Modicon 484 Programmable Controller Maintenance Manual, pages 91 to 100

Pages 91 to 100 of 160

The original document is the PDF (6.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Modicon B553, Modicon B557, AEG B553, Gould B553, Schneider B553, AEG B557, Gould B557 and Schneider B557

Page 91

(4)

Connect wires board (Figure 0

0 slide to IV-4).

terminals on

Rev.

C memory

Lithium batteries supplied with wires are for Place batteries in holders and conconnection. nect red wires to center terminals and black wires to terminals towards side of memory board. Connect jumper between terminals below right holder. batteries Alkaline are placed in spring clip holders. No wires are supplied with these batteries. To connect these batteries in series, jumper is placed between terminals El and E3. Connect only one jumper either below right holder or between holders depending upon battery type.

(5)

Remove the second old battery from its holder batteries are in the controller. Replace with new battery following steps 3 and 4 above.

(6)

Record battery vided.

(7)

Verify operation of BATT OK indicator mainframe and then close mainframe.

(8)

If BATT OK indicator is not illuminated, replace LED lamp, or power supply, or memory board (Figure IV-6).

change on memory board in on if two second space pro- front of

Memory boards can be removed, stored, transported, and exchanged without loss of memory as long as the batteries are inserted. There is no indication of battery level when except installed in controller with AC power applied. Memorv sizes of any controller can be changed by replacing the board. 4.1.3

INPUT/OUTPUT

SECTION

Communications from the mainframe to the real world is acall inThis section isolates complished via the I/O Section. put and output devices to prevent external noise from affecting The circuitry the internal logic of the 484 Controller system. filter inputs and in the I/O Section is specially designed to compatible with user's levels the voltage drive outputs at placement of the There are no limitations on the equipment. handling their voltage modules in the I/O Section relative to AC circuits do not have to be isolated from DC circapacity. be separated cuits nor do high voltage (i.e., 220 VAC) have to from low voltages (i.e., 5 DCMF). Whenever a failure following steps should failure:

is suspected be taken to IV-7 the in I/O systematically

Section, locate the the

Page 92

(1)

Call SINGLE I/O CIRCUIT - Connect Programming Device. (0XxX reference) up input (1XxX reference) or output its compare When it is an input, that is suspected. modinput the status with that of the indicator of and operational input is the agree, If they ule. field wiring external device should be examined. If not, the input module should be replaced. NOTE

When possible, cycle switch, pushbutton etc., tion.

device such as input ON/OFF/ON to confirm limit opera- with When it is an output, its status that compare If they agree, the output indicated on output module. device is operational and the field wiring/external should If not, the output module should be examined. is not being Verify that a blown fuse be replaced. indicated at output module before replacing module. NOTE When possible, use DISABLE function (Paragraph 3.1.5) to force output ON/OFF/ON etc. MEMORYPROTECT must of OFF. CAUTION BE VERY CAREFUL THAT OUTPUT WILL NOT CAUSE UNSAFE USER EQUIPMENT OPERATION. (2)

MULTIPLE I/O CIRCUITS - Connect Programming appropriate verify I/O operation and select from the following: 0

0

Device to procedure power supplied to ON ONE MODULE - Verify proper module. If replace If voltage exists, module. not, troubleshoot field wiring and power source. WITHIN ONE I/O HOUSING -

CAUTION MAIN AC POWERTO 484 SYSTEM SHOULD BE REMOVED FIRST. DO NOT REMOVE CABLES WITH POWERON 484 MAINFRAME. 00 bus connector. Open I/O duct and reseat I/O If this does not correct fault, use spare rotating connectors withI/O bus connector, in duct as necessary to move spare connector to desired housing.

IV-8

Page 93

from susRemove I/O modules one at a time continues. If fault housing if pected faulty module begins to operate when an I/O that module and module is removed, replace inspect its connector on housing backplane. 00 when backplane its Replace I/O housing or does not correct removing all I/O modules fault.

TS-80-0033-2

Figure I V-5. J471 Expander Ins talla tion

0

MULTIPLE I/O 00

00

HOUSINGS- faulty housings Remove top I/O module from address. Only one and verify selection of switch should b positioned on any housing (Figure 11-14). Reset all switches if no obvious errors are detected. bus connectors Open I/O duct and remove I/O from suspected housings one at a time if the Reconnect in the same fault still exists. order examining I/O operation with while If one housing creates programming device. the fault only when connected to the bus, it or its backplane should be replaced. IV-9

Page 94

00

(3)

one Remove the entire bus cable, Replace in same order, at a time. for a faulty I/O housing. Finally, entire I/O bus cable.

connector searching replace

(Figure OTHER I/O DEVICES - The model J471 Expander disIV-S) is maintained similarly to the power supply cussed above. structure can be troubleshot Its I/O following the procedure listed above. I/O bus communiAll I/O modules are parallel to the all I/O data is seen by each modtherefore, cations, modules ule via the I/O bus cable. appropriate Only expanded This includes local or respond to the data. I/O's as well as register modules. Register register I/O housings. B547/B458 are dressing selection is accomplished on the register module.

