For the ABL Sursum 3B16UM
Page 51
The manual motor starter type MA is a specific development, and combines the design of the miniature circuit breaker with the traditional features of a manual motor controller. The adjustable calibration of the thermal tripping in the IEC nominal rating ranges goes up to 40 A. It was designed to handle high inrush loads from power supplies, motors etc. wiring and equipment can be protected from damages due to overcurrent, and nuisance tripping in cases of high inrush currents can be reduced significantly. With the UL508 approval, this device is available either in an IEC or in a UL approved version.
The concept and principles of design of the manual motor starters type MS have proven their reliability through 40 years of experience all around the world. It is still one of the types of manual motor starters most often used in the world for single motor protection. They are equipped with phase failure sensitivity, isolating and main switch functions. In combination with the emergency push button, it is a simple and convenient complete solution for machinery. Enhanced monitoring and control is given with the wide range of accessories such as undervoltage release, shunt trip and auxiliary contacts. Due to the common design and the years of production, it is the ideal spare part for millions of machines which have been equipped with such a device in the past.
51
Page 52
Switching Devices Manual Motor Controller MA Overview
���
File E137938
Lock-off/Lock-on device
Shunt trip
Auxiliary contact
Manual Motor Controller MA...UM
Under voltage trip
52
Page 53
Switching Devices Manual Motor Controller MA according to UL508 and CSA-22.2 no. 14 Product Range MA...UM
���
File E137938
Rated Current [A]
Horesepower ratings at normal line voltage
Operating current short circuit trip [A]
Article no.
Weight g/each
Packing unit
0.1 – 0.16
1.92
MA016UM
450
1
0.16 – 0.25
3.00
MA025UM
450
1
4.80
MA040UM
450
1
7.60
MA063UM
450
1
110-120 V hp (kW)
0.25 – 0.40 0.40 – 0.63 0.63 – 1.0
200V hp (kW)
208 V hp (kW)
220-240 V hp (kW)
460-480 V hp (kW)
Through MA2.5UM, ampere rated for motor circuits having a fullload-amperage (FLA) not exceeding the MA´s general purpose rated current (RC, equals maximum dial setting) and a lockedrotor current not exceeding 6 times the MA´s RC.
12.00
MA1.0UM
450
1
1.0 – 1.6
19.20
MA1.6UM
450
1
1.6 – 2.5
30.00
MA2.5UM
450
1
2.5 – 4.0
½ (0.37)
¾ (0.56)
¾ (0.56)
1 (0.75)
2 (1.5)
48.00
MA4.0UM
450
1
4.0 – 6.3
¾ (0.56)
1½ (1.2)
1½ (1.2)
1 (0.75)
3 (2.24)
75.60
MA6.3UM
450
1
6.3 – 10
1 (0.75)
2 (1.5)
2 (1.5)
3 (2.24)
5 (3.73)
120.00
MA10UM
450
1
10 – 16
2 (1.5)
3 (2.24)
3 (2.24)
5 (3.73)
10 (7.46)
192.00
MA16UM
450
1
16 – 20
3 (2.24)
5 (3.73)
5 (3.73)
5 (3.73)
10 (7.46)
240.00
MA20UM
450
1
20 – 25
3 (2.24)
5 (3.73)
7½ (5.6)
7½ (5.6)
15 (11.19)
300.00
MA25UM
450
1
25 – 32
5 (3.73)
7½ (5.6)
7½ (5.6)
10 (7.46)
20 (14.92)
240.00
MA32UM
450
1
32 – 40
5 (3.73)
10 (7.46)
10 (7.46)
10 (7.46)
25 (18.65)
300.00
MA40UM
450
1
53
Page 54
Accessories for Switching Devices Manual Motor Controller MA according to UL508 and CSA-22.2 No.14 for Product Ranges UM and MA...UM
���
File E137938
Shunt trip Module
Rated operating voltage
Max. operating current at Un (t < 10 ms)
Article no.
