For the ABL Sursum 3B16UM

Page 21

Switching Devices Listed Circuit Breakers AC according to UL489 and CSA-22.2 No. 5-09 UL Product Range, AC Version, C and D Characteristics

File E 329510

Characteristic *

Weight g/each

Packing unit

3D03UL 3D05UL 3D1Ul 3D1.6UL 3D2UL 3D3UL 3D4UL 3D5UL 3D6UL 3D8UL 3D10UL 3D12UL 3D13UL 3D15UL 3D16UL 3D20UL 3D25UL

415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415 415

4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

3C30UL

3D30UL

415

4

3C32UL 3C40UL 3C50UL 3C60UL 3C63UL

3D32UL 3D40UL 3D50UL 3D60UL 3D63UL

415 415 415 415 415

4 4 4 4 4

Weight g/each

Packing unit

165 165

6 6

Rated

Rated current voltage

C

D

In A

Volt AC

Article no.

Article no.

0.3 0.5 1 1.6 2 3 4 5 6 8 10 12 13 15 16 20 25

277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480 277/480

3C03UL 3C05UL 3C1UL 3C1.6UL 3C2UL 3C3UL 3C4UL 3C5UL 3C6UL 3C8UL 3C10UL 3C12UL 3C13UL 3C15UL 3C16UL 3C20UL 3C25UL

30

277/480

32 40 50 60 63

277/480 240 240 240 240

3-pole

* Also available in B and Z characteristics on request

File E 335632

Rated

Rated current voltage

In A

Volt AC

Test currents * electromagnetic not tripping I4 A tripping I5 A

Article no.

Neutral switch – for mounting instructions please consult page 9 0.3 - 32 40 - 63

277/480 240

400 630

700 1000

N32UL N63UL

* additional electromagnetic protection

21

Page 22

Switching Devices Listed Circuit Breakers DC according to UL489 and CSA-22.2 No. 5-09 DL Product Range, DC Version, C Characteristic current

Rated voltage

Characteristic C

In A

Volt DC

Article no.

125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125

1C03DL 1C05DL 1C1DL 1C1.6DL 1C2DL 1C3DL 1C4DL 1C5DL 1C6DL 1C8DL 1C10DL 1C12DL 1C13DL 1C15DL 1C16DL 1C20DL 1C25DL

Rated

File E 329510

Weight g/each

Packing unit

165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165 165

12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12

1-pole 0.3 0.5 1 1.6 2 3 4 5 6 8 10 12 13 15 16 20 25 30

125

1C30DL

165

12

32 40 50 60 63

125 125 125 125 125

1C32DL 1C40DL 1C50DL 1C60DL 1C63DL

165 165 165 165 165

12 12 12 12 12

250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250

2C03DL 2C05DL 2C1DL 2C1.6DL 2C2DL 2C3DL 2C4DL 2C5DL 2C6DL 2C8DL 2C10DL 2C12DL 2C13DL 2C15DL 2C16DL 2C20DL 2C25DL

330 330 330 330 330 330 330 330 330 330 330 330 330 330 330 330 330

6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

2-pole 0.3 0.5 1 1.6 2 3 4 5 6 8 10 12 13 15 16 20 25 30

250

2C30DL

330

6

32 40 50 60 63

250 250 250 250 250

2C32DL 2C40DL 2C50DL 2C60DL 2C63DL

330 330 330 330 330

6 6 6 6 6

Correct polarity must be ensured when connecting the DC switching devices! 22

Page 23

Accessories for Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 for Product Ranges UL and DL

Mounting Instructions of Accessories Switching device

Neutral switch/ Shunt trip

Neutral switch/ Shunt trip

Switching device

Auxiliary contact

Auxiliary contact

5.

3. 4.

6. Mounting screw 34 mm (see accessories page 25)

7mm

1.

4. 3.

90°

1.

6.

24 mm

2.

Applies to N...UL and FA...UL: The accessory devices N...UL and FA...UL can be mounted on the right or left. The auxiliary contact H...UL can only be mounted on the right.

2.