4.2 adI/O

FAULT ISOLATION FLOW CHARTS

This part of Section IV contains five fault isolation These are designed for use by MODICON customers. charts. vice personnel recommend users attempt to isolate faults calling MODICON service center. The fault isolation flowcharts flowSerbefore are as follows:

Figure

IV-6.

DC POWERLamp Fault

Isolation

Flowchart

Figure

IV-7.

BATT OK Lamp Fault

Isolation

FLowchart

Figure

IV-8.

RUN Lamp Fault

Figure

IV-g.

RUN Lamp Fault Isolation FLowchart (Continuation of A from Figure IV-8)

Figure

IV-lo.

I/O

Section

IV-10

Isolation

Fault

Isolation

FLowchart

Flowchart.

Page 95 read from a scan by OCR; it may hold reading errors

Iv-11

PRIMAR AC FUSE F-I INSIDE PWR SUPPLY

YES REPLACE POWER SUPPLY

SUPPLY REGU- LATOR 8D

CHECK PRI- CHECK FOR CHECK FOR MARY AC POSSIBLE POSSIBLE WIRING FOR CAUSE AND CAUSE AND

CAUSE REPLACE FUSE REPLACE FUSE

12 VDC FUSE F-3, STILL Goop

REMOVE ALL

1/0 RIBBON a) CABLES FROM CONTROLLER

RE ATTACH 1/0 RIBBON TO EACH

HOUSING ONE AT A TIME UNTIL

FROM SUSPECT HOUSING. REPLACE REPLACE FUSE F-3. REATTACH 1/0 RIBBON

FUSE F-3 o)

REPLACE 1/0 MODULES ONE AT A TIME UNTIL FUSE F-3 BLOWS RE- PLACE DEFECTIVE 1/0 MODULE.

REPL ACE ENTIRE CONTROLLER

DC POWER LAMP ON

YES

+12 VDC FUSE, F-3

REATTACH 1/0 CABLE IN THE PROPER MANNER AND REPLACE

(1) AC POWER MUST BE REMOVED FROM CONTROLLER BEFORE REMOVING OR REPLACING ANY RIBBON CABLES. FAILURE TO DO SO COULD RESULT IN DAMAGE TO EQUIPMENT.

Figure IV-6. DC POWER Lamp Fault Isolation Flowchart TS-80-0018-1

Page 96 read from a scan by OCR; it may hold reading errors

Iv-12

BATTERY OK LAMP ON

NO

ATTACH PI80 TO

|CONTROLLER

COIL 257 YES a

NO

REPLACE BATTERIES

CHECK RIBBON CABLE BETWEEN C.PU. BOARD AND CONTROL BOARD WHICH HOUSES THE INDICATOR LAMPS

POSSIBLE BAD L.E.D. REPLACE CONTROL BOARD POWER SUPPLY OR ENTIRE CONTROLLER

BATTERY LAMP ON

NO

YES

REPLACE MEMORY (C480) BOARD OR CONTROLLER

!

TS-80-0019-1 Figure |V-7, BATT OK Lamp Fault Isolation Flowchart

Page 97 read from a scan by OCR; it may hold reading errors

Iv-13

© CONTINUED

ON SHEET 4 REMOVE I/O| | CYCLE no [ATTACH THE

CLE RUN PI80 TO EXAMINE CY! CABLES FROM A/C LAMP ON NETWORKS (4)

A/C POWER

YES

INSPECT UNIT REATTACH ONWECTION: 1/0 CABLES

PROCESSOR | |POWER THE INSPECT AND!

CONTROLLER RE AT TACH CABLE

PI6O CABLE CORRECTLY CONNECTED,

RUN LAMP ON

POSSIBLE CAUSE

REPLACE 484

PROBLEM APPEARS 10 BE IN THE 1/0 REMOVE RIBBON CABLE FROM 1/0 HOUSINGS ONE AT A TIME UNTIL RUN LAMP COMES BACK ON. THEN REMOVE 1/0 a) MODULES FROM SUSPECT 1/0 HOUSING UNTIL THE HOUSING OR ONE OF THE MODULES IS FOUND TO BE DEFFECTIVE.