Weight g/each
Packing unit
1
12 V ~ –
1.3 A
FA12UM
105
5
1
24 V ~ –
0.6 A
FA24UM
105
5
1
48 - 72 V ~ –
0.2 A
FA48UM
105
5
1
110 - 240 V ~ – , 415 V~
0.25 A at 110 V
FA110UM
105
5
0.5 A at 240 V 0.58 A at 277 V Switch in duration for Ue 100%
Pull-in voltage 0.7 x Ue
Undervoltage trip (60 Hz) * Module
Rated voltage
Article no.
Weight g/each
Packing unit
1
120 V
UA120UM
150
5
150
5
1
220 V
UA220UM
Pull-in voltage ≥ 0.85 x Ue
Drop out voltage 0.35 - 0.7 x Ue
Switch in duration for Ue 100 %
* without UL approval
Auxiliary contact Module
Type of contact
Contacts
Weight g/each
Article no.
Packing unit
1⁄2
1 auxiliary contact
1NO
H10UM
35
10
1⁄2
2 auxiliary contacts
1NO + 1NC
H11UM
40
10
1⁄2
3 auxiliary contacts
1NO + 2NC
H12UM
45
10
1⁄2
3 auxiliary contacts
2NO + 1NC
H21UM
45
10
24
H10UM
24
12 34
H11UM 23
22 12
H12UM 23
Standards
24
12
H21UM 33
11
34
21
33 11
23
11 according to IEC 60947-5-1, DIN EN 60947-5-1, VDE 0660-200, UL508
Rated operating currents
10 A /240 V AC 3 A / 110 V DC 1 A / 220 V DC
Minimum contact load
1 mA at 24 V DC
Conductor cross sections Type of conductor *)
min.
max.
Single wire
1.0 mm2 (AWG18)
2.5 mm2 (AWG14)
Stranded wire
1.0 mm2 (AWG18)
1.5 mm2 (AWG16)
Stranded wire with ferrule
1.0 mm2 (AWG18)
1.5 mm2 (AWG16)
Torque *) Stripped length 8 - 9 mm
54 max. 0.8 Nm (7 lb.in)
Page 55
Accessories for Switching Devices Manual Motor Controller MA according to UL508 and CSA-22.2 No.14 for Product Ranges UM and MA...UM
Lock-off/Lock-on device For miniature circuit breakers and motor protective circuit breakers
Distance device 9 mm
Module
Article no.
1/2
HDS
Weight Packing g/each unit 7
10
Article no. EASS
Weight Packing g/each unit 4
10
Various Busbars see page 40-41
55
Page 56
Switching Devices Manual Motor Controller MA
��� according to UL508 and CSA-22.2 No.14 Technical Data Product Range MA...UM
File E137938
Technical Data Standards
Short circuit withstand rating
Utilization category Group Short Circuit Ratings (UL/CSA Ratings)
UL508 and CSA-22.2 No.14
0.16 A – 2.5 A / 42 kA, 4 A – 16 A / 14 kA, 20 – 40 A / 10 kA
AC 3 at Ue 415 V~ (up to In 25 A) 1200 A / 42 kA, 350 A / 14 kA, 350 A / 10 kA
Rated voltage AC
480Y / 277 VAC
Rated current range
15 setting ranges from 0.1 up to 40 A
Rated uninterrupted current Ith
40 A
Tripping time at 6 x le
> 5s/TII
Test currents
Thermal not tripping I1 (A) > 2 h Thermal tripping I2 (A) < 2 h
1.05 x Ie
1.15 x le
Electromagnetic not tripping I4 (A) > 0.1 s for the lower setting 16 x le (12.5 x le > 16 A) for the upper setting 10 x le
Electromagnetic tripping I5 (A) < 0.1 s for the lower setting 19 x le (15 x le > 16 A) for the upper setting 12 x le
Temperature compensation Permitted ambient temperature Device depth according to DIN 43880
Mechanical endurance
Permitted operating frequency
Protection cover up to +40 °C open -20 °C to +50 °C, enclosure -20 °C to +40 °C storage/transport -40 °C to +70 °C 68 mm
30 000 switching cycles (30 000 ON / 30 000 OFF)
30 switching cycles/h
Safe for fingers and back of hand acc. to DIN EN 50274, VDE 0660-514 BGV A2
Degree of protection according to EN/IEC 60529
IP20
Installation position any
Mounting
On DIN-rail acc. to DIN EN 60715 35 mm
Lockability
The handle can be secured against manual switching in the on and off position by a lead seal
Climatic resistance
Humid heat constant according to DIN IEC 60068-2 – 78 Humid heat cyclic according to DIN EN 60068-2 – 30
Vibration resistance
> 15 g according to DIN EN 60068-2 – 59 for a load with I1
Resistance to mechanical shocks
56
25 g 11 ms
Page 57
Switching Devices Manual Motor Controller MA according to UL508 and CSA-22.2 No.14 Technical Data Product Range MA...UM
���
File E137938
Conductor cross sections
Box terminal bottom
Type of conductor *)
Box terminal top max.
