Switching Devices according to UL489, UL508 and UL1077, pages 71 to 80

Pages 71 to 80 of 92

The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the ABL Sursum 3B16UM

Page 71

ABL SURSUM Switching Devices according to UL1077 and CSA-22.2 No. 235

Our range of UL1077 supplementary protectors can be used where any additional protection in control circuits is required, and – combined with the accessories from our UL508 UM range – it also offers enhanced monitoring and control capabilities.

71

Page 72

Switching Devices Supplementary Protector according to UL1077 and CSA-22.2 No.235 UR Product Range, B, C and D Characteristics

File E 137915

Rated current

B

Characteristic C

D

Weight g/each

Packing unit

In A

Article no.

Article no.

Article no.

1B1UR 1B2UR 1B3UR 1B4UR 1B5UR 1B6UR 1B8UR 1B10UR 1B12UR 1B13UR 1B15UR 1B16UR 1B20UR 1B25UR 1B30UR 1B32UR 1B40UR 1B50UR 1B60UR 1B63UR

1C05UR 1C1UR 1C2UR 1C3UR 1C4UR 1C5UR 1C6UR 1C8UR 1C10UR 1C12UR 1C13UR 1C15UR 1C16UR 1C20UR 1C25UR 1C30UR 1C32UR 1C40UR 1C50UR 1C60UR 1C63UR

1D05UR 1D1UR 1D2UR 1D3UR 1D4UR 1D5UR 1D6UR 1D8UR 1D10UR 1D12UR 1D13UR 1D15UR 1D16UR 1D20UR 1D25UR 1D30UR 1D32UR 1D40UR 1D50UR 1D60UR 1D63UR

150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150

12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12

2C05UR 2C1UR 2C2UR 2C3UR 2C4UR 2C5UR 2C6UR 2C8UR 2C10UR 2C12UR 2C13UR 2C15UR 2C16UR 2C20UR 2C25UR 2C30UR 2C32UR 2C40UR 2C50UR 2C60UR 2C63UR

2D05UR 2D1UR 2D2UR 2D3UR 2D4UR 2D5UR 2D6UR 2D8UR 2D10UR 2D12UR 2D13UR 2D15UR 2D16UR 2D20UR 2D25UR 2D30UR 2D32UR 2D40UR 2D50UR 2D60UR 2D63UR

300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300

6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

1-pole 0.5 1 2 3 4 5 6 8 10 12 13 15 16 20 25 30 32 40 50 60 63 * * 63 A without UL approval

2-pole 0.5 1 2 3 4 5 6 8 10 12 13 15 16 20 25 30 32 40 50 60 63 * * 63 A without UL approval

72

2B1UR 2B3UR 2B4UR 2B5UR 2B6UR 2B8UR 2B10UR 2B12UR 2B13UR 2B15UR 2B16UR 2B20UR 2B25UR 2B30UR 2B32UR 2B40UR 2B50UR 2B60UR 2B63UR

Page 73

Switching Devices Supplementary Protector according to UL1077 and CSA-22.2 No.235 UR Product Range, B, C and D Characteristics

File E 137915

Rated current

B

Characteristic C

D

In A

Article no.

Article no.

Article no.

3B1UR 3B2UR 3B3UR 3B4UR 3B5UR 3B6UR 3B8UR 3B10UR 3B12UR 3B13UR 3B15UR 3B16UR 3B20UR 3B25UR 3B30UR 3B32UR 3B40UR 3B50UR 3B60UR 3B63UR

3C05UR 3C1UR 3C2UR 3C3UR 3C4UR 3C5UR 3C6UR 3C8UR 3C10UR 3C12UR 3C13UR 3C15UR 3C16UR 3C20UR 3C25UR 3C30UR 3C32UR 3C40UR 3C50UR 3C60UR 3C63UR

3D05UR 3D1UR 3D2UR 3D3UR 3D4UR 3D5UR 3D6UR 3D8UR 3D10UR 3D12UR 3D13UR 3D15UR 3D16UR 3D20UR 3D25UR 3D30UR 3D32UR 3D40UR 3D50UR 3D60UR 3D63UR

Weight g/each

Packing unit

450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450

4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

3-pole 0.5 1 2 3 4 5 6 8 10 12 13 15 16 20 25 30 32 40 50 60 63 * * 63 A without UL approval

��� File E 137938

Rated current

Rated voltage

In A

Volt AC

Test currents * electromagnetic not tripping I4 A tripping I5 A

Weight g/each

Packing unit

150

5

Article no.

