The text of a spec sheet · part 5 of 10
Switching Devices according to UL489, UL508 and UL1077, pages 41 to 50
Pages 41 to 50 of 92
The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the ABL Sursum 3B16UM
Page 41
Busbars for Manual Motor Controllers, Product Ranges UM and MA...UM
Cross section [mm2]
Busbar current Start of busbar/ Middle infeed
Modules/ Phases
Article no.
Weight g/each
Packing unit
SB16010
250
50
Suitable end cap Article no.
Busbars fork type without UL and CSA approval 1-phase 12
65/110
56/1
1-phase 1-pole switching device + auxiliary contact 24
90/150
37/1
SDO.124
200
50
63/100
28/2
SB26010
390
20
SB.A5
22/2
SB26216
310
20
SB.A2
2-phase and 1-phase + N 10
2-phase 2-pole switching device + auxiliary contact 16
80/130
3-phase 10
63/100
4/3
SB31210
84
25
SB.A1
10
63/100
19/3
SB36010
420
20
SB.A1
16
80/130
19/3
SB36016
675
20
SB.A2
SB36316
630
20
SB.A2
3-phase 3-pole switching device + auxiliary contact 16
80/130
16/3
3-phase 1-pole switching device + auxiliary contact 16
80/130
36/1
SDO.316
500
20
SB.A2
80/130
14/4
SB46016
835
15
SB.A3
SB718U
500
20
SB.A2
4-phase and 3-phase + N 16
Busbars pin type without UL and CSA approval 3-phase 16
80/130
19/3
41
Page 42
Switching Devices Manual Motor Controller according to UL508 and CSA-22.2 No.14 Technical Data Product Range UM
���
File E137938
Characteristic
Application
B
Lighting Lighting Circuits control Circuits control Wiring protection Wiring protection Business equipment Business equipment Appliances Appliances Motors low inrush
D
E
G
Z
Transformers Power supplies Reactive load Motors high inrush
Transformers Power supplies Motors high efficiency
Lighting Circuits control Wiring protection Transformers Solenoid Motors general
Wiring protection Semiconductor protection General electronics
Number of poles
1 - 3; 1 + N; 3 + N
Standards
IEC 60898-1, DIN EN 60898-1, VDE 0641-11, UL508, CSA-22.2 No.14
Short circuit withstand rating see data sheet for use in the USA, Canada and Europe (page 44)
Current limiting class
3
3
Max. back-up fuse see data sheet for use in the USA, Canada and Europe (page 44)
Rated voltage AC
277 / 480 V 1-pole 42 V and 2-poles 80 V in serial connection of both poles (up to 25 A rated current)
Rated voltage DC L/R = 4 ms Rated current range
Test currents
C
1-pole 24 V and 2-poles 60 V in serial connection of both poles (30 A - 60 A rated current) 1 - 63* A
0.3 - 63* A
0.3 - 63* A
0.3 - 63* A
0.3 - 63* A
0.3 - 50 A
Thermal not tripping I1 (A) > 1 h
1.13 x In
1.13 x In
1.13 x In
1.05 x In
1.05 x In
1.05 x In
Thermal tripping I2 (A) < 1 h
1.45 x In
1.45 x In
1.45 x In
1.35 x In
