The text of a manual · part 6 of 8

ABL Switching Devices in compliance with UL 489, UL 508 and UL 1077, pages 51 to 60

Pages 51 to 60 of 78

The original document is the PDF (6.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the ABL Sursum 3B16UM

Page 51

SWITCHING DEVICES MANUAL MOTOR CONTROLLER MA according to UL 508 and CSA-22.2 No.14 · Technical Data Product Range MA...UM

Conductor cross sections Box terminal bottom Type of conductor *)

max. 25 mm2 (AWG3)

Single wire Stranded wire

25 mm2 (AWG3) 16 mm2 (AWG6)

Stranded wire with ferrule

16 mm2 (AWG6)

Multiple wire

Busbar Cable lug Combined, conductor and busbar or cable lug

Box terminal top min. 1.0 mm2 (AWG18)

max. 25 mm2 (AWG3)

min.

16 mm2 (AWG6)

25 mm2 (AWG3)

1.0 mm2 (AWG18) 16 mm2 (AWG6)

1.0 mm2 (AWG18) 1.0 mm2 (AWG18)

25 mm2 (AWG3) 16 mm2 (AWG6)

1.0 mm2 (AWG18)

1.0 mm2 (AWG18)

up to 3 mm thickness up to 1.5 mm thickness up to 25 mm2 and up to 2 mm thickness not possible

Torque max. 2.3 Nm (20 lb.in)

*) Stripped length: bottom 12 - 14 mm, top 10 - 12 mm

FILE E137938

1.15 x In

1.15 x In

60 40

Minutes

Minutes

60 40

10 4

10 4

1

1

20 10

10

4

4

1

1 0.4 upper setting short circuit tripping at lower setting

10-1

10-1

4x10-2

4x10-2

Seconds

Seconds

0.4

10-2 4x10-3 upper setting short circuit tripping at lower setting

10-2 4x10-3

10-3

10-3 1

2

3

4

5 6

16

8 10 12

20 19 x Rated current

Characteristic for MA016UM – MA16UM

40

100

1

2

3

4

5 6

8 10 x Rated current

12

15

20

40

100

12.5

Characteristic for MA20UM – MA40UM

51

Page 52

SWITCHING DEVICES MANUAL MOTOR CONTROLLER MA according to UL 508 and CSA-22.2 No.14 · Technical Data Product Range MA...UM

Internal resistance per pole in mΩ and power loss in Watt of the complete device

LOWER SETTING A

TYPE

UPPER SETTING A

LOWER SETTING WATT

UPPER SETTING WATT

MA016UM

0.10

0.16

85500

2.6

6.6

MA025UM

0.16

0.25

35000

2.7

6.6

MA040UM

0.25

0.40

15000

2.8

7.2

MA063UM

0.40

0.63

5200

2.5

6.2

MA1.0UM

0.63

1.0

2300

2.7

6.9

MA1.6UM

1.0

1.6

950

2.9

7.3

MA2.5UM

1.6

2.5

355

2.7

6.7

MA4.0UM

2.5

4.0

142

2.7

6.8

MA6.3UM

4.0

6.3

54

2.6

6.4

MA.10UM

6.3

10

28

3.3

8.4

MA.16UM

10

16

13.9

4.2

10.7

MA.20UM

16

20

9.9

5.2

8.2

MA.25UM

20

25

6.3

8

12.3

MA.32UM

25

32

3.85

6.4

10.5

MA.40UM

32

40

3.1

8.6

13.4

TYPE

RATED CURRENT [A]

FLA DIAL ADJUSTMENT MARKINGS

MA016UM

0.16

0.1/ 0.12/0.14/0.16

MA025UM

0.25

0.16/0.19/0.22/0.25

MA040UM

0.40

0.25/0.30/0.35/0.40

MA063UM

0.63

0.40/0.48/0.56/0.63

MA1.0UM

1.00

0.63/0.75/0.87/1.0

MA1.6UM

1.60

1.0/1.2/1.4/1.6

MA2.5UM

2.50

1.6/1.9/2.2/2.5

MA4.0UM

4.00

2.5/3.0/3.5/4.0

MA6.3UM

6.30

4.0/4.8/5.6/6.3

MA10UM

10

6.3/7.5/8.7/10

MA16UM

16

10/12/14/16

MA20UM

20

16/17/18.5/20

MA25UM

25

20/21.5/23/25

MA32UM

32

25/27/30/32

MA40UM

40

32/34/37/40

GROUP SHORT CIRCUIT RATING AT 480 VAC A) (AND BCP SIZE)