Neutral switch – for mounting instructions please consult page 75 0.3 - 63

277/480

400

700

N63UM

* additional electromagnetic protection

73

Page 74

Accessories for Switching Devices Manual Motor Controller and Supplementary Protectors according to UL508 and CSA-22.2 No.14 for Product Ranges UM and UR

��� File E 137938

Auxiliary contact Type of contact

Module

Article no.

Contacts

Weight g/each

Packing unit

1/2

1 auxiliary contact

1NO

H10UM

35

10

1/2

2 auxiliary contacts

1NO + 1NC

H11UM

40

10

1/2

3 auxiliary contacts

1NO + 2NC

H12UM

45

10

1/2

3 auxiliary contacts

2NO + 1NC

H21UM

45

10

24

12

24

H10UM

34

H11UM

H12UM 11

Standards

34

24

12

H21UM 33

23

23

22 12

21

33 11

23

11

Acc. to IEC 60947-5-1, DIN EN 60947-5-1, VDE 0660-200, UL508 10 A /240 V AC 3 A / 110 V DC 1 A / 220 V DC 1 mA at 24 V DC

Rated operating currents Minimum contact load Conductor cross sections Type of conductor *)

min.

max.

Single wire

1.0 mm2 (AWG18)

2.5 mm2 (AWG14)

Stranded wire

1.0 mm2 (AWG18)

1.5 mm2 (AWG16)

Stranded wire with ferrule

1.0 mm2 (AWG18)

Torque

1.5 mm2 (AWG16) max. 0.8 Nm (7 lb.in)

*) Stripped length 8 - 9 mm

Shunt trip Rated operating voltage max. operating current at Un (t < 10 ms)

Article no.

Weight g/each

Packing unit

1

12 V UC

1.3 A

FA12UM

105

5

1

24 V UC

0.6 A

FA24UM

105

5

1

48 - 74 V UC

0.2 A

FA48UM

105

5

1

110 - 240 V UC, 415 V AC

0.25 A at 110 V

FA110UM

105

5

Module

0.5 A at 240 V 0.58 A at 277 V

Dimension drawing FA..UM, N63UM

Lock-off/Lock-on device

74

Article no.

Weight g/each

Packing unit

EASS

2

10

Page 75

Accessories for Switching Devices Manual Motor Controller and Supplementary Protectors according to UL508 and CSA-22.2 No.14 for Product Ranges UM and UR

Mounting Instructions of Accessories

Switching device

Neutral switch/ Shunt trip

Neutral switch/ Shunt trip

Switching device

Auxiliary contact

Auxiliary contact

5.

3. 4.

6. Mounting screw 34 mm (see accessories page 25)

7mm

1.

4. 3.

90°

1.

6.

24 mm

2.

Applies to N...UM and FA...UM: The accessory devices N...UM and FA...UM can be mounted on the right or left. The auxiliary contact H...UM can only be mounted on the right.

2.

