Page 81

RUN

On whenever DC power is applied via the 484 mainframe and the J474 diagnostic routines indicate proper internal operation of this interface.

ACTIVE

Flashes whenever the J474 interface receives a message via the MODBUSor local EIA port that is addressed to this unit.

474 ERROR

Flashes whenever an error in communications between the 5474 interface and the 484 CPU has been detected. Appropriate error response will be sent to the sending device.

BUS ERROR

Flashes whenever a message addressed to this device from either the MODBUSor local EIA port has error within the message. Appropriate error response will be sent to the sending device.

3.7.5 CONNECTIONS The 5474 Interface is connected to the MODBUSor local EIA This connector device via a single 30-pin connector. (Buchanan Part No. PCB 2B30A616798, MODICON part number S2-2109) with mounting bracket (MODICON assembly AS-4965) is supplied with the interface. To service the J474 unit, this connector may be removed without distrubing MODBUScommunications to the other units provided physical connections are not distrubed. Since all options such as baud rate, unit number, parity and stop bits are selected by the wiring of this connector, easy replacement and rapid restoration of proper operation are accomplished without extensive testing or interruption of MODBUS InterDuring replacement of the 5474 Communication operation. technician does not need to set switches face, the service dip incorrect address. and possibly set the or rotary switches shown in Table including Assignment of functi_ons are 111-3, optional decoding.

III-43

Page 82

Table 111-3. J474Functions Function

Pins

Function

Pins

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Protective Ground Data Transmitted from J474 Data Received by J474 Ready to Send (RTS) Clear to Send (CTS) Data Set Ready (DSR) Signal Ground Binary Address 1 Baud Rate 1 Binary Address 2 Baud Rate 2 Binary Address 4 Baud Rate 4 Binary Address 8 Baud Rate 8

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 rlote:

Pins 1 through 7 and 20 conform to EIA RS 232-C specifications.

tion with

The following illustrates (Figure 111-25) a typical connecfor half duplex operation at 9600 baud, slave number 26 even parity, one stop bit, and ASCII mode.

I

Binary Address 16 Stop Bit Option Binary Address 32 Parity Type Option Data Terminal Ready (DTR) Parity Enable Binary Address 64 MODBUSFULL Duplex In Binary Address 128 MODBUSFULL Duplex Out Signal Ground Modbus Data in Mode Select 1 MODBUSDATA OUT Mode Select 2

Figure111-25. Typical J474 Connections III-44

Page 83

Baud rates are selected by connecting pins to Signal Ground that is available at pin 7. the following chart wil summarize all available = connect to ground; no = leave unconnected):

9, 11, 13 and 15 For convenience, baud rates (yes

Pins Rate

9

11

13

15

50 75 110 134.5 150 300 600 1200 1800 2000 2400 3600 4800 7200 9600 19200 yes yes yes yes yes yes yes yes yes no yes no yes no yes no yes no yes no yes no yes no no no yes yes no no yes yes no no yes yes no no yes yes no no no no ves yes ves yes no no no no yes yes yes yes no no no no no no no no

The slave address is established by binary numbers on pins to Signal Ground Connect 8, 10, 12, 14, 16, 18, 22 and 24. (pin 26) for a zero bit and leave unconnected for a one bit. 00011010 which requires is For example, address 26 in binary of pins 24, 22, 18, 12, and 8 to pin 26 as shown in connection above example. pins Specific modes of operation are selected by connecting following configur28 and 30 to Signal Ground (pin 26) in the to ground; no = leave unconation (yes = connect that pin nected): Pins Mode

28

30

ASCII RTU Not valid Test yes yes no no yes no yes no

The remaining options (stop bits and parity are selected by on pin 7. connecting 17, 19, and 21 to Signal Ground available and their options available summarizes chart The following to ground; no = leave associated connections (yes = connect unconnected): III-45

Page 84

Two stop One stop Two stop One stop Two stop One stop Two stop One stop

Option

17 bits, no parity bit, no parity bits, no parity bit, no parity bits, odd parity bit, odd parity bits, even parity bit, even parity yes no yes no yes no yes no

Pins 19

21 yes yes ves yes no no yes yes no no ves yes no no no no

3.7.6 SELF-TEST diagnostic Upon power up, the J474 conducts an internal CPU, ROM, RAM, Indicators, test to verify proper operation of: error When the Timers, Parallel Bus. Port, and Asynchronous front of the test is being performed, the indicators on the indicators indicators. The four J474 are used as diagnostic will cycle through the following pattern once on power up if no internal errors are detected.

