The text of a spec sheet · part 3 of 10
Switching Devices according to UL489, UL508 and UL1077, pages 21 to 30
Pages 21 to 30 of 92
The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the ABL Sursum 3B16UM
Page 21
Switching Devices Listed Circuit Breakers AC according to UL489 and CSA-22.2 No. 5-09 UL Product Range, AC Version, C and D Characteristics
File E 329510
Characteristic *
Weight g/each
Packing unit
3D03UL 3D05UL 3D1Ul 3D1.6UL 3D2UL 3D3UL 3D4UL 3D5UL 3D6UL 3D8UL 3D10UL 3D12UL 3D13UL 3D15UL 3D16UL 3D20UL 3D25UL
415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
3C30UL
3D30UL
415
4
3C32UL 3C40UL 3C50UL 3C60UL 3C63UL
3D32UL 3D40UL 3D50UL 3D60UL 3D63UL
415 415 415 415 415
4 4 4 4 4
Weight g/each
Packing unit
165 165
6 6
Rated
Rated current voltage
C
D
In A
Volt AC
Article no.
Article no.
0.3 0.5 1 1.6 2 3 4 5 6 8 10 12 13 15 16 20 25
277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480
3C03UL 3C05UL 3C1UL 3C1.6UL 3C2UL 3C3UL 3C4UL 3C5UL 3C6UL 3C8UL 3C10UL 3C12UL 3C13UL 3C15UL 3C16UL 3C20UL 3C25UL
30
277/480
32 40 50 60 63
277/480 240 240 240 240
3-pole
* Also available in B and Z characteristics on request
File E 335632
Rated
Rated current voltage
In A
Volt AC
Test currents * electromagnetic not tripping I4 A tripping I5 A
Article no.
Neutral switch – for mounting instructions please consult page 9 0.3 - 32 40 - 63
277/480 240
400 630
700 1000
N32UL N63UL
* additional electromagnetic protection
21
Page 22
Switching Devices Listed Circuit Breakers DC according to UL489 and CSA-22.2 No. 5-09 DL Product Range, DC Version, C Characteristic current
Rated voltage
Characteristic C
In A
Volt DC
Article no.
125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125
1C03DL 1C05DL 1C1DL 1C1.6DL 1C2DL 1C3DL 1C4DL 1C5DL 1C6DL 1C8DL 1C10DL 1C12DL 1C13DL 1C15DL 1C16DL 1C20DL 1C25DL
Rated
File E 329510
Weight g/each
Packing unit
165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165
12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
1-pole 0.3 0.5 1 1.6 2 3 4 5 6 8 10 12 13 15 16 20 25 30
125
1C30DL
165
12
32 40 50 60 63
125 125 125 125 125
1C32DL 1C40DL 1C50DL 1C60DL 1C63DL
165 165 165 165 165
12 12 12 12 12
250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250
2C03DL 2C05DL 2C1DL 2C1.6DL 2C2DL 2C3DL 2C4DL 2C5DL 2C6DL 2C8DL 2C10DL 2C12DL 2C13DL 2C15DL 2C16DL 2C20DL 2C25DL
330 330 330 330 330 330 330 330 330 330 330 330 330 330 330 330 330
6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
2-pole 0.3 0.5 1 1.6 2 3 4 5 6 8 10 12 13 15 16 20 25 30
250
2C30DL
330
6
32 40 50 60 63
250 250 250 250 250
2C32DL 2C40DL 2C50DL 2C60DL 2C63DL
330 330 330 330 330
6 6 6 6 6
Correct polarity must be ensured when connecting the DC switching devices! 22
Page 23
Accessories for Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 for Product Ranges UL and DL
Mounting Instructions of Accessories Switching device
Neutral switch/ Shunt trip
Neutral switch/ Shunt trip
Switching device
Auxiliary contact
Auxiliary contact
5.
3. 4.
6. Mounting screw 34 mm (see accessories page 25)
7mm
1.
4. 3.
90°
1.
6.
24 mm
2.
Applies to N...UL and FA...UL: The accessory devices N...UL and FA...UL can be mounted on the right or left. The auxiliary contact H...UL can only be mounted on the right.
