The text of a manual · part 7 of 30
Total Access 850 System Manual: Network Turnup Procedure
Pages 55 to 64 of 292, from Total Access 850 System Manual
The original document is the PDF (3.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Adtran 1200375L1
Page 55
NETWORK TURNUP PROCEDURE This section provides shipment contents list, grounding instructions, mounting options, and specifics of supplying power to the unit.
CONTENTS
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Unpack and Inspect the SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Contents of ADTRAN Shipments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Telecommunications Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Grounding Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Supplying Power to the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 AC Powered Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 DC Powered Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Making Alternate Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Required Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Wallmounting the Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Installing Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Instructions for Installing the Power Supply Unit (P/N 1175006L2) . . . . . . . . . . . . . . . . . . . . . . . 61 Instructions for Installing the Total Access 850 Controller and Access Modules . . . . . . . . . . . . . 62 Module Shipping Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Quad FXO Access Module (P/N 1175407L2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Quad FXS Access Module (P/N 1175408L2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 UBR1TE Access Module (P/N 1180020L1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 OCU DP Access Module (P/N 1180005L1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 E&M/TO Access Module (P/N 1180402L1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Dual V.35 Access Module (P/N 1180025L1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 DSX-1 Module (P/N 1200385L1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
FIGURES Total Access 850 Slot Designation (Front View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
TABLES Table 1. Table 2.
Total Access 850 System Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Power Supply Unit Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
64203376L1-1B
© 2004 ADTRAN, Inc.
55
Page 56
Section 3 Network Turnup Procedure
1.
Total Access 850 System Manual
INTRODUCTION
This section discusses Total Access 850 installation.
2.
TOOLS REQUIRED
The tools required for wallmount installation of the Total Access 850 shelf are: • Four #8 x 3/4 inch pan-head wood screws • Drill and drill bit set • Flat head screwdriver (medium) • Two Phillips head screwdrivers (small/medium) • Wire-wrap gun (optional) • 5-pair male amphenol cable (customer connection) •
Selected punch-down block and tool To prevent electrical shock, do not install equipment in a wet location or during a lightning storm.
During installation, power should be the last connection made.
Electronic modules can be damaged by static electrical discharge. Before handling modules, put on an antistatic discharge wrist strap to prevent damage to electronic components. Place modules in antistatic packing material when transporting or storing. When working on modules, always place them on an approved antistatic mat that is electrically grounded.
3.
UNPACK AND INSPECT THE SYSTEM
Each Total Access 850 is shipped in its own cardboard shipping carton. Open each carton carefully and avoid deep penetration into the carton with sharp objects. After unpacking the unit, inspect it for possible shipping damage. If the equipment has been damaged in transit, immediately file a claim with the carrier, and then contact ADTRAN Customer Service (see Customer Service, Product Support Information, and Training in the front of this manual).
56
© 2004 ADTRAN, Inc.
64203376L1-1B
Page 57
Total Access 850 System Manual
Section 3 Network Turnup Procedure
Contents of ADTRAN Shipments Your ADTRAN shipment of the Total Access 850 chassis includes the following items: • The Total Access 850 Base Unit • The Total Access 850 Series System CD • Wallmount brackets and screws • RJ-45 to RJ-45 8-pin cable (15 ft) - ADTRAN P/N 3125M008 • UL 1950 Notice Card - ADTRAN P/N 61200375L1-17
Customer must supply Ethernet cable and the DB-9 serial cable for configuration via the VT100 CRAFT interfaces.
4.
TELECOMMUNICATIONS CODES
The installation configurations codes are given below. Table 1. Total Access 850 System Codes CODE
IN
OUT
PC
F
C
IC
E
–
TC
X
X
Table 2. Power Supply Unit Codes
5.
CODE
IN
OUT
PC
F
C
IC
E
–
TC
A
–
GROUNDING INSTRUCTIONS
To following paragraphs provide grounding instruction information from the Underwriters’ Laboratory UL1950 Standard for Safety of Information Technology Equipment Including Electrical Business Equipment, of July 28, 1995. An equipment grounding conductor that is not smaller in size than the ungrounded branch-circuit supply conductors is to be installed as part of the circuit that supplies the product or system. Bare, covered, or insulated grounding conductors are acceptable. Individually covered or insulated equipment grounding conductors shall have a continuous outer finish that is either green, or green with one or more yellow stripes. The equipment grounding conductor is to be connected to ground at the service equipment. The attachment-plug receptacles in the vicinity of the product or system are all to be of a grounding type,
64203376L1-1B
© 2004 ADTRAN, Inc.