min.
max.
min.
Single wire
25 mm2 (AWG3)
1.0 mm2 (AWG18)
25 mm2 (AWG3)
1.0 mm2 (AWG18)
Multiple wire
25 mm2 (AWG3)
16 mm2 (AWG6)
25 mm2 (AWG3)
16 mm2 (AWG6)
Stranded wire
16 mm2 (AWG6)
1.0 mm2 (AWG18)
25 mm2 (AWG3)
1.0 mm2 (AWG18)
Stranded wire with ferrule
16 mm2 (AWG6)
1.0 mm2 (AWG18)
16 mm2 (AWG6)
1.0 mm2 (AWG18)
Busbar Cable lug Combined, conductor and busbar or cable lug up to 3 mm thickness up to 1.5 mm thickness up to 25 mm2 and up to 2 mm thickness not possible
Torque max. 2.5 Nm (22.2 lb.in)
*) Stripped length: bottom 12 - 14 mm, top 10 - 12 mm
1.15 x In
1.15 x In 60 40
Minutes
Minutes
60 40
10 4
1
10 4
1
20 10
10
4
4
1
1 0.4 upper setting short circuit tripping at lower setting
10-1
10-1
4x10-2
4x10-2
Seconds
Seconds
0.4
10-2 4x10-3
10-3 upper setting short circuit tripping at lower setting
10-2 4x10-3
10-3 1
2
3
4
5 6
16
8 10 12
20 19
40 x Rated current
Characteristic for MA016UM – MA16UM
100
1
2
3
4
5 6 x Rated current
8 10 15 12
20
40
100
12.5
Characteristic for MA20UM – MA40UM
57
Page 58
Switching Devices Manual Motor Controller MA according to UL508 and CSA-22.2 No.14 Technical Data Product Range MA...UM
���
File E137938
Internal resistance per pole in mΩ and power loss in Watt of the complete device Type
Lower setting
Upper setting
Internal resistance per pole
A
A mΩ lower setting Watt upper setting Watt
MA016UM
0.10
0.16
85500
2.6
6.6
MA025UM
0.16
0.25
35000
2.7
6.6
MA040UM
0.25
0.40
15000
2.8
7.2
MA063UM
0.40
0.63
5200
2.5
6.2
MA1.0UM
0.63
1.0
2300
2.7
6.9
MA1.6UM
1.0
1.6
950
2.9
7.3
MA2.5UM
1.6
2.5
355
2.7
6.7
MA4.0UM
2.5
4.0
142
2.7
6.8
MA6.3UM
4.0
6.3
54
2.6
6.4
MA.10UM
6.3
10
28
3.3
8.4
MA.16UM
10
16
13.9
4.2
10.7
MA.20UM
16
20
9.9
5.2
8.2
MA.25UM
20
25
6.3
8
12.3
MA.32UM
25
32
3.85
6.4
10.5
MA.40UM
32
40
3.1
8.6
13.4
Type
Rated Current [A]
FLA Dial Adjustment Markings
MA016UM
0.16
0.1/ 0.12/0.14/0.16
MA025UM
0.25
0.16/0.19/0.22/0.25
MA040UM
0.40
0.25/0.30/0.35/0.40
MA063UM
0.63
0.40/0.48/0.56/0.63
MA1.0UM
1.00
0.63/0.75/0.87/1.0
MA1.6UM
1.60
1.0/1.2/1.4/1.6
MA2.5UM
2.50
1.6/1.9/2.2/2.5
MA4.0UM
4.00
2.5/3.0/3.5/4.0
MA6.3UM
6.30
4.0/4.8/5.6/6.3
MA10UM
10
6.3/7.5/8.7/10
MA16UM
16
10/12/14/16
MA20UM
20
16/17/18.5/20
MA25UM
25
20/21.5/23/25
MA32UM
32