2.
Mounting: 1. Bring the blue knobs of all devices into the “OFF” position 2. Remove grey cover from the switching device and attachment 3. Insert drive plate between the switching device and N...UL or FA...UL 4. Insert connecting pin into the knob (insertion depth approx. 7 mm) 5. Combine switching device and N...UL or FA...UL 6. Screw devices together (observe correct screw length)
Applies to H...UL: The auxiliary contact H...UL can only be mounted on the right. Mounting: 1. Bring the blue knobs of both devices into the “OFF” position 2. Remove grey cover from the switching device 3. Combine switching device and H...UL 4. Insert connection screws and connect the two devices by turning the screws by 90° 5. After mounting close and open to check operation
Applies to all switching devices ...UL, ...DL, N32UL, N63UL and FA...UL: The load and mains can be connected either from the top or the bottom (Line/Load Reversible).
Box terminal for • solid conductors • flexible conductors with or without cable lug
Screw terminal for forked cable lug
Screw terminal for ring cable lug (ring tongue)
• Ring cable lugs can be connected by opening the flap and removing the connecting screw • Can also be used for applications that require ring cable lugs (e.g. nuclear power stations)
• Protection against contact with live parts according to DIN EN 50274, VDE 0660-514 is fully guaranteed
Design of the terminals • Optical detection of the screw position • Increased break resistance if the screwdriver becomes jammed • Universal connecting terminals, suitable for connecting all known cable lugs such as ring or forked cable lugs and pin terminals
23
Page 24
Accessories for Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 for Product Ranges UL and DL File E 335632
Auxiliary contact, for mounting on the right Module
Type of contact
Contacts
Article no.
Weight g/each
Packing unit
1/2
1 auxiliary contact
1NO
H10UL
35
6
1/2
2 auxiliary contacts
1NO + 1NC
H11UL
40
6
1/2
3 auxiliary contacts
1NO + 2NC
H12UL
45
6
1/2
3 auxiliary contacts
2NO + 1NC
H21UL
45
6
24
12
24
H10UL
34
H11UL
34
H12UL 11
24
12
H21UL 33
23
23
22 12
21
33 11
Standards
23
11
UL489 and CSA-22.2 Nr. 5-09 10 A /240 V AC 3 A / 110 V DC 1 A / 220 V DC 1 mA at 24 V DC
Rated operating currents Minimum contact load Conductor cross sections Type of conductor *)
min.
max.
Single wire
1.0 mm2 (AWG18)
2.5 mm2 (AWG14)
Stranded wire
1.0 mm2 (AWG18)
1.5 mm2 (AWG16)
Stranded wire with ferrule
1.0 mm2 (AWG18)
1.5 mm2 (AWG16)
Torque max. 0.8 Nm (7 lb.in)
*) Stripped length 8 - 9 mm
( ) values in brackets = measurement units for North America
Shunt trip, for mounting on the right or left Rated operating voltage max. operating current at Un (t < 10 ms)
Article no.
Weight g/each
Packing unit
1
12 V UC
1.3 A
FA12UL
110
5
1
24 V UC
0.6 A
FA24UL
110
5
1
48 - 72 V UC
0.2 A
FA48UL
110
5
1
110 - 240 V UC, 277 V AC
0.25 A at 110 V
FA110UL
110
5
Module
0.5 A at 240 V 0.58 A at 277 V
Dimension drawings FA...UL, N32UL and N63UL
Lock-off/Lock-on device
24
Article no.
Weight g/each
Packing unit
EASS
2
10
Page 25
Accessories for Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 for Product Ranges UL and DL
Mounting screw 34 mm to connect the auxiliary contact and shunt trip or neutral switch to the switching devices
Touch-protection caps to cover the connecting screws on the switching devices, neutral switches and shunt trips for increased touch protection
Packing unit: 10 pieces Article no. E983419
Packing unit: 100 pieces Article no. BS.UL
Busbars pin type
Cross section [mm2]
Busbar current
Number of poles
Article no.