57
Page 58
Section 3 Network Turnup Procedure
Total Access 850 System Manual and the equipment grounding conductors serving these receptacles are to be connected to earth ground at the service equipment. A supplementary equipment grounding conductor shall be installed between the product or system and ground that is in addition to the equipment grounding conductor in the power supply cord. The supplementary equipment grounding conductor shall not be smaller in size than the ungrounded branch-circuit supply conductors. The supplementary equipment grounding conductor shall be connected to the product at the terminal provided, and shall be connected to ground in a manner that will retain the ground connection when the product is unplugged from the receptacle. The connection to ground of the supplementary equipment grounding conductor shall be in compliance with the rules for terminating bonding jumpers at Part K or Article 250 of the National Electrical Code, ANSI/NFPA 70. Termination of the supplementary equipment grounding conductor is permitted to be made to building steel, to a metal electrical raceway system, or to any grounded item that is permanently and reliably connected to the electrical service equipment ground. The supplemental grounding conductor shall be connected to the equipment using a number 8 ring terminal and should be fastened to the grounding lug provided on the rear panel of the equipment. The ring terminal should be installed using the appropriate crimping tool (AMP P/N 59250 T-EAD Crimping Tool or equivalent.)
6.
SUPPLYING POWER TO THE UNIT The Total Access 850 has two power connection points. In all cases, only one of the connection points is used. Adhere to the alternate connection instructions to ensure correct installation.
On the Total Access 850 chassis, the incoming power termination point is on either of two backplane connections, P6 or P7 (see Power Connections (P6 and P7) on page 39). Both sources connect directly to the PSU. Connector P6 is used when the chassis is powered by an approved ADTRAN AC/DC Power Supply and Battery Charger (for example, P/N 1175043Lx) which mounts directly to the chassis. Connector P7 is used when -48 VDC is available on site and screw-type terminal connections are required.
AC Powered Systems As shipped, the Total Access 850 is set to factory default conditions. After installing the chassis and any access modules, the Total Access 850 is ready for power-up. To power-up the unit, ensure that the unit is properly connected to an appropriate power source. •
•
• • •
58
This unit shall be installed in accordance with Article 400 and 364.8 of the NEC NFPA 70 when installed outside of a Restricted Access Location (i.e., central office, behind a locked door, service personnel only area). To comply with GR-1089-CORE, Issue 3, this equipment MUST only be installed in a DC-C bonding and grounding environment. It may not be utilized in a DC-I (isolated) bonding and grounding environment. Power to the Total Access 850 AC system must be from a grounded 90-130 VAC, 50/60 Hz source. Verify the power receptacle uses double-pole, neutral fusing. Maximum recommended ambient operating temperature is 45 ºC.
© 2004 ADTRAN, Inc.
64203376L1-1B
Page 59
Total Access 850 System Manual
Section 3 Network Turnup Procedure
DC Powered Systems The DC powered Total Access 850 comes equipped with a DC Power supply to furnish the voltages necessary for proper backplane operation. As shipped, the Total Access 850 is set to factory default conditions. After installing the chassis and any access modules, the Total Access 850 is ready for power-up. •
•
• • • •
This unit shall be installed in accordance with Article 400 and 364.8 of the NEC NFPA 70 when installed outside of a Restricted Access Location (i.e., central office, behind a locked door, service personnel only area). To comply with GR-1089-CORE, Issue 3, this equipment MUST only be installed in a DC-C bonding and grounding environment. It may not be utilized in a DC-I (isolated) bonding and grounding environment. Power to the Total Access 850 DC system must be from a reliably grounded -48 VDC source which is electrically isolated from the AC source. The branch circuit overcurrent protection shall be a fuse or circuit breaker rated minimum 48 VDC, maximum 20A. A readily accessible disconnect device, suitably approved and rated, shall be incorporated in the input source wiring. Maximum recommended ambient operating temperature is 45 oC.
Making Alternate Power Connections For wire-wrap or screw terminal connections, the rear cover does not need to be removed; only the terminal access cover needs to be removed. Make wire-wrap or screw terminal connections as follows: 1. Unscrew the access cover hold-down screw. 2. Slide the access cover down slightly to disengage the lock-tabs from their slots.
Use wire gauge suitable for the application.
3. Identify the wire-wrap pins designated for use, and make the connections starting with the pins closest to the exit port to avoid wiring interference as work progresses. 4. If alternate power connection to P7 is to be used, make those terminal connections last. 5. Carefully route wiring through the exit port. 6. Position and align the access cover tabs to the slots; insert the tabs and slide the cover up slightly until the screw holes are aligned. Ensure that exit wiring is not pinched or damaged. 7. Reinsert the hold-down screw.
64203376L1-1B
© 2004 ADTRAN, Inc.
59
Page 60
Section 3 Network Turnup Procedure
7.
Total Access 850 System Manual
MOUNTING OPTIONS
The Total Access 850 chassis may be wallmounted or installed in a 19-inch or 23-inch rack. Wallmount brackets are included with the chassis. For a rackmount installation, the Total Access 850 Base Unit allows flush-face mount, face-forward mount, center mount, and rear mount. The Total Access 850 chassis includes wallmount brackets. If rack mount brackets are needed, use part number 1175045L1 or 1175046L1 for 19 inch or 23 inch, respectively.
Be careful not to upset the stability of the equipment mounting rack when installing this product.
