Range MA..UM Accessories Technical Data
44 48 50
Manual Motor Controller MS Product Range MS Accessories Busbars Technical Data
54 56 59 60
SWITCHING DEVICES ACC. TO UL 1077 AND CSA-22.2 NO. 235
64
Supplementary Protector UR Accessories Technical data
66 68 70
ITEM NUMBER DIRECTORY
73
Page 4
SWITCHING DEVICES FOR THE WORLD
®
Since 1933, we develop and produce switching devices for the North American market. The approvals in accordance with UL and IEC standards offer you the opportunity to standardize your machinery and make you independent of the location where the equipment will later be used.
Page 5
Page 6
THE WINNING FEATURES OF ABL SURSUM SWITCHING DEVICES
1 FUNCTIONAL FORM · Contemporary design · User-friendly ergonomics · Intuitive product coding · Clearly marked ON/OFF positions
Rated current Characteristic
Circuit diagram
Rated voltage
Approval
No. of Poles
Rated breaking capacity
Approval for heating devices, refrigerating systems, air-conditioning systems
Product range
DESIGN OFFERING 2 COMPACT MAXIMUM WIRING SPACE · At 105 mm installation height one of the smallest UL 489 compliant circuit breakers available · At 89.3 mm the smallest UL 508 manual motor controller available · An equally space-saving 89.3 mm for the UL 1077 supplementary protector
3 UL SWITCHING DEVICES in a consistent and contemporary design
6
UL 489 Height only 105 mm
UL 508 UL 1077 Height only 89,3 mm
Page 7
APPLICATION 4 EXTENSIVE POSSIBILITIES · Three separate product ranges for circuit protection, manual motor control and supplementary protection applications · AC and DC versions available · European and North American standard tripping characteristics featuring the widest possible range of nominal ratings
· UL 508 0.3 - 63 A, 1-pole/2-pole/3-pole compliant with UL 508 and CSA-22.2 No.14 UM product range, B, C, D, G, E and Z types B , C and D up to 25 A also compliant with IEC 60898-1, DIN EN 60898-1, VDE 0641-11
· UL 489 AC, 0.3 - 63 A, 1-pole/2-pole/3-pole compliant with UL 489 and CSA-22.2 No. 5-09 UL product range tripping types AC: B, C, D, Z DC, 0.3 - 63 A, 1-pole/2-pole DL product range type C
· UL 1077 0.5 - 63 A, 1-pole/2-pole/3-pole compliant with the UL 1077 and CSA-22.2 No.235 UR product range types B, C, and D
PRODUCT 5 COMPLETE SYSTEM · Full range of accessories for UL 489 Circuit Breakers · Common line of accessories for the UL 508 and UL 1077 Product lines · Full range of auxiliary switches · Shunt trip and neutral pole can be added left or right
FILE E 335632
Auxiliary contact
Shunt trip
Neutral switch
Activation lock
Touch protection caps
6 PROFESSIONAL LABELING SYSTEM · with marking window · Blank perforated labels available for one pole, two pole and three pole windows for convenient circuit indication
DUAL 7 STANDARD CONNECTION METHOD for all three product ranges
· Box clamp terminal (line load reversible) · for solid and flexible conductors Top: 18-3AWG (1.0 mm2 - 25 mm2) Bottom: 18-2AWG (1.0 mm2 - 35 mm2) · for busbars Unique connecting system for the convenient connection of all known cable lugs such as ring or forked cable lugs and pin terminals. 7
Page 8