FILE E137938

3 Ø HORSEPOWER RATINGS AT NOMINAL LINE VOLTAGE (SEE NOTE FOR HEA DEFINITION) 110 – 120 V HP (HEA)

14 kARMS symmetrical (max. 350 A MCCB or RK5) 10 kARMS symmetrical (max. 350 A MCCB or RK5)

200 V HP (HEA)

208 V HP (HEA)

220 – 240 V HP (HEA)

460 – 480 V HP (HEA)

Through MA2.5UM, ampere rated for motor circuits having a fullload-amperage (FLA) not exceeding the MA´s general purpose rated current and a lockedrotor current not exceeding 6 times the MA´s rated current. Rated current equals maximum dial setting.

42 kARMS symmetrical (max. 1200 A MCCB or RK5)

Note: HEA - Horsepower Equivalent Amperes, the nominal amperage assigned to standard motor horsepower ratings in design guide tables such as NFPA-70 Tables 430-248, 430-249, 430-250; UL 1077 Table 16.2; CSA - C22.2 No. 235-M89 Tables 44 and 45; CSA-C22.2 No. 14-M91 Table 19, etc. Multiply HEA values (in parenthesis) by 1.1 if power factor is 90%, and by 1.2 if power factor is 80%

52

POWER LOSS FOR THE COMPLETE DEVICE FOR

INTERNAL RESISTANCE PER POLE MΩ

½ (4.0)

¾ (3.2)

¾ (3.1)

1 (3.6)

2 (3.42)

¾ (5.6)

1½ (6.0)

1½ (5.7)

1½ (5.2)

3 (4.8)

1 (7.2)

2 (7.8)

2 (7.5)

3 (9.6)

5 (7.6)

2 (13.6)

3 (11.0)

3 (10.6)

5 (15.2)

10 (14.0)

3 (19.2)

5 (17.5)

5 (16.7)

5 (15.2)

10 (14.0)

3 (19.2)

5 (17.5)

7½ (24.2)

7½ (22.0)

15 (21.0)

5 (30.4)

7½ (25.0)

7½ (24.2)

10 (28.0)

20 (27.0)

5 (30.4)

10 (32.0)

10 (31.0)

10 (28.0)

25 (34.0)

a) The standard-circuit short-circuit rating is 14 kA for all types. Group ratings can be used in a standard circuit (e.g., MA1.0UM at 42 kA), but a higher standard rating cannot be used in a group circuit (e.g., MA40UM at 14 kA only in standard circuit.)

Page 53

SWITCHING DEVICES MANUAL MOTOR CONTROLLER MA according to UL 508 and CSA-22.2 No.14 · Dimension Drawing

FILE E137938

53

Page 54

SWITCHING DEVICES MANUAL MOTOR CONTROLLER MS Overview

Trip-indicating auxiliary contact or shunt trip or undervoltage trip

Auxiliary contact right and/or left hand mounted

Auxiliary contact right and/ or left mounted

Emergencystop button

Indicator light

Activation lock

54

Insulated enclosure IP41 or IP55

Insulated flush mounting enclosure IP41 or IP55

Page 55

SWITCHING DEVICES MANUAL MOTOR CONTROLLER MS

HORSEPOWER RATINGS AT NOMINAL LINE VOLTAGE RATED CURRENT [A]

0.1 - 0.16 0.16 - 0.25 0.25 - 0.40 0.40 - 0.63

115V HP (KW)

200V HP (KW)

230V HP (KW)

480V HP (KW)

600 HP (KW)

Ampere rated for motor circuits having a full-loadamperage (FLA) not exceeding the MS’s general purpose rated current and a locked rotor current not exceeding 6 times the MS’s rated current.

OPERATING CURRENT SHORT CIRCUIT TRIP [A]

ITEM NO.