Weight g/each
Packing unit
1-phase 16
115
6
S106U
58
1
16
115
12
S112U
115
1
16
115
6
S206U
67
1
16
115
12
S216U
132
1
16
115
6
S306U
72
1
16
115
12
S316U
140
1
AK35U
33
3
S3BRU
5
5
2-phase
3-phase
Power feed terminals 6 - 35
115
Protection cover for busbars
Busbars cannot be cut to length!
®
25
Page 26
Switching Devices Listed Circuit Breakers AC according to UL489 and CSA-22.2 No. 5-09 Technical Data Product Range UL File E 329510
Characteristic *
C
D
Application
Lighting Wiring protection Control circuits Business equipment Appliances Motors low inrush
Transformers Power supplies Heaters Motors high inrush Reactive load
Number of poles
1 - 3; 1 + N; 3 + N
Standards
UL489 and CSA-22.2 Nr. 5-09
Short circuit withstand rating
10 kA
Back-up fuse ≤ 10 kA short circuit withstand rating none
Rated voltage AC 50/60 Hz 0.3 - 32 A
277 / 480 V
Rated voltage AC 50/60 Hz 40 - 63 A
240 V
Test currents
Rated current range
0.3 - 63 A
0.3 - 63 A
Thermal not tripping I1 (A) > 1 h
1.05 x In
1.05 x In
Thermal tripping I2 (A) < 1 h
1.35 x In
1.35 x In
Electromagnetic not tripping I4 (A) > 0.1 s
5 x In
10 x In
Electromagnetic tripping I5 (A) < 0.1 s
10 x In
16 x In
Reference calibration temperature of the thermal tripping
40 °C Influence of the ambient temperature on the thermal release: Decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5 % per 10 °C difference in temperature
Frequency range of the electromagnetic trip
16 2/3 to 60 Hz With higher frequencies, the electromagnetic tripping values increase by approximately a factor of 1.1 at 100 Hz; 1.2 at 200 Hz; 1.3 at 300 Hz; 1.4 at 400 Hz; 1.5 for DC
Ambient temperature
-25 °C to +55 °C
Storage temperature
-40 °C to +70 °C
Device depth according to DIN 43880
68 mm
Mechanical life
10,000 switching cycles (ON / OFF)
Protection cover
Finger safe and safe to back of hand according to DIN EN 50274, VDE 0660-514
Degree of protection acc. EN / IEC 60529
IP20
Installation position any
Mounting
DIN-rail according to DIN EN 60715 35 mm
Lockability
The handle can be secured against manual switching in the on and off position by a lead seal
Climatic resistance
Humid heat constant according to DIN EN 60068-2-78 Humid heat cycle according to DIN EN 60068-2-30
Vibration resistance
> 15 g according to DIN EN 60068-2-59 during a load with I1
Resistance to mechanical shocks
25 g 11 ms
* Other switching devices in B and Z characteristics available on request
26
Page 27
Switching Devices Listed Circuit Breakers DC according to UL489 and CSA-22.2 No. 5-09 Technical Data Product Range DL File E 329510
C
Application
Lighting Wiring protection Control circuits Business equipment Appliances Motors low inrush
Number of poles
1 and 2
Standards
UL489 and CSA-22.2 Nr. 5-09
Short circuit withstand rating
10 kA
Back-up fuse ≤ 10 kA short circuit withstand rating none
Rated voltage DC 1-pole
125 V
Rated voltage DC 2-pole
250 V
Rated current range
0.3 - 63 A
Test currents
Characteristic
Thermal not tripping I1 (A) > 1 h
1.05 x In
Thermal tripping I2 (A) < 1 h
1.35 x In
Electromagnetic not tripping I4 (A) > 0.1 s
7 x In
Electromagnetic tripping I5 (A) < 0.1 s
14 x In
Reference calibration temperature of the thermal tripping
40 °C Influence of the ambient temperature on the thermal release: Decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5 % per 10 °C difference in temperature
Ambient temperature
-25 °C to +55 °C
Storage temperature
-40 °C to +70 °C
Device depth according to DIN 43880
68 mm
Mechanical life
10,000 switching cycles (ON / OFF)
Protection cover
Finger safe and safe to back of hand according to DIN EN 50274, VDE 0660-514 BGV A3
Degree of protection acc. EN / IEC 60529
IP20
Installation position any
Mounting
DIN-rail according to DIN EN 60715 35 mm
Lockability
The handle can be secured against manual switching in the on and off position by a lead seal
Climatic resistance
Humid heat constant according to DIN EN 60068-2-78 Humid heat cycle according to DIN EN 60068-2-30
Vibration resistance
> 15 g according to DIN EN 60068-2-59 during a load with I1
Resistance to mechanical shocks
25 g 11 ms
27
Page 28
Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 Technical Data Product Ranges UL and DL File E 329510
Dimension drawings product ranges UL and DL
1-pole
28
2-pole
3-pole
Page 29
Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 Technical Data File E 329510
Conductor cross sections Box terminal bottom
Box terminal top
Type of conductor *)
max.
