For the ABL Sursum 3B16UM

Page 51

The manual motor starter type MA is a specific development, and combines the design of the miniature circuit breaker with the traditional features of a manual motor controller. The adjustable calibration of the thermal tripping in the IEC nominal rating ranges goes up to 40 A. It was designed to handle high inrush loads from power supplies, motors etc. wiring and equipment can be protected from damages due to overcurrent, and nuisance tripping in cases of high inrush currents can be reduced significantly. With the UL508 approval, this device is available either in an IEC or in a UL approved version.

The concept and principles of design of the manual motor starters type MS have proven their reliability through 40 years of experience all around the world. It is still one of the types of manual motor starters most often used in the world for single motor protection. They are equipped with phase failure sensitivity, isolating and main switch functions. In combination with the emergency push button, it is a simple and convenient complete solution for machinery. Enhanced monitoring and control is given with the wide range of accessories such as undervoltage release, shunt trip and auxiliary contacts. Due to the common design and the years of production, it is the ideal spare part for millions of machines which have been equipped with such a device in the past.

51

Page 52

Switching Devices Manual Motor Controller MA Overview

���

File E137938

Lock-off/Lock-on device

Shunt trip

Auxiliary contact

Manual Motor Controller MA...UM

Under voltage trip

52

Page 53

Switching Devices Manual Motor Controller MA according to UL508 and CSA-22.2 no. 14 Product Range MA...UM

���

File E137938

Rated Current [A]

Horesepower ratings at normal line voltage

Operating current short circuit trip [A]

Article no.

Weight g/each

Packing unit

0.1 – 0.16

1.92

MA016UM

450

1

0.16 – 0.25

3.00

MA025UM

450

1

4.80

MA040UM

450

1

7.60

MA063UM

450

1

110-120 V hp (kW)

0.25 – 0.40 0.40 – 0.63 0.63 – 1.0

200V hp (kW)

208 V hp (kW)

220-240 V hp (kW)

460-480 V hp (kW)

Through MA2.5UM, ampere rated for motor circuits having a fullload-amperage (FLA) not exceeding the MA´s general purpose rated current (RC, equals maximum dial setting) and a lockedrotor current not exceeding 6 times the MA´s RC.

12.00

MA1.0UM

450

1

1.0 – 1.6

19.20

MA1.6UM

450

1

1.6 – 2.5

30.00

MA2.5UM

450

1

2.5 – 4.0

½ (0.37)

¾ (0.56)

¾ (0.56)

1 (0.75)

2 (1.5)

48.00

MA4.0UM

450

1

4.0 – 6.3

¾ (0.56)

1½ (1.2)

1½ (1.2)

1 (0.75)

3 (2.24)

75.60

MA6.3UM

450

1

6.3 – 10

1 (0.75)

2 (1.5)

2 (1.5)

3 (2.24)

5 (3.73)

120.00

MA10UM

450

1

10 – 16

2 (1.5)

3 (2.24)

3 (2.24)

5 (3.73)

10 (7.46)

192.00

MA16UM

450

1

16 – 20

3 (2.24)

5 (3.73)

5 (3.73)

5 (3.73)

10 (7.46)

240.00

MA20UM

450

1

20 – 25

3 (2.24)

5 (3.73)

7½ (5.6)

7½ (5.6)

15 (11.19)

300.00

MA25UM

450

1

25 – 32

5 (3.73)

7½ (5.6)

7½ (5.6)

10 (7.46)

20 (14.92)

240.00

MA32UM

450

1

32 – 40

5 (3.73)

10 (7.46)

10 (7.46)

10 (7.46)

25 (18.65)

300.00

MA40UM

450

1

53

Page 54

Accessories for Switching Devices Manual Motor Controller MA according to UL508 and CSA-22.2 No.14 for Product Ranges UM and MA...UM

���

File E137938

Shunt trip Module

Rated operating voltage

Max. operating current at Un (t < 10 ms)

Article no.