WEIGHT G / EACH

PACKING UNIT

1.92

MS016

250

1

3.00

MS025

250

1

4.80

MS040

250

1

7.60

MS063

250

1

0.63 - 1.0

1/2 (0.37)

1/2 (0.37)

12.00

MS1

250

1

1.0 - 1.6

3/4 (0.56)

1 (0.75)

19.20

MS1.6

250

1 1

1.6 - 2.5

1/2 (0.37)

1/2 (0.37)

1 (0.75)

11/2 (1.2)

30.00

MS2.5

250

2.5 - 4.0

1/2 (0.37)

3/4 (0.56)

1 (0.75)

2 (1.5)

3 (2.24)

48.00

MS4

250

1

4.0 - 6.3

3/4 (0.56)

11/2 (1.2)

1 (0.75)

3 (2.24)

5 (3.73)

75.60

MS6.3

250

1

6.3 - 10

1 (0.75)

2 (1.5)

3 (2.24)

5 (3.73)

71/2 (5.6)

120.00

MS10

250

1

10 - 16

2 (1.5)

3 (2.24)

5 (3.73)

10 (7.46)

10 (7.46)

192.00

MS16

250

1

16 - 20

3 (2.24)

5 (3.73)

5 (3.73)

10 (7.46)

_

240.00

MS20

250

1

20 - 25

3 (2.24)

5 (3.73)

71/2 (5.6)

15 (11.19

_

300.00

MS25

250

1

FILE E137938

55

Page 56

ACCESSORIES FOR MANUAL MOTOR CONTROLLER MS

CONTACTS

ITEM NO.

WEIGHT G / EACH

PACKING UNIT

1⁄2 M

2 NO

HMS20

40

5

1⁄2 M

1 NO + 1 NC

HMS11

40

5

1⁄2 M

1 NO

HMS10

40

5

1⁄2 M

2 NC

HMS02

40

5

1⁄2 M

1 NC

HMS01

40

5

MODULES

WIRING DIAGRAM

Auxiliary contact for side mounting

FILE E137938

Early make auxiliary contact for side mounting

56

1⁄2 M

1 NO + 1 NC

VHMS11

40

5

1⁄2 M

2 NO

VHMS20

40

5

Technical Data

HMS, VHMS

Rated impulse withstand voltage Uimp

4 000 V

Rated operating voltage Ue

500 V

Overvoltage category/Pollution level

III/3

Max. current (with free air circulation) Ith

6A

Rated operating current Ie

3.5/2 A

Can also be used for low voltage and PLC-inputs

24 V DC, 10 mA

Cross section: 1 conductor mm2 2 conductor mm2

0.75 – 2.5 r; 0.75 – 1.5 f (with ferrule) 0.75 – 2.5 r; 0.75 – 1.5 f (with ferrule)

only HMS, VHMS

Page 57

ACCESSORIES FOR MANUAL MOTOR CONTROLLER MS

RATED OPERATING VOLTAGE

ITEM NO.

WEIGHT G / EACH

PACKING UNIT

Shunt trip for inside mounting with connecting cable (140 mm long) 110 V 50 Hz, 120 V 60 Hz

AMS110

75

10

220-230V 50 Hz, 240 V 60 Hz

AMS220

75

10

380-415 V 50 Hz, 440 V 60 Hz

AMS380

75

10

24 V 50/60 Hz

AMS24

75

10

500 V 50 Hz

AMS500

75

10

24 V DC

AMSD24

75

10

Pull-in voltage 0.7 x Ue

Switch in duration for Ue 100% AC

Undervoltage trip for inside mounting with connecting cable (140 mm long) 110 V 50 Hz, 120 V 60 Hz

UMS110

75

10

220-230 V 50 Hz, 240 V 60 Hz

UMS220

75

10

380-415 V 50 Hz, 440 V 60 Hz

UMS380

75

10

24 V 50/60 Hz

UMS24

75

10

500 V 50 Hz

UMS500

75

Pull-in voltage ≥ 0.85 x Ue

Drop out voltage 0.35-0.7 x Ue

10 Switch in duration for Ue 100%

FILE E137938

57

Page 58

ACCESSORIES FOR MANUAL MOTOR CONTROLLER MS

INSULATED ENCLOSURE IP55 with integrated PE(N) terminal top and bottom each 2 metric knock-outs with integrated PE(N) terminal

ITEM NO.

WEIGHT G / EACH

PACKING UNIT

ITEM NO.

WEIGHT G / EACH

PACKING UNIT

MS.G55

240

1

MS.F55

170

1

ACTIVATION LOCK for up to three padlocks

STOP BUTTON not latching red, on grey surface ITEM NO.

WEIGHT G / EACH

PACKING UNIT

ITEM NO.