Figure IV-8. RUN Lamp Fault Isolation Flowchart TS-80-0020-1

Page 98 read from a scan by OCR; it may hold reading errors

Iv-14

CONTINUED FROM SHEET 3

No |ON THE PI80 GO TO SUPERVISORY RUN NO DO: STOP START LAMP ON

POWER FLOW INFO OF PI80

THE PIS SAY" FCN OR START FAIL

YES YES

INSPECT FOR CHECK + 5VDC IT IS NECESSARY TO FUSE ,F-2 POSSIBLE CLEAR THE USER MEM- INSIDE POWER CAUSE ORY, ON THE PI80 GO SUPPLY TO SUPERVISORY AND DO: 1. STOP 2.CLEAR MEMORY 3. START

NO REPLACE poe ENTIRE CONTROLLER

YES

REPLACE NO REPLACE FUSE CONTROLLER

REAT TACH YES 0. RIBBON @ LE TO CONTROLLER © CHECK FOR PROBLEM APPEARS TO BE IN THE Oe Con 1/0, REMOVE 1/0 RIBBON CABLE - FROM 1/O HOUSINGS ONE AT A TIME UNTIL F-2 DOES NOT BLOW THEN REMOVE THE 1/0 MODULES FROM THE SUSPECT HOUSING UNTIL THE 1/0 HOUSING OR ONE MODULE IS FOUND DEFECTIVE.

(5)

INSPECT FOR POSSIBLE PROBLEM IN 1/0 OR ASSOCIATE CABLING

TS-80-0021-1

Figure IV-9. RUN Lamp Fault Isolation Flowchart (Continuation of A from Figure IV-8)

Page 99 read from a scan by OCR; it may hold reading errors

Iv-15

1/0 FUNCTIONING PROPERLY.

END

OUTPUT PROBLEM

MODULE ILLUMINATED

REPLACE INPUT MODULE

PROBLEM WITH MORE THAN ONE 1/0 POINT

NO

ALL STRIP SEL. SWITCHES {N CORRECT POS ON | LEFT

MORE THAN ONE 1/0 STRIP IN THIS SYSTEI

REMOVE RIBBON

YES CABLE FROM EACH

I/O STRIP ONE AT A TIME

PROBLEM GOES AWAY WITH THE REMOVAL OF A PARTICULAR

YES | POSSIBLE BAD

1/0 STRIP OR

1/0 MOOULE

1/0 STRIP,

CORRECT

POSSIBLE BAD MROBULE OR CONTROLLER

ONE MUST BE REPLACED

NO | REPLACE OUTPUT MODULE

OUTPUT MODULE WIRED CORRECTLY *

FUSE INDICATOR

LLUMINATED

REPLACE REWIRE DEFECTIVE * FUSE

% SEE APPENDIX 'B IN THE 484 MANUAL FOR WIRING INFO

PROBABLE BAD INPUT DEVICE LIMIT

SW PUSH BUT ®

ECT.

READDRESS THE

GOOD STRIP WITH THE BAD ONES ADDRESS

AND REMOVE THE RIBBON CABLE FROM YES THE BAD STRIP

OTHER 1/0 HOUSINGS WITH NPUT CARDS IN THI

POSSIBLE BAD VO STRIP OR

POSSIBLE BAD CONTROLLER RIBBON CABLE

POSSIBLY BAD NO 11/0 STRIP OR CONTROLLER A SWAP OF ONE IS NECESSARY

OTHER 1/0 HOUSINGS WITH OUTPUT CARDS

READDRESS THE GOOD STRIP WITH

THE BAD ONES, ADDRESS @ AND REMOVE THE

RIBBON CABLE FROM

THE BAD STRIP

OUTPUT WORKS

POSSIBLE DEFECTIVE CONTROLLER

SYSTEM

[ - ] CONTROLLER, SWAP ONE.

Figure 1V-10. 1/O Section Fault Isolation Flowchart

POSSIBLE BAD 1/0 STRIP OR

MODULE

TS-80-0022-1

Page 100

4.3

P180 ERROR MESSAGES

All P180 alphabetically error messages are detailed here and are after the 484 Error Code is described;

organized

There are Many errors are caused by illegal user actions. also a number of SYSTEM ERRORS which seldom appear in a funcsystem However, if SYSTEM ERRORS do occur, the tioning system. may be in serious difficulty and needs to be serviced. The following 484 which indicate list it of SYSTEM ERRORS are has received erroneous 1 2 3 4 5

6 17 12 15 messages from information:

the

'PARITY ERROR' 'OVERRUN ERR' 'CHKSUM ERROR' 'BAD ADR RNGE' 'ILLEGAL ADDR' 'ILLEGAL NODE' 'BAD LED REQ' 'BAD COMMAND' 'BAD LENGTH' the The following list of SYSTEM ERRORS are messages from P180 which indicate that it has received erroneous information: 'BAD RESPONSE' 'P180 OVERRUN' 'P180 PARITY' 'P180 CKSUM' 'P3 PARITY' 'P3 OVERRUN' 'P3 CKSUM ERR' 4.3.1

484 ERROR CODE

This an error followed following message appears when P180 is in supervisory status 484. The message will has been detected in the by a two-digit number code indicating error type. list contains the error codes and their meanings: Code

Definition Communications Overrun Memory Checksum Failed Invalid Node Type Found I/O Port Error Scratchpad Diagnostic Failed -Fatal-No Run Light Coil RAM Checksum Failed CPU Diagnostic Failed IV-16 and be The