Indicator

12

RUN ACTIti 484 ERROR BUS ERROR

Off Off Off On

Off Off On On

3

Test 4

5

6

7

8

Off On On On

On On On Off

On On Off Off

On Off Off Off

On On Off Off

On Off Off Off

Each test pattern lasts for appproximately 150 milliseconds (total 1.2 seconds of power up tests). If an error is detected, testing stops and the indicators can be used to indicate the test level that failed: MODICON Field Service personnel can correlate the test number to the internal component failure. When the MODBUSconnector is removed or if the Internal Test Mode is selected (pins 28 and 30 disconnected), the internal Self Test will operate continuously. The J474 will halt its operation when an error is detected during diagnostic testing. While in the Halt mode, no communications with the MODBUSnor the controller is possible. The diagnostic testing can be restated and possible reactivation of communications by cycling 5474 ON-OFF-ON.

III-46

Page 85

SECTION

IV

TROUBLESHOOTING 4.0

INTRODUCTION

The MODICON 484 Controllers are rugged, modular systems designed specifically for ments. They require no regular maintenance. components may be quickly replaced. failure, are provided to indicate proper operation subassemblies.

heavily protected, industrial environIn the event of Indicator lights of the mainframe's

If a suspected failure is encountered, there are several customer to determine procedures to be followed by the that and to there is a failure in the MODICON system isolate that failure to a particular assembly. These procedures are outlined in this section. no special They require test equipAs basic understanding of functions of the the comment. ponents is necessary.

b

The major troubleshooting methods available to the user are checkouts of the processor using the programming panel. This panel allows any network, input, output, or register to be examined and changed in any proper manner desired. Through the combination of logic examination and visual inspection or electrical test of field wiring terminals, failures may be isolated to the processor, I/O module, power sunply, or customer's hardware. The MODICON maintenance philosophy is based on the assumption that when a major subsystem is proved faulty, it should be immediately removed and replaced in its entirety. This procedure greatly increases system availability. 4.1

INDICATOR

LIGHTS

The mainframe has a series of three LED indicators (Figure Each LED is energized when a major portion of the IV-l). mainframe is operating.

AC power must be applied will function.

is

NOTE to mainframe before any

LED inIn addition to the mainframe, each I/O module has four its cirdicators to show the field voltage status of each of for the input The controller need not be functioning cuits. the proper The only requirement is for indicators to operate. Output indicators are on only when the field voltage to exist. controller is in operation. IV-1

Page 86

TS-80-0005-2

Figure IV-l. Indicators on Mainframe

4.1.1

POWER SUPPLY

The Power Supply is located in the front cover of the mainIts proper operation (output of both 5DCMF and 12 VDC) frame. mainframe. As long is indicated by the DC POWERlight on the the proper supplying as this LED is lit, the Power Supply is volIf this indicator is off, verify proper voltages. supply the With proper AC power voltage, tage at AC power terminals. and verOpen the mainframe internal fuses should be checked. ify continuity of internal fuses (Figure IV-2). operational, are If all internal fuses still off, and the LED itself is operational, should be replaced as follows:

the the

(1)

Remove AC power from mainframe

(2)

Unlatch

(3)

Disconnect wiring harness and ground strap supply side of mainframe (Figure IV-2). connect ribbon cable at power supply.

and swing mainframe

IV-2 indicator is Power SUPPlY terminals.

open. from Also, power dis-

Page 87

(4)

Support power supply (approximately 20 pounds) and lift up to separate hinges that connect power supply section to fixed portion of mainframe.