WEIGHT G / EACH

PACKING UNIT

MS.PT

55

5

MS.VS

100

10

EMERGENCY-STOP BUTTON

EMERGENCY-STOP BUTTON latching, turn to release red, on yellow surface latching, key release (2 keys) red, on yellow surface

ITEM NO.

WEIGHT G / EACH

PACKING UNIT

ITEM NO.

WEIGHT G / EACH

PACKING UNIT

MS.PV

60

5

MS.PS2

65

5

INDICATOR LIGHT

INDICATOR LIGHT with glow bulb, nominal rated voltage: 220-240 V with glow bulb, nominal rated voltage: 380-440 V

COLOUR green

58

INSULATED FLUSH MOUNTING ENCLOSURE IP55

ITEM NO.

WEIGHT G / EACH

PACKING UNIT

MS.SLG2

10

5

COLOUR green

ITEM NO.

WEIGHT G / EACH

PACKING UNIT

MS.SLG3

10

5

Page 59

ACCESSORIES FOR MANUAL MOTOR CONTROLLER MS

MAX. BUSBAR CURRENT (A)

LENGTH

ITEM NO.

WEIGHT G / EACH

PACKING UNIT for 2 MPCBs without auxiliary contacts

63

90 mm

SB.D02

37

10 for 3 MPCBs without auxiliary contacts

63

136 mm

SB.D03

55

10 for 4 MPCBs without auxiliary contacts

63

180 mm

SB.D04

75

10 for 2 MPCBs each with 1 auxiliary contact fitted on the right side

63

99 mm

SB.D12

40

10 for 3 MPCBs each with 1 auxiliary contact fitted on the right side

63

153 mm

SB.D13

65

10 for 4 MPCBs each with 1 auxiliary contact fitted on the right side

63

207 mm

SB.D14

90

10 for 5 MPCBs each with 1 auxiliary contact fitted on the right side

63

261 mm

SB.D15

115

10 for 2 MPCBs each with 2 auxiliary contacts

63

108 mm

SB.D22

45

10 for 4 MPCBs each with 2 auxiliary contacts

63

234 mm

SB.D24

105

10

SB.DE1

30

10

SB.DA1

5

10

DESCRIPTION

Busbars

Incoming terminal block 63

Shroud

59

Page 60

SWITCHING DEVICES MANUAL MOTOR CONTROLLER MS Technical Data

Standards

IEC 60947, DIN EN 60947, VDE 0660

Mechanical endurance = Electrical endurance

0.1 x 106 switching cycles

Max. operating frequency

30 switching cycles / h

Ambient temperature not enclosed, max./min. enclosed, max./min.

+55 °C / -20 °C +40 °C / -20 °C

Resistance to mechanical shocks

15 g / 10 ms

Installation position any, in IP41 enclosure vertical 1.0 – 6 r; 0.75 – 4 f (with ferrule) 2 conductors differing by not more than 2 sizes

Cross section (1 or 2 conductors)

Torque for terminal screws - Main conductor - Auxiliary conductor - Auxiliary contact for front mounting

1.2 Nm 1.0 Nm 0.5 Nm

Rated impulse withstand voltage Uimp

6 000 V

Overvoltage category / Pollution level

III / 3

Rated operating voltage Ue

690 V AC

Rated operating current Ie

0.16 – 25 A according to setting range

Frequency

40…60 Hz At higher frequencies, the electromagnetic tripping threshold increases by a factor of about 1.1 at 100 Hz; 1.2 at 200 Hz; 1.4 at 400 Hz; 1.5 at 500 Hz

Utilization category (IEC 60947-4-1, DIN EN 60947-4-1, VDE 0660-102)

AC-3 max. 690 V

Temperature compensation (reference values to VDE / IEC)

-5 °C / +40 °C

Temperature compensation Operating range

-20 °C…+55 °C

Power loss in watt per current path by min. setting range 0.6 – 1.05 W / by max. setting range 1.5 – 2.6 W

Rated interrupting capacity Icu MS IEC 60947-2, DIN EN 60947-2, VDE 0660-101 Upper setting Thermal tripping

Icu (kA) 230 V

0.16 – 1.6 A

400 V

500 V

690 V

3

2.5

6

3

2.5

6

2.5

2

No additional protective devices needed inherently stable for any selected short circuit currents

2.5 – 6.3 A 10 A 16 – 25 A

FILE E137938

60

10

Switching times at short circuit minimum command time 2 ms opening delay 2 ms opening time 7 ms