Mounting: 1. Bring the blue knobs of all devices into the “OFF” position 2. Remove grey cover from the switching device and attachment 3. Insert drive plate between the switching device and N...UL or FA...UL 4. Insert connecting pin into the knob (insertion depth approx. 7 mm) 5. Combine switching device and N...UL or FA...UL 6. Screw devices together (observe correct screw length)

Applies to H...UL: The auxiliary contact H...UL can only be mounted on the right. Mounting: 1. Bring the blue knobs of both devices into the “OFF” position 2. Remove grey cover from the switching device 3. Combine switching device and H...UL 4. Insert connection screws and connect the two devices by turning the screws by 90° 5. After mounting close and open to check operation

Applies to all switching devices ...UL, ...DL, N32UL, N63UL and FA...UL: The load and mains can be connected either from the top or the bottom (Line/Load Reversible).

Box terminal for • solid conductors • flexible conductors with or without cable lug

Screw terminal for forked cable lug

Screw terminal for ring cable lug (ring tongue)

• Ring cable lugs can be connected by opening the flap and removing the connecting screw • Can also be used for applications that require ring cable lugs (e.g. nuclear power stations)

• Protection against contact with live parts according to DIN EN 50274, VDE 0660-514 is fully guaranteed

Design of the terminals • Optical detection of the screw position • Increased break resistance if the screwdriver becomes jammed • Universal connecting terminals, suitable for connecting all known cable lugs such as ring or forked cable lugs and pin terminals

23

Page 24

Accessories for Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 for Product Ranges UL and DL File E 335632

Auxiliary contact, for mounting on the right Module

Type of contact

Contacts

Article no.

Weight g/each

Packing unit

1/2

1 auxiliary contact

1NO

H10UL

35

6

1/2

2 auxiliary contacts

1NO + 1NC

H11UL

40

6

1/2

3 auxiliary contacts

1NO + 2NC

H12UL

45

6

1/2

3 auxiliary contacts

2NO + 1NC

H21UL

45

6

24

12

24

H10UL

34

H11UL

34

H12UL 11

24

12

H21UL 33

23

23

22 12

21

33 11

Standards

23

11

UL489 and CSA-22.2 Nr. 5-09 10 A /240 V AC 3 A / 110 V DC 1 A / 220 V DC 1 mA at 24 V DC

Rated operating currents Minimum contact load Conductor cross sections Type of conductor *)

min.

max.

Single wire

1.0 mm2 (AWG18)

2.5 mm2 (AWG14)

Stranded wire

1.0 mm2 (AWG18)

1.5 mm2 (AWG16)

Stranded wire with ferrule

1.0 mm2 (AWG18)

1.5 mm2 (AWG16)

Torque max. 0.8 Nm (7 lb.in)

*) Stripped length 8 - 9 mm

( ) values in brackets = measurement units for North America

Shunt trip, for mounting on the right or left Rated operating voltage max. operating current at Un (t < 10 ms)

Article no.

Weight g/each

Packing unit

1

12 V UC

1.3 A

FA12UL

110

5

1

24 V UC

0.6 A

FA24UL

110

5

1

48 - 72 V UC

0.2 A

FA48UL

110

5

1

110 - 240 V UC, 277 V AC

0.25 A at 110 V

FA110UL

110

5

Module

0.5 A at 240 V 0.58 A at 277 V

Dimension drawings FA...UL, N32UL and N63UL

Lock-off/Lock-on device

24

Article no.

Weight g/each

Packing unit

EASS

2

10

Page 25

Accessories for Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 for Product Ranges UL and DL

Mounting screw 34 mm to connect the auxiliary contact and shunt trip or neutral switch to the switching devices

Touch-protection caps to cover the connecting screws on the switching devices, neutral switches and shunt trips for increased touch protection

Packing unit: 10 pieces Article no. E983419

Packing unit: 100 pieces Article no. BS.UL

Busbars pin type

Cross section [mm2]

Busbar current

Number of poles

Article no.

Weight g/each

Packing unit

1-phase 16

115

6

S106U

58

1

16

115

12

S112U

115

1

16

115

6

S206U

67

1

16

115

12

S216U

132

1

16

115

6

S306U

72

1

16

115

12

S316U

140

1

AK35U

33

3

S3BRU

5

5

2-phase

3-phase

Power feed terminals 6 - 35

115

Protection cover for busbars

Busbars cannot be cut to length!