1.35 x In
1.35 x In
Electromagnetic not tripping I4 (A) > 0,1 s
3 x In
5 x In
10 x In
14 x In
8 x In
2 x In
Electromagnetic tripping I5 (A) < 0,1 s
5 x In
10 x In
16 x In
18 x In
10 x In
3 x In
Reference calibration temperature of the thermal tripping
30° C + 5° C
20° C + 5° C
Influence of the ambient temperature on the thermal release: Decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5% per 10°C difference in temperature
Frequency range of the electromagnetic trip
16 2/3 to 60 Hz With higher frequencies, the electromagnetic tripping values increase by approximately a factor of 1.1 at 100 Hz; 1.2 at 200 Hz; 1.3 at 300 Hz; 1.4 at 400 Hz; 1.5 for DC
Ambient temperature
-25 °C to +55 °C
Storage temperature
-40 °C to +70 °C
Device depth according to DIN 43880
68 mm
Mechanical life
10,000 switching cycles (ON / OFF)
Protection cover
Finger safe and safe to back of hand according to DIN EN 50274/ VDE0660-514, BGV A3
Insulation group acc. to DIN/VDE 0110
C at 250 V AC B at 400 V AC
Degree of protection acc. to EN/IEC 60529
IP20
Installation position any
Mounting
DIN-rail according to DIN EN 60715 35 mm
Lockability
The handle can be secured against manual switching in the on and off position by a lead seal
Climatic resistance
Humid heat constant according to DIN EN 60068-2-78 Humid heat cycle according to DIN EN 60068-2-30
Vibration resistance
> 15 g according to DIN EN 60068-2-59 during a load with I1
Resistance to mechanical shocks
25g 11ms * 63 A without UL approval
42
Page 43
Switching Devices Manual Motor Controller according to UL508 and CSA-22.2 No.14 Technical Data Product Range UM
���
File E137938
Conductor cross sections Box terminal bottom
Box terminal top
Type of conductor *)
max.
min.
max.
min.
Single wire
35 mm2 (AWG2)
1.0 mm2 (AWG18)
25 mm2 (AWG3)
1.0 mm2 (AWG18)
Multiple wire
35 mm2 (AWG2)
16 mm2 (AWG6)
25 mm2 (AWG3)
16 mm2 (AWG6)
Stranded wire
25 mm2 (AWG3)
1.0 mm2 (AWG18)
16 mm2 (AWG6)
1.0 mm2 (AWG18)
Stranded wire with ferrule
16 mm2 (AWG6)
1.0 mm2 (AWG18)
16 mm2 (AWG6)
1.0 mm2 (AWG18)
Busbar cable lug up to 3 mm thickness up to 1.5 mm thickness
Combined, conductor and busbar or cable lug up to 35 mm2 and up to 2 mm thickness not possible
Torque max. 2.5 Nm (22.2 lb.in)
*) Stripped length: bottom 12 - 14 mm, top 10 - 12 mm
1-pole
2-pole
3-pole
43
Page 44
Switching Devices Manual Motor Controller according to UL508 and CSA-22.2 No.14 Technical Data Product Range UM
���
File E137938
Short circuit withstand rating and maximum back-up fuse according to UL508 and CSA-22.2 No.14 Characteristic
B; C; D; E; G and Z
Standards
UL508 and CSA-22.2 No.14 Number of poles