25/27/30/32
MA40UM
40
32/34/37/40
Group short circuit rating at 480 VAC a) (and BCP size)
10 kARMS symmetrical (max. 350 A MCCB or RK5)
Note: HEA - Horsepower Equivalent Amperes, the nominal amperage assigned to standard motor horsepower ratings in design guide tables such as NFPA-70 Tables 430-248, 430-249, 430-250; UL1077 Table 16.2; CSA - C22.2 No. 235-M89 Tables 44 and 45; CSA-C22.2 No. 14-M91 Table 19, etc. Multiply HEA values (in parenthesis) by 1.1 if power factor is 90%, and by 1.2 if power factor is 80%.
58
3 Ø horsepower ratings at nominal line voltage (see note for HEA definition) 110 – 120 V hp (HEA)
200 V hp (HEA)
208 V hp (HEA)
220 – 240 V hp (HEA)
460 – 480 V hp (HEA)
Through MA2.5UM, ampere rated for motor circuits having a fullload-amperage (FLA) not exceeding the MA´s general purpose rated current (RC, equals maximum dial setting) and a lockedrotor current not exceeding 6 times the MA´s RC.
42 kARMS symmetrical (max. 1200 A MCCB or RK5)
14 kARMS symmetrical (max. 350 A MCCB or RK5)
Power loss for the complete device for
½ (4.0)
¾ (3.2)
¾ (3.1)
1 (3.6)
¾ (5.6)
1½ (6.0)
1½ (5.7)
1½ (5.2)
2 (3.42) 3 (4.8)
1 (7.2)
2 (7.8)
2 (7.5)
3 (9.6)
5 (7.6)
2 (13.6)
3 (11.0)
3 (10.6)
5 (15.2)
10 (14.0)
3 (19.2)
5 (17.5)
5 (16.7)
5 (15.2)
10 (14.0)
3 (19.2)
5 (17.5)
7½ (24.2)
7½ (22.0)
15 (21.0)
5 (30.4)
7½ (25.0)
7½ (24.2)
10 (28.0)
20 (27.0)
5 (30.4)
10 (32.0)
10 (31.0)
10 (28.0)
25 (34.0)
a) The standard-circuit short-circuit rating is 14 kA for all types. Group ratings can be used in a standard circuit (e.g., MA1.0UM at 42 kA), but a higher standard rating cannot be used in a group circuit (e.g., MA40UM at 14 kA only in standard circuit.)
Page 59
Switching Devices Manual Motor Controller MA
��� according to UL508 and CSA-22.2 No.14 Dimension Drawing
File E137938
59
Page 60
Switching Devices Manual Motor Controller MS Overview
Trip-indicating auxiliary contact or shunt trip or undervoltage trip
Auxiliary contact for front mounting
Auxiliary contact right and/ or left hand mounted Auxiliary contact right and/ or left hand mounted
Emergency-stop button Indicator light
Insulated flush mounting enclosure IP41 or IP55
Insulated enclosure IP41 or IP55 Padlocking facility
60