Weight g/each

Packing unit

1

12 V ~ –

1.3 A

FA12UM

105

5

1

24 V ~ –

0.6 A

FA24UM

105

5

1

48 - 72 V ~ –

0.2 A

FA48UM

105

5

1

110 - 240 V ~ – , 415 V~

0.25 A at 110 V

FA110UM

105

5

0.5 A at 240 V 0.58 A at 277 V Switch in duration for Ue 100%

Pull-in voltage 0.7 x Ue

Undervoltage trip (60 Hz) * Module

Rated voltage

Article no.

Weight g/each

Packing unit

1

120 V

UA120UM

150

5

150

5

1

220 V

UA220UM

Pull-in voltage ≥ 0.85 x Ue

Drop out voltage 0.35 - 0.7 x Ue

Switch in duration for Ue 100 %

* without UL approval

Auxiliary contact Module

Type of contact

Contacts

Weight g/each

Article no.

Packing unit

1⁄2

1 auxiliary contact

1NO

H10UM

35

10

1⁄2

2 auxiliary contacts

1NO + 1NC

H11UM

40

10

1⁄2

3 auxiliary contacts

1NO + 2NC

H12UM

45

10

1⁄2

3 auxiliary contacts

2NO + 1NC

H21UM

45

10

24

H10UM

24

12 34

H11UM 23

22 12

H12UM 23

Standards

24

12

H21UM 33

11

34

21

33 11

23

11 according to IEC 60947-5-1, DIN EN 60947-5-1, VDE 0660-200, UL508

Rated operating currents

10 A /240 V AC 3 A / 110 V DC 1 A / 220 V DC

Minimum contact load

1 mA at 24 V DC

Conductor cross sections Type of conductor *)

min.

max.

Single wire

1.0 mm2 (AWG18)

2.5 mm2 (AWG14)

Stranded wire

1.0 mm2 (AWG18)

1.5 mm2 (AWG16)

Stranded wire with ferrule

1.0 mm2 (AWG18)

1.5 mm2 (AWG16)

Torque *) Stripped length 8 - 9 mm

54 max. 0.8 Nm (7 lb.in)

Page 55

Accessories for Switching Devices Manual Motor Controller MA according to UL508 and CSA-22.2 No.14 for Product Ranges UM and MA...UM

Lock-off/Lock-on device For miniature circuit breakers and motor protective circuit breakers

Distance device 9 mm

Module

Article no.

1/2

HDS

Weight Packing g/each unit 7

10

Article no. EASS

Weight Packing g/each unit 4

10

Various Busbars see page 40-41

55

Page 56

Switching Devices Manual Motor Controller MA

��� according to UL508 and CSA-22.2 No.14 Technical Data Product Range MA...UM

File E137938

Technical Data Standards

Short circuit withstand rating

Utilization category Group Short Circuit Ratings (UL/CSA Ratings)

UL508 and CSA-22.2 No.14

0.16 A – 2.5 A / 42 kA, 4 A – 16 A / 14 kA, 20 – 40 A / 10 kA

AC 3 at Ue 415 V~ (up to In 25 A) 1200 A / 42 kA, 350 A / 14 kA, 350 A / 10 kA

Rated voltage AC

480Y / 277 VAC

Rated current range

15 setting ranges from 0.1 up to 40 A

Rated uninterrupted current Ith

40 A

Tripping time at 6 x le

> 5s/TII

Test currents

Thermal not tripping I1 (A) > 2 h Thermal tripping I2 (A) < 2 h

1.05 x Ie

1.15 x le

Electromagnetic not tripping I4 (A) > 0.1 s for the lower setting 16 x le (12.5 x le > 16 A) for the upper setting 10 x le

Electromagnetic tripping I5 (A) < 0.1 s for the lower setting 19 x le (15 x le > 16 A) for the upper setting 12 x le

Temperature compensation Permitted ambient temperature Device depth according to DIN 43880