Required Clearances A minimum 10-inch clearance is required on the front end for access module insertion and withdrawal. On the backplane end, a five-inch clearance is required for wiring access to the V.35 connector. For those units installed in a communications bay, standard bay clearances are satisfactory.
Wallmounting the Chassis Tools Needed
The Total Access 850 chassis mounts and connects with standard fasteners and hand tools: • Four #8 x 3/4-inch pan-head wood screws • Drill and drill bit set • Flat head screwdriver (medium) • Two Phillips head screwdrivers (small/medium) • Wire-wrap gun (optional) • 25-pair male amphenol cable (customer connection) • Selected punch-down block and tool Installing the Chassis
1. Position the chassis at the desired location; observe required clearances and ensure cable plugs reach their designated sockets. 2. Ensure the chassis is plumb; then mark through the flange mounting holes to identify where the pilot holes will be drilled. 3. Using a 1/16-inch drill bit, drill pilot holes at the marked locations. 4. Mount the chassis using the four #8 x 3/4-inch pan-head wood screws.
60
© 2004 ADTRAN, Inc.
64203376L1-1B
Page 61
Total Access 850 System Manual
8.
Section 3 Network Turnup Procedure
INSTALLING MODULES
Figure 1 shows the slot numbering designation as viewed from the front of the Total Access 850 chassis. The functionally identical option slots only accept Total Access 850 access modules, and the controller slots only accept Total Access 850 controller modules. PSU
RCU
ACCESS MODULES
Figure 1. Total Access 850 Slot Designation (Front View)
Access modules are intended to be serviced by qualified service personnel only.
Electronic modules can be damaged by static electrical discharge. Before handling modules, put on an antistatic discharge wrist strap to prevent damage to electronic components. Place modules in antistatic packing material when transporting or storing. When working on modules, always place them on an approved antistatic mat that is electrically grounded.
Instructions for Installing the Power Supply Unit (P/N 1175006L2) Follow the steps below to install the Power Supply Unit. 1. The Power Supply Unit inserts directly into the common card area in the position labeled PSU. The unit is mechanically keyed to prevent insertion in any other slot. Prior to circuit card installation, remove the chassis card-lock safety bar by disengaging the captured screw and lifting the safety bar away from the chassis.
2. To install the PSU, grasp the unit by the faceplate while supporting the bottom side.
64203376L1-1B
© 2004 ADTRAN, Inc.
61
Page 62
Section 3 Network Turnup Procedure
Total Access 850 System Manual
3. Align the card edges to the guide grooves and insert the unit until the edge connector seats firmly into the backplane. 4. Lock the card in place by pushing in on the lock lever. 5. Reinstall the card-lock safety bar.
Instructions for Installing the Total Access 850 Controller and Access Modules Individual access modules insert from the front. A locking bar holds the modules in place for added security. Disengaging the captured screw allows removal of the locking bar. To install Controller Resource and Access Modules for the Total Access 850, follow the steps outlined below. 1. Hold the access module by the faceplate while supporting the bottom side. 2. Align the module edges to the guide grooves for the designated slot. 3. Insert the module until the edge connector seats firmly into the backplane. 4. Lock the module in place by pushing in on the locking lever. 5. Connect the cables to the associated device(s). All wiring connections terminate on the backplane of the chassis.
9.
MODULE SHIPPING CONTENTS
Quad FXO Access Module (P/N 1175407L2) Shipping Contents The ADTRAN shipment of the Quad FXO Access Module includes the following: • Quad FXO Access Module
Quad FXS Access Module (P/N 1175408L2) Shipping Contents The ADTRAN shipment of the Quad FXS Access Module includes the following: • Quad FXS Access Module
UBR1TE Access Module (P/N 1180020L1) Shipping Contents The ADTRAN shipment of the UBR1TE Access Module includes the following items: • UBR1TE Access Module • UBR1TE Access Module Job Aid
62
© 2004 ADTRAN, Inc.
64203376L1-1B
Page 63
Total Access 850 System Manual
Section 3 Network Turnup Procedure
OCU DP Access Module (P/N 1180005L1) Shipping Contents The ADTRAN shipment of the OCU DP Access Module includes the following items: • OCU DP Access Module • OCU DP Access Module Job Aid
E&M/TO Access Module (P/N 1180402L1) Shipping Contents The ADTRAN shipment of the E&M/TO Access Module includes the following items: • E&M/TO Access Module • E&M/TO Access Module Job Aid
Dual V.35 Access Module (P/N 1180025L1) Shipping Contents The ADTRAN shipment of the Dual V.35 Access Module includes the following items: • Dual V.35 Access Module • Dual V.35 Access Module Job Aid
DSX-1 Module (P/N 1200385L1) The ADTRAN shipment of the DSX-1 Module includes the following: • DSX-1 Module
64203376L1-1B
© 2004 ADTRAN, Inc.
63
Page 64
Section 3 Network Turnup Procedure
64
Total Access 850 System Manual
© 2004 ADTRAN, Inc.
64203376L1-1B