Mounting: 1. Bring the blue knobs of all devices into the “OFF” position 2. Remove grey cover from the switching device and attachment 3. Insert drive plate between the switching device and N...UM or FA...UM 4. Insert connecting pin into the knob (insertion depth approx. 7 mm) 5. Combine switching device and N...UM or FA...UM 6. Screw devices together (observe correct screw length)

Applies to H...UM: The auxiliary contact H...UM can only be mounted on the right. Mounting: 1. Bring the blue knobs of both devices into the “OFF” position 2. Remove grey cover from the switching device 3. Combine switching device and H...UM 4. Insert connection screws and connect the two devices by turning the screws by 90° 5. After mounting close and open to check operation

Applies to all switching devices ...UM, ...UR, N63UM and FA...UM

Box terminal for • solid conductors • flexible conductors with or without cable lug

Screw terminal for forked cable lug

Screw terminal for ring cable lug (ring tongue)

• Ring cable lugs can be connected by opening the flap and removing the connecting screw • Can also be used for applications that require ring cable lugs (e.g. nuclear power stations)

• Protection against contact with live parts according to DIN EN 50274, VDE 0660-514 is fully guaranteed

Design of the terminals • Optical detection of the screw position • Increased break resistance if the screwdriver becomes jammed • Universal connecting terminals, suitable for connecting all known cable lugs such as ring or forked cable lugs and pin terminals

75

Page 76

Switching Devices Supplementary Protector according to UL1077 and CSA-22.2 No.235 Product Range UR, B, C and D Characteristics Technical Data

File E137915

Characteristic

B

C

D

Application

Lighting,Control circuits General electronics Wiring protection, Business equipment, Appliances

Lighting,Control circuits Wiring protection, Business equipment Appliances

Control transformers Power supplies Reactive load

Number of poles

1 - 3; 1 + N; 3 + N

Standards

UL1077 and CSA-22.2 No.235

Short circuit withstand rating see data sheet for use in the USA and Canada (page 77)

Current limiting class

3

Max. back-up fuse see data sheet for use in the USA and Canada (page 77)

Rated voltage AC

277 / 480 V

Rated current range

Test currents

3

1 - 63* A

0.5 - 63* A

0.5 - 63* A

Thermal not tripping I1 (A) > 1 h

1.13 x In

1.13 x In

1.13 x In

Thermal tripping I2 (A) < 1 h

1.45 x In

1.45 x In

1.45 x In

Electromagnetic not tripping I4 (A) > 0,1 s

3 x In

5 x In

10 x In

Electromagnetic tripping I5 (A) < 0,1 s

5 x In

10 x In

16 x In

Reference calibration temperature of the thermal tripping

30° C + 5° C Influence of the ambient temperature on the thermal release: Decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5% per 10°C difference in temperature

Frequency range of the electromagnetic trip

16 2/3 to 60 Hz With higher frequencies, the electromagnetic tripping values increase by approximately a factor of 1.1 at 100 Hz; 1.2 at 200 Hz; 1.3 at 300 Hz; 1.4 at 400 Hz; 1.5 for DC

Ambient temperature

-25 °C to +55 °C

Storage temperature

-40 °C to +70 °C

Device depth according to DIN 43880

68 mm

Mechanical live

10,000 cycles (ON / OFF)

Protection cover

Finger safe and safe to back of hand according to DIN EN 50274/ VDE0660-514, BGV A3

Insulation group acc. to DIN/VDE 0110

C at 250 V AC B at 400 V AC

Degree of protection acc. to EN/IEC 60529

IP20

Installation position any

Mounting

DIN-rail according to DIN EN 60715 35 mm

Lockability

The handle can be secured against manual switching in the on and off position by a lead seal

Climatic resistance

Humid heat constant according to DIN EN 60068-2-78 Humid heat cycle according to DIN EN 60068-2-30

Vibration resistance

> 15 g according to DIN EN 60068-2-59 during a load with I1

Resistance to mechanical shocks

25g 11ms * 63 A without UL approval

76

Page 77

Switching Devices Supplementary Protector according to UL1077 and CSA-22.2 No.235 Product Range UR, B, C and D Characteristics Technical Data

File E137915

Conductor cross sections Box terminal bottom

Box terminal top

Type of conductor *)

max.

min.

max.

min.