Maximum rated voltage V
Rated current
1/1+N
277
0.3 - 10
10
70 A
1/1+N
277
12 - 60
10
4 x In
2/3/3+N
480
0.3 - 10
10
70 A
Short circuit withstand rating at rated voltage Ambient temperature 40 °C
Back-up fuse for group installations
A
Short circuit withstand rating kA
Maximum back-up fuse A
2/3/3+N
480
12 - 60
10
4 x In
1/1+N
277
0.3 - 10
10
800 A 800 A
1/1+N
277
12 - 60
5
2/3/3+N
480
0.3 - 10
10
800 A
2/3/3+N
480
12 - 60
5
800 A
Short circuit withstand rating and maximum back-up fuse according to EN and IEC Characteristic
B; C; D; E; G and Z
Standards
IEC 60947-2, DIN EN 60947-2, VDE 0660-101 B, C and D characteristic acc. to IEC 60898-1, DIN EN 60898-1, VDE 0641-11 Number of poles
Short circuit withstand rating at rated voltage
Rated current
1 /1+N
Maximum rated voltage V 277
2/3/3+N
480
A 0.3 - 60
Short circuit withstand rating kA 10
Maximum back-up fuse A 160
0.3 - 60
10
160
Internal Resistance for Product Ranges UM and UR Rated current [A]
Trip characteristic] B [Ohm]
C [Ohm]
D [Ohm]
G [Ohm]
E [Ohm]
0.3
16.8620
16.8620
16.862
14.52000
31.5060
0.5
6.8540
6.0009
6.854
5.92000
10.2460
0.75/0.8
3.0540
3.0540
3.054
2.70000
5.3920
1.0
1.7000
1.7000
1.7560
1.756
1.48000
2.6910
1.6
0.5870
0.5870
0.5870
0.587
0.57400
0.9440
2.0
0.4190
0.4190
0.4190
0.419
0.40500
0.8900
2.5
0.2950
0.2950
0.2950
0.295
0.26900
0.4290
3.0
0.2020
0.2020
0.2020
0.202
0.18600
0.3460
3.5
0.1390
0.1390
0.1390
0.139
0.13900
0.1790
4.0
0.1090
0.1090
0.1090
0.109
0.10600
0.1620
5.0
0.0654
0.0654
0.0654
0.0654
0.05900
0.1050
6.0
0.0528
0.0528
0.0491
0.0491
0.04600
0.0823
0.0278
0.0240
0.0333
0.03040
0.0371
0.0216
0.0216
0.0187
0.0211
0.02020
0.0278
0.0084
0.00724
0.0151
13
0.0113
0.0084
0.0085
0.0084
0.00724
0.0151
15/16
0.0085
0.0085
0.0076
0.0076
0.00731
0.0114
20
0.0067
0.0067
0.0064
0.0064
0.00582
0.0075
25
0.0050
0.0050
0.0041
0.0046
0.00411
0.0050
30/32
0.0032
0.0032
0.0027
0.003
0.00272
0.0032
40
0.0025
0.0025
0.0022
0.0022
0.00212
0.0022
50
0.0019
0.0019
0.0018
0.0019
0.00184
0.0020
60/63 *
0.0018
0.0018
0.0017
0.00179
0.00172, 8.0 10 12
* 63 A without UL approval
44
Z [Ohm]
Page 45
Switching Devices Manual Motor Controller according to UL508 and CSA-22.2 No.14 Technical Data Product Range UM
���
File E137938
Ampere rating and horsepower rating 1 phase FLA and LRC converted to table horsepower (see Note 2) use FLA and LRC ratings where no hp rating is given Rated current [A]
Motor nameplate
Motor nameplate
(see Note 1)
FLA rating [A]
Starting/ LCR rating [A]
0.30 0.50 0.75
0.30 0.50 0.75
1.80 3.00 4.35
0.80 1.0 1.6
0.80 1.0 1.6
4.8 6.0 9.6
2.0 2.5 3.0
2.0 2.5 3.0
12.0 15.0 18.0