®

25

Page 26

Switching Devices Listed Circuit Breakers AC according to UL489 and CSA-22.2 No. 5-09 Technical Data Product Range UL File E 329510

Characteristic *

C

D

Application

Lighting Wiring protection Control circuits Business equipment Appliances Motors low inrush

Transformers Power supplies Heaters Motors high inrush Reactive load

Number of poles

1 - 3; 1 + N; 3 + N

Standards

UL489 and CSA-22.2 Nr. 5-09

Short circuit withstand rating

10 kA

Back-up fuse ≤ 10 kA short circuit withstand rating none

Rated voltage AC 50/60 Hz 0.3 - 32 A

277 / 480 V

Rated voltage AC 50/60 Hz 40 - 63 A

240 V

Test currents

Rated current range

0.3 - 63 A

0.3 - 63 A

Thermal not tripping I1 (A) > 1 h

1.05 x In

1.05 x In

Thermal tripping I2 (A) < 1 h

1.35 x In

1.35 x In

Electromagnetic not tripping I4 (A) > 0.1 s

5 x In

10 x In

Electromagnetic tripping I5 (A) < 0.1 s

10 x In

16 x In

Reference calibration temperature of the thermal tripping

40 °C Influence of the ambient temperature on the thermal release: Decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5 % per 10 °C difference in temperature

Frequency range of the electromagnetic trip

16 2/3 to 60 Hz With higher frequencies, the electromagnetic tripping values increase by approximately a factor of 1.1 at 100 Hz; 1.2 at 200 Hz; 1.3 at 300 Hz; 1.4 at 400 Hz; 1.5 for DC

Ambient temperature

-25 °C to +55 °C

Storage temperature

-40 °C to +70 °C

Device depth according to DIN 43880

68 mm

Mechanical life

10,000 switching cycles (ON / OFF)

Protection cover

Finger safe and safe to back of hand according to DIN EN 50274, VDE 0660-514

Degree of protection acc. EN / IEC 60529

IP20

Installation position any

Mounting

DIN-rail according to DIN EN 60715 35 mm

Lockability

The handle can be secured against manual switching in the on and off position by a lead seal

Climatic resistance

Humid heat constant according to DIN EN 60068-2-78 Humid heat cycle according to DIN EN 60068-2-30

Vibration resistance

> 15 g according to DIN EN 60068-2-59 during a load with I1

Resistance to mechanical shocks

25 g 11 ms

* Other switching devices in B and Z characteristics available on request

26

Page 27

Switching Devices Listed Circuit Breakers DC according to UL489 and CSA-22.2 No. 5-09 Technical Data Product Range DL File E 329510

C

Application

Lighting Wiring protection Control circuits Business equipment Appliances Motors low inrush

Number of poles

1 and 2

Standards

UL489 and CSA-22.2 Nr. 5-09

Short circuit withstand rating

10 kA

Back-up fuse ≤ 10 kA short circuit withstand rating none

Rated voltage DC 1-pole

125 V

Rated voltage DC 2-pole

250 V

Rated current range

0.3 - 63 A

Test currents

Characteristic

Thermal not tripping I1 (A) > 1 h

1.05 x In

Thermal tripping I2 (A) < 1 h

1.35 x In

Electromagnetic not tripping I4 (A) > 0.1 s

7 x In

Electromagnetic tripping I5 (A) < 0.1 s

14 x In

Reference calibration temperature of the thermal tripping

40 °C Influence of the ambient temperature on the thermal release: Decrease of the current values with higher ambient temperature and increase with lower temperatures of approximately 5 % per 10 °C difference in temperature

Ambient temperature

-25 °C to +55 °C

Storage temperature

-40 °C to +70 °C

Device depth according to DIN 43880

68 mm

Mechanical life

10,000 switching cycles (ON / OFF)

Protection cover

Finger safe and safe to back of hand according to DIN EN 50274, VDE 0660-514 BGV A3

Degree of protection acc. EN / IEC 60529

IP20

Installation position any

Mounting

DIN-rail according to DIN EN 60715 35 mm

Lockability

The handle can be secured against manual switching in the on and off position by a lead seal