Single wire

35 mm2 (AWG2)

1 mm2 (AWG18)

25 mm2 (AWG3)

1 mm2 (AWG18)

Multiple wire

35 mm2 (AWG2)

16 mm2 (AWG6)

25 mm2 (AWG3)

16 mm2 (AWG6)

Stranded wire

25 mm2 (AWG3)

1 mm2 (AWG18)

16 mm2 (AWG6)

1 mm2 (AWG18)

Stranded wire with ferrule

16 mm2 (AWG6)

1 mm2 (AWG18)

16 mm2 (AWG6)

1 mm2 (AWG18)

Busbar cable lug up to 3 mm thickness

Torque up to 1.5 mm thickness max. 2.5 Nm (22.2 lb.in)

*) Stripped length: bottom 12 - 14 mm, top 10 - 12 mm

Short circuit withstand rating and maximum back-up fuse for use in the USA and Canada Characteristic

B, C and D

Standards

Short circuit withstand rating at rated voltage Ambient temperature 40 °C

UL1077 and CSA-22.2 No.235 Number of poles

Maximum rated voltage [V]

Rated current [A]

Short circuit withstand rating [kA]

1/1+N

277

0.3 - 10

10

70 A

1/1+N

277

12 - 60

10

4 x In

2/3/3+N

480

0.3 - 10

10

70 A

2/3/3+N

480

12 - 60

10

4 x In

Maximum back-up fuse [A]

Internal resistance for Product Ranges UR Rated current [A]

Trip characteristic B [Ohm]

0.5

C [Ohm]

D [Ohm]

6.8540

6.0009

1,0

1.7000

1.7000

1.7560

2,0

0.4190

0.4190

0.4190

3,0

0.2020

0.2020

0.2020

4,0

0.1090

0.1090

0.1090

5,0

0.0654

0.0654

0.0654

6,0

0.0528

0.0528

0.0491

8,0

0.0278

0.0278

0.0240

10

0.0216

0.0216

0.0187

12/13

0.0113

0.0084

0.0085

15/16

0.0085

0.0085

0.0076

20

0.0067

0.0067

0.0064

25

0.0050

0.0050

0.0041

30/32

0.0032

0.0032

0.0027

40

0.0025

0.0025

0.0022

50

0.0019

0.0019

0.0018

60/63 *

0.0018

0.0018

0.0017

* 63 A without UL approval

77

Page 78

Switching Devices Supplementary Protector according to UL1077 and CSA-22.2 No.235 Product Range UR, B, C and D Characteristics Technical Data

File E137915

1,13-1,45 x IN

60 40

Minutes

Minutes

60 40

10 4

4

1

10

10

4

4

1

1

0,4

0,4

C

D

B

10 -1

10 -1

4x10-2

4x10-2

10

Seconds

Seconds

10

1

B

1,13-1,45 x I N

-2

-3 4x10

10

C

D

-2

-3 4x10

10 -3

10 -3 1

2

3

4

5 6

8 10

16 20

40

100 x Rated current

B, C and D characteristic UR

1

2

3

4

5 6

8 10

20

40

100 x Rated current ln = 0.3 - 10 A

B, C and D characteristic UR ln = 13 - 63* A

* 63 A without UL approval

78

Page 79

Switching Devices Supplementary Protector according to UL1077 and CSA-22.2 No.235 Product Range UR, B, C and D Characteristics Dimension Drawing

File E137915

1-pole

2-pole

3-pole

79

Page 80

Where Innovation is a Tradition

Setting market standards with new developments has always been a fundamental concern for ABL SURSUM. Such is the idea behind the SCHUKO system, to this day one of the most popular plug connection systems in the world and the creation of ABL founder Albert Büttner. The first screw-in circuit breaker with an electromagnetic release was created at SURSUM, founded in 1912 by Wilhelm Leyhausen. These two inventions were the prelude to a series of innovative developments which have gave the two companies a central role in the annals of consumer electronics for decades.

In 1986 the two traditional medium-sized companies merged; plug connection specialist ABL and circuit breaker specialist SURSUM formed one highly productive company now known as ABL SURSUM Bayerische Elektrozubehör GmbH & Co.KG.