(5)

Remove power supply to work area for further or packaging for shipment to MODICON for repair.

(6)

Reverse supply.

steps

1 through

4 to re-install testing new power

DISCONNECT HERE

FUSE / 57-0006

FUSES (2) 57-0013 TS-80-0031-2

Figure I V-2. Power Supply - Location

IV-3 of Fuses

Page 88

4.1.2

PROCESSOR

The main function of the processor is to monitor the staus of all inputs continuously and direct the of all status outThere are two LED indicators that, puts. when energized, reThe flect proper operation of the processor (Figure IV-l). first indicates proper operation of the processor the (RUN), second proper battery voltage (BATT OK). If the RUN light goes out, and the DC POWER light i.5 lit, the processor has ceased operation. the processor If fails, its .memory should be restored by one of the peripheral devices, such as the model L206 Tape Loader or model T158 Telephone manual. Interface. These are discussed in Section II of this I1dump" have Center If neither a magnetic tape nor a Service been made, operation of the controller may be restored by iniInitializing tializing memory with the P180 Programming Panel. contains memory will restore all logic to the null state which cannot be restored by If the RUN light no customer program. the processor the appropriate should be peripheral device, replaced as follows: (1)

Disconnect AC power connections at lower right of mainframe.

from power terminals

(2)

Open

(3)

Loosen the support of the mainframe at the bottom. Do the mainframe Support not remove bolts completely. (33 pounds) and remove the upper bolts.

connectors mainframe and locate (Figure I/O Disconnect I/O connector(s) on the end of the 11-13). into I/O I/O bus cable(s). Remove from mainframe the I/O If an I/O bus cable is used to connect duct. the entire housings at the bottom of the mainframe, cable needs to be removed from the mainframe and saved.

NOTE To reduct the weight of the mainframe to the power supply section may be removed base section of the mainframe. Lift the mainframe clear

12 pounds, before the of bottom supports.

(4)

Take the mainframe to work area for futher If necessary, package and ship to MODICON for

(5)

Reverse steps

1 through

3 to install new mainframe.

The second indicator for the mainframe operation OK. When this LED is energized, there is sufficient capacity to retain memory upon loss of AC power. IV-4 testing. repair.

is BATT battery

Page 89

AC power is required to operate BATT OK Batteries are designed only troller system. They will not run the controller.

indicator retain to conor memory.

When the RATT OK LED is not illuminated, check the POWER If not illuminated, replace batteries. If illuminated, LED. verify voltage at AC power terminals at bottom right of mainframe. this tain battery The BATT OK LED is a warning about voltage. capacity to indicator goes off there is sufficient memory for at least seven days.

When main- batteries The following procedure should be used when the conIt is recommended that AC power to are to be replaced. Memory will be troller be left on while replacing batteries. either of the alkaline lost if the AC power is removed while when AC Memory will not be lost batteries is not installed. installed. One power is removed if either lithium battery is lithium battery is sufficient to retain memory. ,

TS-80-0032-2

Figure IV-3. Memory

Module

IV-5 with Batteries

Page 90

Procedures for replacement of alkaline are basically the same and are as follows:

or lithium and locate

(1)

Open mainframe, swing out memory board (Figure IV-3).

(2)

remove ONE If both battery holders contain batteries, alkaline Remember that one to create a vacant holder. battery is insufficient to maintain memorv without AC power.

(3)

Insert 0 0 new battery into power batteries vacant holder as follows:

Lithium batteries are inserted with .positive red wire towards center. Alkaline batteries are inserted with positive red wire towards left side. CAUTION

REVERSE POLARITY WILL CANCEL VOLTAGE OF TERY AND ELIMINATE BATTERY SUPPORT.

RED ;q:/+

RED i)j?E

El

CONNECTIONS

E3

FOR LITHIUM BATTERIES BLACK

CONNECTIONS

EXISTING

RIGHT HOLDER

LEFT HOLDER

TS-80-0017-1

SUPPlY,

RED

FOR ALKALINE BATTERIES

Figure I V-4. Wiring of Batteries

IV-6

BAT-

(+) (+)