The text of a manual · part 10 of 16
Modicon 484 Programmable Controller Maintenance Manual, pages 91 to 100
Pages 91 to 100 of 160
The original document is the PDF (6.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B553, Modicon B557, AEG B553, Gould B553, Schneider B553, AEG B557, Gould B557 and Schneider B557
Page 91
(4)
Connect wires board (Figure 0
0 slide to IV-4).
terminals on
Rev.
C memory
Lithium batteries supplied with wires are for Place batteries in holders and conconnection. nect red wires to center terminals and black wires to terminals towards side of memory board. Connect jumper between terminals below right holder. batteries Alkaline are placed in spring clip holders. No wires are supplied with these batteries. To connect these batteries in series, jumper is placed between terminals El and E3. Connect only one jumper either below right holder or between holders depending upon battery type.
(5)
Remove the second old battery from its holder batteries are in the controller. Replace with new battery following steps 3 and 4 above.
(6)
Record battery vided.
(7)
Verify operation of BATT OK indicator mainframe and then close mainframe.
(8)
If BATT OK indicator is not illuminated, replace LED lamp, or power supply, or memory board (Figure IV-6).
change on memory board in on if two second space pro- front of
Memory boards can be removed, stored, transported, and exchanged without loss of memory as long as the batteries are inserted. There is no indication of battery level when except installed in controller with AC power applied. Memorv sizes of any controller can be changed by replacing the board. 4.1.3
INPUT/OUTPUT
SECTION
Communications from the mainframe to the real world is acall inThis section isolates complished via the I/O Section. put and output devices to prevent external noise from affecting The circuitry the internal logic of the 484 Controller system. filter inputs and in the I/O Section is specially designed to compatible with user's levels the voltage drive outputs at placement of the There are no limitations on the equipment. handling their voltage modules in the I/O Section relative to AC circuits do not have to be isolated from DC circapacity. be separated cuits nor do high voltage (i.e., 220 VAC) have to from low voltages (i.e., 5 DCMF). Whenever a failure following steps should failure:
is suspected be taken to IV-7 the in I/O systematically
Section, locate the the
Page 92
(1)
Call SINGLE I/O CIRCUIT - Connect Programming Device. (0XxX reference) up input (1XxX reference) or output its compare When it is an input, that is suspected. modinput the status with that of the indicator of and operational input is the agree, If they ule. field wiring external device should be examined. If not, the input module should be replaced. NOTE
When possible, cycle switch, pushbutton etc., tion.
device such as input ON/OFF/ON to confirm limit opera- with When it is an output, its status that compare If they agree, the output indicated on output module. device is operational and the field wiring/external should If not, the output module should be examined. is not being Verify that a blown fuse be replaced. indicated at output module before replacing module. NOTE When possible, use DISABLE function (Paragraph 3.1.5) to force output ON/OFF/ON etc. MEMORYPROTECT must of OFF. CAUTION BE VERY CAREFUL THAT OUTPUT WILL NOT CAUSE UNSAFE USER EQUIPMENT OPERATION. (2)
MULTIPLE I/O CIRCUITS - Connect Programming appropriate verify I/O operation and select from the following: 0
0
Device to procedure power supplied to ON ONE MODULE - Verify proper module. If replace If voltage exists, module. not, troubleshoot field wiring and power source. WITHIN ONE I/O HOUSING -
CAUTION MAIN AC POWERTO 484 SYSTEM SHOULD BE REMOVED FIRST. DO NOT REMOVE CABLES WITH POWERON 484 MAINFRAME. 00 bus connector. Open I/O duct and reseat I/O If this does not correct fault, use spare rotating connectors withI/O bus connector, in duct as necessary to move spare connector to desired housing.
IV-8
Page 93
from susRemove I/O modules one at a time continues. If fault housing if pected faulty module begins to operate when an I/O that module and module is removed, replace inspect its connector on housing backplane. 00 when backplane its Replace I/O housing or does not correct removing all I/O modules fault.
TS-80-0033-2
Figure I V-5. J471 Expander Ins talla tion
0
MULTIPLE I/O 00
00
HOUSINGS- faulty housings Remove top I/O module from address. Only one and verify selection of switch should b positioned on any housing (Figure 11-14). Reset all switches if no obvious errors are detected. bus connectors Open I/O duct and remove I/O from suspected housings one at a time if the Reconnect in the same fault still exists. order examining I/O operation with while If one housing creates programming device. the fault only when connected to the bus, it or its backplane should be replaced. IV-9
Page 94
00
(3)
one Remove the entire bus cable, Replace in same order, at a time. for a faulty I/O housing. Finally, entire I/O bus cable.
connector searching replace
(Figure OTHER I/O DEVICES - The model J471 Expander disIV-S) is maintained similarly to the power supply cussed above. structure can be troubleshot Its I/O following the procedure listed above. I/O bus communiAll I/O modules are parallel to the all I/O data is seen by each modtherefore, cations, modules ule via the I/O bus cable. appropriate Only expanded This includes local or respond to the data. I/O's as well as register modules. Register register I/O housings. B547/B458 are dressing selection is accomplished on the register module.
