Page 61
Switching Devices Manual Motor Controller MS
���
File E137938
Rated Current [A]
Horsepower ratings at nominal line voltage
115V hp (kW) 0.1 - 0.16
200V hp (kW)
230V hp (kW)
480V hp (kW)
0.40 - 0.63
Ampere rated for motor circuits having a full-load-amperage (FLA) not exceeding the MS’s general purpose rated current and a locked rotor current not exceeding 6 times the MS’s rated current.
0.63 - 1.0
1/2 (0.37)
0.16 - 0.25 0.25 - 0.40
1.0 - 1.6 1.6 - 2.5
600 hp (kW)
Operating current short circuit trip [A]
Article no.
Weight g/each
Packing unit
1.92
MS016
250
1
3.00
MS025
250
1
4.80
MS040
250
1
7.60
MS063
250
1
1/2 (0.37)
12.00
MS1
250
1
3/4 (0.56)
1 (0.75)
19.20
MS1.6
250
1
1/2 (0.37)
1/2 (0.37)
1 (0.75)
11/2 (1.2)
30.00
MS2.5
250
1
3 (2.24)
48.00
MS4
250
1 1
2.5 - 4.0
1/2 (0.37)
3/4 (0.56)
1 (0.75)
2 (1.5)
4.0 - 6.3
3/4 (0.56)
11/2 (1.2)
1 (0.75)
3 (2.24)
5 (3.73)
75.60
MS6.3
250
6.3 - 10
1 (0.75)
2 (1.5)
3 (2.24)
5 (3.73)
71/2 (5.6)
120.00
MS10
250
1
10 - 16
2 (1.5)
3 (2.24)
5 (3.73)
10 (7.46)
10 (7.46)
192.00
MS16
250
1
16 - 20
3 (2.24)
5 (3.73)
5 (3.73)
10 (7.46)
_
240.00
MS20
250
1
20 - 25
3 (2.24)
5 (3.73)
71/2 (5.6)
15 (11.19
_
300.00
MS25
250
1
61
Page 62
Accessories for Manual Motor Controller MS
���
File E137938
Modules
Wiring diagram
Contacts
Article no.
Weight g/each
Packing unit
1⁄2 M
2 NO
HMS20
40
5
1⁄2 M
1 NO + 1 NC
HMS11
40
5
1⁄2 M
1 NO
HMS10
40
5
1⁄2 M
2 NC
HMS02
40
5
1⁄2 M
1 NC
HMS01
40
5
Auxiliary contact for side mounting
Early make auxiliary contact for side mounting
1⁄2 M
1 NO + 1 NC
VHMS11
40
5
1⁄2 M
2 NO
VHMS20
40
5
Technical Data
HMS, VHMS
Rated impulse withstand voltage Uimp
4 000 V
Rated operating voltage Ue
500 V
Overvoltage category/Pollution level
III/3
Max. current (with free air circulation) Ith Rated operating current Ie Can also be used for low voltage and PLC-inputs Cross section: 1 conductor mm2 2 conductor mm2
62 only HMS, VHMS
6A 3.5/2 A 24 V DC, 10 mA 0.75 – 2.5 r; 0.75 – 1.5 f (with ferrule) 0.75 – 2.5 r; 0.75 – 1.5 f (with ferrule)
Page 63
Accessories for Manual Motor Controller MS
���
File E137938
Rated operating voltage
Article no.
Weight g/each
Packing unit
Shunt trip for inside mounting with connecting cable (140 mm long) 110 V 50 Hz, 120 V 60 Hz
AMS110
75
10
220-230V 50 Hz, 240 V 60 Hz
AMS220
75
10
380-415 V 50 Hz, 440 V 60 Hz
AMS380
75
10
24 V 50/60 Hz
AMS24
75
10
500 V 50 Hz
AMS500
75
10
24 V DC
AMSD24
75
10
Pull-in voltage 0.7 x Ue
Switch in duration for Ue 100 % AC
Undervoltage trip for inside mounting with connecting cable (140 mm long) 110 V 50 Hz, 120 V 60 Hz
UMS110
75
10
220-230 V 50 Hz, 240 V 60 Hz
UMS220
75
10
380-415 V 50 Hz, 440 V 60 Hz
UMS380
75
10
24 V 50/60 Hz
UMS24
75
10
500 V 50 Hz
UMS500
75
10
Pull-in voltage ≥ 0.85 x Ue
Drop out voltage 0.35-0.7 x Ue
Switch in duration for Ue 100%
63
Page 64
Accessories for Manual Motor Controller MS
Insulated enclosure IP55 with integrated PE(N) terminal top and bottom each 2 metric knock-outs
Insulated flush mounting enclosure IP55 with integrated PE(N) terminal
Article no.