Climatic resistance

Humid heat constant according to DIN EN 60068-2-78 Humid heat cycle according to DIN EN 60068-2-30

Vibration resistance

> 15 g according to DIN EN 60068-2-59 during a load with I1

Resistance to mechanical shocks

25 g 11 ms

27

Page 28

Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 Technical Data Product Ranges UL and DL File E 329510

Dimension drawings product ranges UL and DL

1-pole

28

2-pole

3-pole

Page 29

Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 Technical Data File E 329510

Conductor cross sections Box terminal bottom

Box terminal top

Type of conductor *)

max.

min.

max.

min.

Single wire

35 mm2 (AWG2)

1.0 mm2 (AWG18)

25 mm2 (AWG3)

1.0 mm2 (AWG18)

Multiple wire

35 mm2 (AWG2)

16 mm2 (AWG6)

25 mm2 (AWG3)

16 mm2 (AWG6)

Stranded wire

25 mm2 (AWG3)

1.0 mm2 (AWG18)

16 mm2 (AWG6)

1.0 mm2 (AWG18)

Stranded wire with ferrule

16 mm2 (AWG6)

1.0 mm2 (AWG18)

16 mm2 (AWG6)

1.0 mm2 (AWG18)

Busbar cable lug up to 3 mm thickness up to 1.5 mm thickness

Combined, conductor and busbar or cable lug up to 35 mm2 and up to 2 mm thickness not possible

Torque max. 2.5 Nm (22.2 lb.in)

*) Stripped lengths: 12 - 14 mm at the bottom, 10 - 12 mm at the top ( ) values in brackets = measurement units for North America Copper conductor with sheath insulation for 60/75 °C

Internal Resistance for Product Ranges UL and DL Rated current [A]

Trip characteristic C [Ohm]

D [Ohm]

0.3

16.8620

16.8620

0.5

6.8540

6.0009

1.0

1.7000

1.7560

1.6

0.5870

0.5870

2.0

0.4190

0.4190

3.0

0.2020

0.2020

4.0

0.1090

0.1090

5.0

0.0654

0.0654

6.0

0.0528

0.0491

8.0

0.0278

0.0240

10

0.0216

0.0187

12

0.0084

0.0085

13

0.0084

0.0085

15/16

0.0085

0.0076

20

0.0067

0.0064

25

0.0050

0.0041

30/32

0.0032

0.0027

40

0.0025

0.0022

50

0.0019

0.0018

60/63

0.0018

0.0017

29

Page 30

Switching Devices Listed Circuit Breakers according to UL489 and CSA-22.2 No. 5-09 Characteristic Product Ranges UL and DL File E 329510

1,05-1,35xIN

Product Range UL

60 40

10

1,05-1,35xIN

10 4

1

1

10

10

4

4

1

1

0,4

0,4

D

C 10 -1

4x10 -2

4x10 -2

Seconds

10 -1

10 -2 4x10 -3

10 -3

4x10 -3

1

2

3

4 5 6

8 10

16 20

40

10 -3

100

1

2

Tripping time t Minutes

60 40

10

8 10

16 20

40

100

Product Range DL

1,05-1,35xIN

10 4

1

1

10

10

4

4

1

1

0,4

0,4

10 -1

10 -1

4x10 -2

4x10 -2

10 -2 ln = 12 - 63 A

60 40

4

10 -2 4x10 -3

4x10 -3

1

2

3

4 5 6 7 8 10 1 4

20

40

100

Multiple of rated current

C characteristic DC UL

30

4 5 6

C and D characteristic AC UL

Seconds

Minutes Seconds ln = 0,3 - 10 A

Product Range DL

1,05-1,35xIN

3

Multiple of rated current

C and D characteristic AC UL

10 -3

D

10 -2

Multiple of rated current

Tripping time t

Product Range UL

60 40

4

C

Seconds

Tripping time t Minutes

Minutes

Tripping time t

10 -3

1

2

3

4 5 6 7 8 10 14

20

40

100

Multiple of rated current ln = 0,3 - 10 A

C characteristic DC UL ln = 12 - 63 A