4.2 adI/O
FAULT ISOLATION FLOW CHARTS
This part of Section IV contains five fault isolation These are designed for use by MODICON customers. charts. vice personnel recommend users attempt to isolate faults calling MODICON service center. The fault isolation flowcharts flowSerbefore are as follows:
Figure
IV-6.
DC POWERLamp Fault
Isolation
Flowchart
Figure
IV-7.
BATT OK Lamp Fault
Isolation
FLowchart
Figure
IV-8.
RUN Lamp Fault
Figure
IV-g.
RUN Lamp Fault Isolation FLowchart (Continuation of A from Figure IV-8)
Figure
IV-lo.
I/O
Section
IV-10
Isolation
Fault
Isolation
FLowchart
Flowchart.
Page 95
Iv-11
PRIMAR AC FUSE F-I INSIDE PWR SUPPLY
YES REPLACE POWER SUPPLY
SUPPLY REGU- LATOR 8D
CHECK PRI- CHECK FOR CHECK FOR MARY AC POSSIBLE POSSIBLE WIRING FOR CAUSE AND CAUSE AND
CAUSE REPLACE FUSE REPLACE FUSE
12 VDC FUSE F-3, STILL Goop
REMOVE ALL
1/0 RIBBON a) CABLES FROM CONTROLLER
RE ATTACH 1/0 RIBBON TO EACH
HOUSING ONE AT A TIME UNTIL
FROM SUSPECT HOUSING. REPLACE REPLACE FUSE F-3. REATTACH 1/0 RIBBON
FUSE F-3 o)
REPLACE 1/0 MODULES ONE AT A TIME UNTIL FUSE F-3 BLOWS RE- PLACE DEFECTIVE 1/0 MODULE.
REPL ACE ENTIRE CONTROLLER
DC POWER LAMP ON
YES
+12 VDC FUSE, F-3
REATTACH 1/0 CABLE IN THE PROPER MANNER AND REPLACE
(1) AC POWER MUST BE REMOVED FROM CONTROLLER BEFORE REMOVING OR REPLACING ANY RIBBON CABLES. FAILURE TO DO SO COULD RESULT IN DAMAGE TO EQUIPMENT.
Figure IV-6. DC POWER Lamp Fault Isolation Flowchart TS-80-0018-1
Page 96
Iv-12
BATTERY OK LAMP ON
NO
ATTACH PI80 TO
|CONTROLLER
COIL 257 YES a
NO
REPLACE BATTERIES
CHECK RIBBON CABLE BETWEEN C.PU. BOARD AND CONTROL BOARD WHICH HOUSES THE INDICATOR LAMPS
POSSIBLE BAD L.E.D. REPLACE CONTROL BOARD POWER SUPPLY OR ENTIRE CONTROLLER
BATTERY LAMP ON
NO
YES
REPLACE MEMORY (C480) BOARD OR CONTROLLER
!
TS-80-0019-1 Figure |V-7, BATT OK Lamp Fault Isolation Flowchart
Page 97
Iv-13
© CONTINUED
ON SHEET 4 REMOVE I/O| | CYCLE no [ATTACH THE
CLE RUN PI80 TO EXAMINE CY! CABLES FROM A/C LAMP ON NETWORKS (4)
A/C POWER
YES
INSPECT UNIT REATTACH ONWECTION: 1/0 CABLES
PROCESSOR | |POWER THE INSPECT AND!
CONTROLLER RE AT TACH CABLE
PI6O CABLE CORRECTLY CONNECTED,
RUN LAMP ON
POSSIBLE CAUSE
REPLACE 484
PROBLEM APPEARS 10 BE IN THE 1/0 REMOVE RIBBON CABLE FROM 1/0 HOUSINGS ONE AT A TIME UNTIL RUN LAMP COMES BACK ON. THEN REMOVE 1/0 a) MODULES FROM SUSPECT 1/0 HOUSING UNTIL THE HOUSING OR ONE OF THE MODULES IS FOUND TO BE DEFFECTIVE.