3.5 4.0
3.5 4.0
21.0 24.0
5.0 6.0 8.0
5.0 6.0 8.0
30.0 36.0 48.0
1
10.0
10
60.0
1
/2
12.0 12.5
12.0 12.5
72.0 75.0
1
/2 1 /2
13.0 15.0 16.0
13.0 15.0 16.0
78.0 90.0 96.0
1
3
/2 /4 1
20.0 25.0
20.0 25.0
120.0 150.0
30.0
30.0
32.0
32.0
40.0 50.0 60.0
Nominal circuit voltage 110 – 120 VAC [hp]
200 VAC [hp]
208 VAC [hp]
1
220 – 240 VAC [hp]
265 VAC [hp]
277 VAC [hp]
1
1
/6 /6 1 /4
1
/6 1 /6
/6 /6 1 /4
1
/6 /6
1
1
1
1 1
/4 /4
1
/4 /3
1
1
1
1
1
1
1
1
1
1
/2 /2 3 /4
1
/2 /2 1
1
1
/2 /4 1
1
1
3
3
1
1
1 1/2
1 1/2
2
1 1/2 1 1/2
1 1/2 1 1/2
2 2
2 2
2 2
1 1/2 2 2
1 1/2 2 2
2 2 2
2 3 3
2 3 3
1 1/2 2
3 3
3 3
3 3
3 5
3 5
180.0
2
3
3
5
5
5
192.0
2
3
5
5
5
5
40.0
240.0
3
5
7 1/2
7 1/2
7 1/2
7 1/2
50.0 60.0
300.0 360.0
3 5
7 1/2 10
10 10
10 10
10 10
10 15
/6 /4 1 /3
1
Note 1: For AC motor circuit nameplate full load current, AC general-use loads, AC resistance loads, AC incandescent lamp (tungsten) loads, AC electric discharge lamp (ballast) loads
/3 /2 3 /4 1
/4 /3
/3 /3
/6 /4 1 /3 /3 /3
/2 /4 1
Note 2: Conversions per UL508 Table 45.2 and NFPA-70: National Electrical Code® 2008 Tables 430-248 and 430-251(A)
45
Page 46
Switching Devices Manual Motor Controller according to UL508 and CSA-22.2 No.14 Technical Data Product Range UM
���
File E137938
Ampere rating and horsepower rating 3 phase and 2 phase – 4 wire FLA and LRC ratings converted to table horsepower (see Note 2) use FLA and LRC ratings where no hp rating is listed Rated current [A] (see Note 1)
Motor nameplate
Motor nameplate
FLA rating [A]
Starting/ LCR rating [A]
Nominal circuit voltage 110 – 120 VAC Motordesign B, C, D [hp]
0.30 0.50 0.75
0.30 0.50 0.75
3.0 5.0 7.5
0.80 1.0 1.6
0.80 1.0 1.6
8.0 10.0 16.0
2.0 2.5 3.0
2.0 2.5 3.0
20.0 25.0 30.0
3.5 4.0
3.5 4.0
35.0 40.0
5.0 6.0 8.0
5.0 6.0 8.0
42.0 50.4 67.2
1
/2 /2 3 /4
10.0 12.0 12.5
10.0 12.0 12.5
84.0 100.8 105.0
13.0 15.0 16.0
13.0 15.0 16.0
20.0 25.0
20.0 25.0
30.0 32.0 40.0 50.0 60.0
208 VAC
Motordesign B, C, D [hp]
E [hp]
220 – 240 VAC
Motordesign B, C, D [hp]
E [hp]
Motordesign
440 – 480 VAC Motordesign
B, C, D [hp]
E [hp]
B, C, D [hp]
E [hp]
1
/2
1
1
3
3
/2
1
1
1
1
1
1
/2 /2
1
1
1
1
/2 /2 /2
1
1
1
/2 /2 /2
/4 1 1 1/2
/4 1 1 1/2
/2 /2
/2 /2
/2 /2
1
/2 /4
1
/2 /4
3
3
/4 /4
3
3
/4 /4
3
3
/4 /4
3
3
3
3
/4 /4
2 2
2 2
1
/2 /2 3 /4
1 1 2
1 1 2
1 1 2
1 1 2
1 1 1/2 2
1 1 1/2 2
3 3 5
3 3 5
1 1 1/2 1 1/2
1 1 1/2 1 1/2
2 3 3
2 3 3
2 3 3
2 3 3
3 3 3
3 3 3
5 7 1/2 7 1/2
5 7 1/2 7 1/2
109.2 126.0 134.4
1 1/2 2 2
1 1/2 2 2
3 3 3
3 3 3
3 3 3
3 3 3
3 3 5
3 3 5
7 1/2 10 10
7 1/2 10 10
168.0 210.0
3 3
3 3
5 5
5 5
5 7 1/2
5 7 1/2
5 7 1/2
5 7 1/2
10 15
10 15
30.0
252.0
5
5
5
5
7 1/2