Mechanical endurance

Permitted operating frequency

Protection cover up to +40 °C open -20 °C to +50 °C, enclosure -20 °C to +40 °C storage/transport -40 °C to +70 °C 68 mm

30 000 switching cycles (30 000 ON / 30 000 OFF)

30 switching cycles/h

Safe for fingers and back of hand acc. to DIN EN 50274, VDE 0660-514 BGV A2

Degree of protection according to EN/IEC 60529

IP20

Installation position any

Mounting

On DIN-rail acc. to DIN EN 60715 35 mm

Lockability

The handle can be secured against manual switching in the on and off position by a lead seal

Climatic resistance

Humid heat constant according to DIN IEC 60068-2 – 78 Humid heat cyclic according to DIN EN 60068-2 – 30

Vibration resistance

> 15 g according to DIN EN 60068-2 – 59 for a load with I1

Resistance to mechanical shocks

56

25 g 11 ms

Page 57

Switching Devices Manual Motor Controller MA according to UL508 and CSA-22.2 No.14 Technical Data Product Range MA...UM

���

File E137938

Conductor cross sections

Box terminal bottom

Type of conductor *)

Box terminal top max.

min.

max.

min.

Single wire

25 mm2 (AWG3)

1.0 mm2 (AWG18)

25 mm2 (AWG3)

1.0 mm2 (AWG18)

Multiple wire

25 mm2 (AWG3)

16 mm2 (AWG6)

25 mm2 (AWG3)

16 mm2 (AWG6)

Stranded wire

16 mm2 (AWG6)

1.0 mm2 (AWG18)

25 mm2 (AWG3)

1.0 mm2 (AWG18)

Stranded wire with ferrule

16 mm2 (AWG6)

1.0 mm2 (AWG18)

16 mm2 (AWG6)

1.0 mm2 (AWG18)

Busbar Cable lug Combined, conductor and busbar or cable lug up to 3 mm thickness up to 1.5 mm thickness up to 25 mm2 and up to 2 mm thickness not possible

Torque max. 2.5 Nm (22.2 lb.in)

*) Stripped length: bottom 12 - 14 mm, top 10 - 12 mm

1.15 x In

1.15 x In 60 40

Minutes

Minutes

60 40

10 4

1

10 4

1

20 10

10

4

4

1

1 0.4 upper setting short circuit tripping at lower setting

10-1

10-1

4x10-2

4x10-2

Seconds

Seconds

0.4

10-2 4x10-3

10-3 upper setting short circuit tripping at lower setting

10-2 4x10-3

10-3 1

2

3

4

5 6

16

8 10 12

20 19

40 x Rated current

Characteristic for MA016UM – MA16UM

100

1

2

3

4

5 6 x Rated current

8 10 15 12

20

40

100

12.5

Characteristic for MA20UM – MA40UM

57

Page 58

Switching Devices Manual Motor Controller MA according to UL508 and CSA-22.2 No.14 Technical Data Product Range MA...UM

���

File E137938

Internal resistance per pole in mΩ and power loss in Watt of the complete device Type

Lower setting

Upper setting

Internal resistance per pole

A

A mΩ lower setting Watt upper setting Watt

MA016UM

0.10

0.16

85500

2.6

6.6

MA025UM

0.16

0.25

35000

2.7

6.6

MA040UM

0.25

0.40

15000

2.8

7.2

MA063UM

0.40

0.63

5200

2.5

6.2

MA1.0UM

0.63

1.0

2300

2.7

6.9

MA1.6UM

1.0

1.6

950

2.9

7.3

MA2.5UM

1.6

2.5

355

2.7

6.7

MA4.0UM

2.5

4.0

142

2.7

6.8

MA6.3UM

4.0

6.3

54

2.6

6.4

MA.10UM

6.3

10

28

3.3

8.4

MA.16UM

10

16

13.9

4.2

10.7

MA.20UM

16

20

9.9

5.2

8.2

MA.25UM

20

25

6.3

8

12.3

MA.32UM

25

32

3.85

6.4

10.5

MA.40UM

32

40

3.1

8.6

13.4

Type

Rated Current [A]