Weight g/each
Packing unit
Article no.
Weight g/each
Packing unit
MS.G55
240
1
MS.F55
170
1
Stop button not latching red, on grey surface
Padlocking facility for up to three padlocks
Article no.
Weight g/each
Packing unit
Article no.
Weight g/each
Packing unit
MS.PT
55
5
MS.VS
100
10
Emergency-stop button latching, turn to release red, on yellow surface
Emergency-stop button latching, key release (2 keys) red, on yellow surface
Article no.
Weight g/each
Packing unit
Article no.
Weight g/each
Packing unit
MS.PV
60
5
MS.PS2
65
5
Indicator light with glow bulb, nominal rated voltage: 220-240 V
Colour
Article no.
transp. MS.SLW2 green MS.SLG2 red MS.SLR2 yellow MS.SLJ2
64
Weight g/each
Packing unit
10 10 10 10
5 5 5 5
Indicator light with glow bulb, nominal rated voltage: 380-440 V
Colour
Article no.
transp. MS.SLW3 green MS.SLG3 red MS.SLR3 yellow MS.SLJ3
Weight g/each
Packing unit
10 10 10 10
5 5 5 5
Page 65
Accessories for Manual Motor Controller MS
Description max. busbar current (A)
Length
Article no.
Weight g/each
Packing unit for 2 MPCBs without auxiliary contacts
63
90 mm
SB.D02
37
10 for 3 MPCBs without auxiliary contacts
63
136 mm
SB.D03
55
10 for 4 MPCBs without auxiliary contacts
63
180 mm
SB.D04
75
10 for 2 MPCBs each with 1 auxiliary contact fitted on the right side
63
99 mm
SB.D12
40
10 for 3 MPCBs each with 1 auxiliary contact fitted on the right side
63
153 mm
SB.D13
65
10 for 4 MPCBs each with 1 auxiliary contact fitted on the right side
63
207 mm
SB.D14
90
10 for 5 MPCBs each with 1 auxiliary contact fitted on the right side
63
261 mm
SB.D15
115
10 for 2 MPCBs each with 2 auxiliary contacts
63
108 mm
SB.D22
45
10 for 4 MPCBs each with 2 auxiliary contacts
63
234 mm
SB.D24
105
10
SB.DE1
30
10
SB.DA1
5
10
Busbars
Incoming terminal block 63
Shroud
65
Page 66
Switching Devices Manual Motor Controller MS Technical Data
���
File E137938
Standards
IEC 60947, DIN EN 60947, VDE 0660
Mechanical endurance = Electrical endurance
0.1 x 106 switching cycles
Max. operating frequency
30 switching cycles / h
Ambient temperature not enclosed, max./min. enclosed, max./min.
+55 °C / -20 °C +40 °C / -20 °C
Resistance to mechanical shocks
15 g / 10 ms
Installation position any, in IP41 enclosure vertical 1.0 – 6 r; 0.75 – 4 f (with ferrule) 2 conductors differing by not more than 2 sizes
Cross section (1 or 2 conductors) Torque for terminal screws - Main conductor - Auxiliary conductor - Auxiliary contact for front mounting
1.2 Nm 1.0 Nm 0.5 Nm
Rated impulse withstand voltage Uimp
6 000 V
Overvoltage category / Pollution level
III / 3
Rated operating voltage Ue
690 V AC
Rated operating current Ie
0.16 – 25 A according to setting range
Frequency
40…60 Hz At higher frequencies, the electromagnetic tripping values rise by a factor of about 1.1 at 100 Hz; 1.2 at 200 Hz; 1.4 at 400 Hz; 1.5 at 500 Hz
Utilization category (IEC 60947-4-1, DIN EN 60947-4-1, VDE 0660-102)
AC-3 max. 690 V
Temperature compensation (reference values to VDE / IEC)
-5 °C / +40 °C
Temperature compensation Operating range
-20 °C…+55 °C