Figure IV-8. RUN Lamp Fault Isolation Flowchart TS-80-0020-1
Page 98
Iv-14
CONTINUED FROM SHEET 3
No |ON THE PI80 GO TO SUPERVISORY RUN NO DO: STOP START LAMP ON
POWER FLOW INFO OF PI80
THE PIS SAY" FCN OR START FAIL
YES YES
INSPECT FOR CHECK + 5VDC IT IS NECESSARY TO FUSE ,F-2 POSSIBLE CLEAR THE USER MEM- INSIDE POWER CAUSE ORY, ON THE PI80 GO SUPPLY TO SUPERVISORY AND DO: 1. STOP 2.CLEAR MEMORY 3. START
NO REPLACE poe ENTIRE CONTROLLER
YES
REPLACE NO REPLACE FUSE CONTROLLER
REAT TACH YES 0. RIBBON @ LE TO CONTROLLER © CHECK FOR PROBLEM APPEARS TO BE IN THE Oe Con 1/0, REMOVE 1/0 RIBBON CABLE - FROM 1/O HOUSINGS ONE AT A TIME UNTIL F-2 DOES NOT BLOW THEN REMOVE THE 1/0 MODULES FROM THE SUSPECT HOUSING UNTIL THE 1/0 HOUSING OR ONE MODULE IS FOUND DEFECTIVE.
(5)
INSPECT FOR POSSIBLE PROBLEM IN 1/0 OR ASSOCIATE CABLING
TS-80-0021-1
Figure IV-9. RUN Lamp Fault Isolation Flowchart (Continuation of A from Figure IV-8)
Page 99
Iv-15
1/0 FUNCTIONING PROPERLY.
END
OUTPUT PROBLEM
MODULE ILLUMINATED
REPLACE INPUT MODULE
PROBLEM WITH MORE THAN ONE 1/0 POINT
NO
ALL STRIP SEL. SWITCHES {N CORRECT POS ON | LEFT
MORE THAN ONE 1/0 STRIP IN THIS SYSTEI
REMOVE RIBBON
YES CABLE FROM EACH
I/O STRIP ONE AT A TIME
PROBLEM GOES AWAY WITH THE REMOVAL OF A PARTICULAR
YES | POSSIBLE BAD
1/0 STRIP OR
1/0 MOOULE
1/0 STRIP,
CORRECT
POSSIBLE BAD MROBULE OR CONTROLLER
ONE MUST BE REPLACED
NO | REPLACE OUTPUT MODULE
OUTPUT MODULE WIRED CORRECTLY *
FUSE INDICATOR
LLUMINATED
REPLACE REWIRE DEFECTIVE * FUSE
% SEE APPENDIX 'B IN THE 484 MANUAL FOR WIRING INFO
PROBABLE BAD INPUT DEVICE LIMIT
SW PUSH BUT ®
ECT.
READDRESS THE
GOOD STRIP WITH THE BAD ONES ADDRESS
AND REMOVE THE RIBBON CABLE FROM YES THE BAD STRIP
OTHER 1/0 HOUSINGS WITH NPUT CARDS IN THI
POSSIBLE BAD VO STRIP OR
POSSIBLE BAD CONTROLLER RIBBON CABLE
POSSIBLY BAD NO 11/0 STRIP OR CONTROLLER A SWAP OF ONE IS NECESSARY
OTHER 1/0 HOUSINGS WITH OUTPUT CARDS
READDRESS THE GOOD STRIP WITH
THE BAD ONES, ADDRESS @ AND REMOVE THE
RIBBON CABLE FROM
THE BAD STRIP
OUTPUT WORKS
POSSIBLE DEFECTIVE CONTROLLER
SYSTEM
[ - ] CONTROLLER, SWAP ONE.
Figure 1V-10. 1/O Section Fault Isolation Flowchart
POSSIBLE BAD 1/0 STRIP OR
MODULE
TS-80-0022-1
Page 100
4.3
P180 ERROR MESSAGES
All P180 alphabetically error messages are detailed here and are after the 484 Error Code is described;
organized
There are Many errors are caused by illegal user actions. also a number of SYSTEM ERRORS which seldom appear in a funcsystem However, if SYSTEM ERRORS do occur, the tioning system. may be in serious difficulty and needs to be serviced. The following 484 which indicate list it of SYSTEM ERRORS are has received erroneous 1 2 3 4 5
6 17 12 15 messages from information:
the
'PARITY ERROR' 'OVERRUN ERR' 'CHKSUM ERROR' 'BAD ADR RNGE' 'ILLEGAL ADDR' 'ILLEGAL NODE' 'BAD LED REQ' 'BAD COMMAND' 'BAD LENGTH' the The following list of SYSTEM ERRORS are messages from P180 which indicate that it has received erroneous information: 'BAD RESPONSE' 'P180 OVERRUN' 'P180 PARITY' 'P180 CKSUM' 'P3 PARITY' 'P3 OVERRUN' 'P3 CKSUM ERR' 4.3.1
484 ERROR CODE
This an error followed following message appears when P180 is in supervisory status 484. The message will has been detected in the by a two-digit number code indicating error type. list contains the error codes and their meanings: Code
Definition Communications Overrun Memory Checksum Failed Invalid Node Type Found I/O Port Error Scratchpad Diagnostic Failed -Fatal-No Run Light Coil RAM Checksum Failed CPU Diagnostic Failed IV-16 and be The