FLA Dial Adjustment Markings

MA016UM

0.16

0.1/ 0.12/0.14/0.16

MA025UM

0.25

0.16/0.19/0.22/0.25

MA040UM

0.40

0.25/0.30/0.35/0.40

MA063UM

0.63

0.40/0.48/0.56/0.63

MA1.0UM

1.00

0.63/0.75/0.87/1.0

MA1.6UM

1.60

1.0/1.2/1.4/1.6

MA2.5UM

2.50

1.6/1.9/2.2/2.5

MA4.0UM

4.00

2.5/3.0/3.5/4.0

MA6.3UM

6.30

4.0/4.8/5.6/6.3

MA10UM

10

6.3/7.5/8.7/10

MA16UM

16

10/12/14/16

MA20UM

20

16/17/18.5/20

MA25UM

25

20/21.5/23/25

MA32UM

32

25/27/30/32

MA40UM

40

32/34/37/40

Group short circuit rating at 480 VAC a) (and BCP size)

10 kARMS symmetrical (max. 350 A MCCB or RK5)

Note: HEA - Horsepower Equivalent Amperes, the nominal amperage assigned to standard motor horsepower ratings in design guide tables such as NFPA-70 Tables 430-248, 430-249, 430-250; UL1077 Table 16.2; CSA - C22.2 No. 235-M89 Tables 44 and 45; CSA-C22.2 No. 14-M91 Table 19, etc. Multiply HEA values (in parenthesis) by 1.1 if power factor is 90%, and by 1.2 if power factor is 80%.

58

3 Ø horsepower ratings at nominal line voltage (see note for HEA definition) 110 – 120 V hp (HEA)

200 V hp (HEA)

208 V hp (HEA)

220 – 240 V hp (HEA)

460 – 480 V hp (HEA)

Through MA2.5UM, ampere rated for motor circuits having a fullload-amperage (FLA) not exceeding the MA´s general purpose rated current (RC, equals maximum dial setting) and a lockedrotor current not exceeding 6 times the MA´s RC.

42 kARMS symmetrical (max. 1200 A MCCB or RK5)

14 kARMS symmetrical (max. 350 A MCCB or RK5)

Power loss for the complete device for

½ (4.0)

¾ (3.2)

¾ (3.1)

1 (3.6)

¾ (5.6)

1½ (6.0)

1½ (5.7)

1½ (5.2)

2 (3.42) 3 (4.8)

1 (7.2)

2 (7.8)

2 (7.5)

3 (9.6)

5 (7.6)

2 (13.6)

3 (11.0)

3 (10.6)

5 (15.2)

10 (14.0)

3 (19.2)

5 (17.5)

5 (16.7)

5 (15.2)

10 (14.0)

3 (19.2)

5 (17.5)

7½ (24.2)

7½ (22.0)

15 (21.0)

5 (30.4)

7½ (25.0)

7½ (24.2)

10 (28.0)

20 (27.0)

5 (30.4)

10 (32.0)

10 (31.0)

10 (28.0)

25 (34.0)

a) The standard-circuit short-circuit rating is 14 kA for all types. Group ratings can be used in a standard circuit (e.g., MA1.0UM at 42 kA), but a higher standard rating cannot be used in a group circuit (e.g., MA40UM at 14 kA only in standard circuit.)

Page 59

Switching Devices Manual Motor Controller MA

��� according to UL508 and CSA-22.2 No.14 Dimension Drawing

File E137938

59

Page 60

Switching Devices Manual Motor Controller MS Overview

Trip-indicating auxiliary contact or shunt trip or undervoltage trip

Auxiliary contact for front mounting

Auxiliary contact right and/ or left hand mounted Auxiliary contact right and/ or left hand mounted

Emergency-stop button Indicator light

Insulated flush mounting enclosure IP41 or IP55

Insulated enclosure IP41 or IP55 Padlocking facility

60