Power loss in watt per path of current by min. setting range 0.6 – 1.05 W / by max. setting range 1.5 – 2.6 W
Rated short circuit withstand rating Icu MS IEC 60947-2, DIN EN 60947-2, VDE 0660-101 Upper setting Thermal tripping
Icu (kA)
230 V
0.16 – 1.6 A
400 V
500 V
690 V
3
2.5
6
3
2.5
6
2.5
2
No additional protective devices needed inherently stable for any selected short circuit currents
2.5 – 6.3 A 10 A 16 – 25 A Switching times at short circuit minimum command time 2 ms opening delay 2 ms opening time 7 ms
66
10
Page 67
Switching Devices Manual Motor Controller MS Technical Data
���
File E137938
Back-up-protection MS UL and CSA Rating Type
EN and IEC Rating Fuse
Group Fusing
Voltage
[A]
[A]
[V]
Interrupting Capacity [kA]
MS016
1
100
600
5
MS025
1
100
600
5
MS040
1
100
600
5
MS063
2
100
600
5
MS1
4
100
600
5
MS1.6
6
100
600
5
MS2.5
10
100
600
5
25
20
Back-up fuse (gL, aM) [A] 230 V
400 V
500 V
690 V
No back-up fuse necessary inherently stable for any selected short circuit currents
MS4
15
100
600
5
35
25
MS6.3
25
50
600
5
50
35
MS10
40
600
5
MS16
60
600
5
MS20
60
480
MS25
70
480
80
50
35
80
80
63
35
5
80
80
63
50
5
80
80
63
50
1,05-1,2 x In 120
40
40
Minutes
Minutes
1,05-1,2 x In 120
10 4
1
10 4
1 3-pole tripping
3-pole tripping
10
10
MPCB BS
MPCB BS 4
4 2-pole tripping
2-pole tripping 1
1
0,4 upper setting short circuit tripping at lower setting
10-1
10-1
4x10-2
4x10-2
Seconds
Seconds
0,4
10-2 4x10-3
10-3 upper setting short circuit tripping at lower setting
10-2 4x10-3
10-3 1
2
3
4
5 6
8 10
16 20 14 22
40
100
1
2
3
4
5 6
8
12,5 17,5 10 14 20 x Rated current x Rated current
Characteristic for MS 016 – MS 16
Characteristic for MS 20 – MS 25
40
100
67
Page 68
Switching Devices Manual Motor Controller MS Dimension Drawings
Motor protective circuit breaker MS
35,5
80
42
45
76,5
45
Mounting dimensions 30
63
71,5 75,5 85,5
Insulated enclosure MS.G55
38 Mounting dimensions
M20
90
90 possible to integrate 1 MPCB and 2 side mounted auxiliary contacts
M20
140
150
80
140
97,5
M20
55
M20 55
70-72
6 max.
85,5
70-72
64
110
116-118
104
130
M4
45°
R4 81
15
Emergency-stop button MS.PT – PS.PS2
95 54
68
55,5
27
28,5
MS.PT
MS.PV
68 37
MS.PS2
33-34
116-118
Insulated flush mounting enclosur MS.F55
Page 69
Horsepower rating and Kilowatt rating
Wire cross section in AWG and mm²
Kilowatt [kW]
AWG No.
Cross section [mm2]
Diameter [mm]
0.167
0.13
21
0.412
0.724
0.25
0.184
20
0.519
0.813
0.5
0.38
19
0.653
0.912
0.75
0.55
18
0.824
1.27
1
0.735
17
1.01
1.151
1.25
0.919
16
1.307
1.29
1.5
1.103
15
1.651
1.45
1.75
1.287
14
2.082
1.628
Horsepower [hp]
2
1.471
13
2.627
1.829
2.5
1.839
12
3.307
2.052
3
2.206
11
4.169
2.304
4
2.942
10
5.26
2.588
5
3.677
9
6.633
2.906
6
4.413
8
8.367
3.264
7
5.148
7
10.55
3.665
7.5
5.516
6
13.229
4.115
8
5.884
5
16.767
4.62
9
6.619
4
21.148
5.189
10
7.355
3
26.667
5.827
11
8.09
2
33.624
6.543
12
8.826
1
42.406
7.348
13
9.561
1/0
53.182
8.252
14
10.297
2/0
67.43
9.266
15
11.032
3/0
85.014
10.404
16
11.768
4/0
107.22
11.684
69
Page 70
ABL(4 )SURSUM ABL(7)SURSUM p10
*DIOUR 4 4D1 dis »
10kA
1