OVERVIEW · Extensive range of possible applications · Three product ranges for circuit protection, manual motor control and supplementary protection applications · AC and DC versions available · European and North American standard tripping characteristics with the widest possible range of nominal ratings
BUSBARS AVAILABLE FOR UL 489 DEVICE
Product Range
BUSBARS AVAILABLE FOR UL 508 AND UL 1077 DEVICE
UL
DL UL 489
Standards
E 329510
UL File
UM **
UR **
UL 508
UL 1077
E 137938
E 137915
Rated voltage
240 V AC
277 V AC
480 V AC
125 V DC
250 V DC
277 V AC
480 V AC
42 V DC
80 V DC
24 V DC
60 V DC
277 V AC
480 V AC
Number of poles
1/ 1+N* / 2/3/ 3+N*
1 / 1+N*
2/3/ 3+N*
1
2
1 / 1+N*
2/3/ 3+N*
1
2
1
2
1 / 1+N*
2/3/ 3+N*
1-63 A
1-63 A
1-25 A
1-25 A
30-63 A
30-63 A
1-63 A
1-63 A
C - Characteristic
40-63 A
0.3-32 A
0.3-32 A
0.3-63 A
0.3-63 A
0.3-63 A
0.3-63 A
0.3-25 A
0.3-25 A
30-63 A
30-63 A
0.3-63 A
0.3-63 A
D - Characteristic
40-63 A
0.3-32 A
0.3-32 A
0.3-63 A
0.3-63 A
B - Characteristic
E - Characteristic
0.3-63 A
0.3-63 A
0.3-25 A
0.3-25 A
30-63 A
30-63 A
0.3-63 A
0.3-63 A
0.3-25 A
0.3-25 A
30-63 A
30-63 A
G - Characteristic
0.3-63 A
0.3-63 A
0.3-25 A
0.3-25 A
30-63 A
30-63 A
Z - Characteristic
0.3-50 A
0.3-50 A
0.3-25 A
0.3-25 A
30-50 A
30-50 A
* N pole to be mounted separately ** UL approval up to 60 A
8
Page 9
FULL RANGE OF ACCESSORIES FOR UL 489, UL 508 AND UL 1077 · Auxiliary switches · Shunt trip and Neutral pole can be added on the left or right
Activation lock
Neutral switch UL 489
Shunt trip UL 489
Auxiliary contact UL 489
Neutral switch UL 508 UL 1077
UL 489 LISTED CIRCUIT BREAKERS AC DISTRIBUTION EQUIPMENT
UL 508 LISTED MANUAL MOTOR CONTROLLER INDUSTRIAL CONTROL EQUIPMENT
•
•
Shunt trip UL 508 UL 1077
Auxiliary contact UL 508 UL 1077
UL 1077 SUPPLEMENTARY PROTECTOR
Main Characteristics Listed component Recognized components for supplementary protection only
•
Field wiring
•
•
Factory wiring
•
•
•
Feeder circuit protection
•
Branch circuit protection
•
Control Circuits
•
•
•
Functions Short circuit protection
•
Switching function
•
•
Disconnect function
•
•
Overload protection
•
•
•
Applications Heaters, coolers, -air conditioning (HACR approval)
•
Protection of outlets
•
Transformers
•
Motor protection
•
•
Control transformers
•
•
•
Inductive loads
•
•
•
Appliances, Business Equipment
•
•
•
General lamps
•
•
•
Fuorescent lamps
•
•
•
9
Page 10
WIRING DIAGRAM WITH SWITCHING DEVICES ACC. TO UL 489, UL 508 AND UL 1077 European standard
Power Circuit
UL 489
Power Circuit
Power Circuit
UL 489
Power Circuit
Power Transformer UL 489
Control Circuit
UL 489
Control Transformer
UL 508 or UL 1077
UL 508
UL 508 or UL 1077
Power Transformer
UL 489
Pushbutton OFF
Pushbutton OFF
Pushbutton ON
Pushbutton ON
UL 489
UL 508
UL 489
UL 508
General Loads
M
M
Rating of main branch circuit protector according to table 430.52 in NEC ® · Dual Element (Time Delay) Fuse Maximum fuse = largest motor FLA x 175 %
+ FLA of all other motors and general loads in group · Inverse Time Breaker Maximum circuit breaker = largest motor FLA x 250 %
+ FLA of all other motors and general loads in group
(for other fuse/breaker types see table 430.52) 10
Heaters
Lamps
Coolers
Fluorescent Lamps
Air Conditioner
Resistive load
Blowers
Motors
Socket Outlets