min.
max.
min.
Single wire
35 mm2 (AWG2)
1.0 mm2 (AWG18)
25 mm2 (AWG3)
1.0 mm2 (AWG18)
Multiple wire
35 mm2 (AWG2)
16 mm2 (AWG6)
25 mm2 (AWG3)
16 mm2 (AWG6)
Stranded wire
25 mm2 (AWG3)
1.0 mm2 (AWG18)
16 mm2 (AWG6)
1.0 mm2 (AWG18)
Stranded wire with ferrule
16 mm2 (AWG6)
1.0 mm2 (AWG18)
16 mm2 (AWG6)
1.0 mm2 (AWG18)
Busbar cable lug up to 3 mm thickness up to 1.5 mm thickness
Combined, conductor and busbar or cable lug up to 35 mm2 and up to 2 mm thickness not possible
Torque max. 2.5 Nm (22.2 lb.in)
*) Stripped lengths: 12 - 14 mm at the bottom, 10 - 12 mm at the top ( ) values in brackets = measurement units for North America Copper conductor with sheath insulation for 60/75 °C
Internal Resistance for Product Ranges UL and DL Rated current [A]
Trip characteristic C [Ohm]
D [Ohm]
0.3
16.8620
16.8620
0.5
6.8540
6.0009
1.0
1.7000
1.7560
1.6
0.5870
0.5870
2.0
0.4190
0.4190
3.0
0.2020
0.2020
4.0
0.1090
0.1090
5.0
0.0654
0.0654
6.0
0.0528
0.0491
8.0
0.0278
0.0240
10
0.0216
0.0187
12
0.0084
0.0085
13
0.0084
0.0085
15/16
0.0085
0.0076
20
0.0067
0.0064
25
0.0050
0.0041
30/32
0.0032
0.0027
40
0.0025
0.0022
50
0.0019
0.0018
60/63
0.0018
0.0017
29
Page 30
Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 Characteristic Product Ranges UL and DL File E 329510
1,05-1,35xIN
Product Range UL
60 40
10
1,05-1,35xIN
10 4
1
1
10
10
4
4
1
1
0,4
0,4
D
C 10 -1
4x10 -2
4x10 -2
Seconds
10 -1
10 -2 4x10 -3
10 -3
4x10 -3
1
2
3
4 5 6
8 10
16 20
40
10 -3
100
1
2
Tripping time t Minutes
60 40
10
8 10
16 20
40
100
Product Range DL
1,05-1,35xIN
10 4
1
1
10
10
4
4
1
1
0,4
0,4
10 -1
10 -1
4x10 -2
4x10 -2
10 -2 ln = 12 - 63 A
60 40
4
10 -2 4x10 -3
4x10 -3
1
2
3
4 5 6 7 8 10 1 4
20
40
100
Multiple of rated current
C characteristic DC UL
30
4 5 6
C and D characteristic AC UL
Seconds
Minutes Seconds ln = 0,3 - 10 A
Product Range DL
1,05-1,35xIN
3
Multiple of rated current
C and D characteristic AC UL
10 -3
D
10 -2
Multiple of rated current
Tripping time t
Product Range UL
60 40
4
C
Seconds
Tripping time t Minutes
Minutes
Tripping time t
10 -3
1
2
3
4 5 6 7 8 10 14
20
40
100
Multiple of rated current ln = 0,3 - 10 A
C characteristic DC UL ln = 12 - 63 A