7 1/2
10
10
20
20
32.0
268.8
5
5
5
5
10
10
10
10
20
20
40.0
226.0
5
5
10
7 1/2
10
7 1/2
10
10
30
20
282.5 339.0
1
1
15 15
10 10
15 20
10 10
15 20
10 15
30 40
25 30
50.0 60.0
1
7 /2 10
Note 1: For AC motor circuit nameplate full load current, AC general-use loads, AC resistance loads, AC incandescent lamp (tungsten) loads, AC electric discharge lamp (ballast)loads
46
E [hp]
200 VAC
1
7 /2 10
Note 2: Conversions per UL508 proposed Tables 45.2 and 45.4 and NFPA-70: National Electrical Code® 2008 Tables 430-249, 430-250 and 430-251B)
Page 47
Switching Devices Manual Motor Controller according to UL508 and CSA-22.2 No.14 Characteristic Product Range UM
���
File E137938
60 40
1,13-1,45 x IN
Tripping time t Minutes
Minutes
Tripping time t
10 4
4
1
10
10
4
4
1
1
0,4
0,4
C
D
B 10 -1
4x10-2
4x10-2
Seconds
10 -1
10
1,13-1,45 x I N
10
1
B
Seconds
60 40
-2
-3 4x10
10
1
-2
-3 4x10
2
3
4
5 6
8 10
16 20
40
1
100
Multiple of rated current
3
4
5 6
8 10
20
1,05-1,35 x IN
B, C and D characteristic UM
Minutes
Tripping time t
4
60 40
40
100
10
10
4
4
1
1
0,4
0,4
10 -1
10 -1
4x10-2
4x10-2
-3 4x10
1,05-1,35 x I N
4
1
-2 ln = 13 - 63* A
10
1
Seconds
Minutes Seconds ln = 0.3 - 10 A
10
10
2
Multiple of rated current
B, C and D characteristic UM
60 40
D
10 -3
10 -3
Tripping time t
C
10
-2
-3 4x10
10 -3
10 -3 1
2
3
4
5 6
8 10
20
40
Multiple of rated current
G characteristic UM ln = 0.3 - 10 A
100
1
2
3
4
5 6
8 10
20
40
100
Multiple of rated current
G characteristic UM ln = 12 - 63* A
* 63 A without UL approval
47
Page 48
Switching Devices Manual Motor Controller according to UL508 and CSA-22.2 No.14 Characteristic Product Range UM
���
File E137938
1,05-1,35 x I N
4
Tripping time t
60 40
Minutes
10
10 4
1
1
10
10
4
4
1
1
0,4
0,4
10 -1
10 -1
4x10-2
4x10-2
10
Seconds
Seconds
60 40
Minutes
1,05-1,35 x IN
Tripping time t
-2
-3 4x10
10 -3
10
-2
-3 4x10
10 -3 1
2
3
4
5 6
8 10
14
20 18
40
100
1
2
Multiple of rated current
10 ln = 0.3 - 10 A
1,05-1,35 x N I
4
Tripping time t
60 40
10
5 6
8 10 14 18 20
40
100
1
10
10
4
4
1 0,4
10 -1
10 -1
4x10-2
4x10-2
Seconds
1 0,4
-2
-3 4x10
10 -3 ln = 12 - 63* A
1,05-1,35 x I N
4
1
10
4
E characteristic UM
Minutes
60 40
Seconds
Tripping time t Minutes
E characteristic UM
3
Multiple of rated current
10
-2
-3 4x10
10 -3 1
2
3
4
5 6
8 10
15
20
40
Multiple of rated current
Z characteristic UM ln = 0.3 - 10 A
100
1
2
3
4
5 6
8 10
15
20
40
100
Multiple of rated current
Z characteristic UM ln = 12.5 - 50 A
* 63 A without UL approval
48
Page 49
ABL(¥_ )SURSUM
49
Page 50
Extensively tested for practical use – ABL SURSUM Switching Devices according to UL508 and CSA-22.2 No.14
50