SECTION 484 GENERAL
I
INFORMATION
INTRODUCTION
1.0 overview of ProgramThe introduction provides a general the MODICON mable Controllers (PC) and specific orientation to 484. All topics discussed here are discussed in more detail in trees For information on family other sections of the manual. cables to refer to Appendix A and for information on external Appendix B. A Glossary of Terms is included at the back.
1.1
GENERAL
SYSTEM
DEFINITION device (PC) is a solid-state Controller A Programmable situacontrol industrial in designed to make logic decisions with Relays and solid-state electronics can be replaced tions. a PC. Outstanding 0 0 0 0 features of a PC include:
fast responses in hostile environments. Reliable, ladder diagram with Programmable and reprogrammable language. indicator with diagnostic Simplified troubleshooting lights at major points. Easy maintenance with modular replacement.
The MODICON 484 is one of the finest examples of PC techIt is designed to replace control svstems of nology available. solid-state Advantages over relays and other 10 to 400 relays. devices include: Lower hardware costs. 4 to 20 ms depending on memory size. Faster scan rate: Expandable memory in six sizes: 1/4K to 8K. Expandable Input/Output (I/O) with four point modules. Easier installation. Retentive memory for logic and timer/counter values. Direct plug-in programming devices. on line programming. Real-time,
Table I-l lists and Figure troller, the I-l for specifications shows the controller I-l a basic system.
484
Con-
Page 12
Table I-1. Basic484 ControllerSpecifications Power Requirements: Standard
115 VAC + 15%, 60 Hz + 150 3 amp- peak Volt amps (max) start-up transient
Optional
115/220 VAC + 15%, 50 Hz 2 5% 3 amp amps (mat) 150 Volt transient (2 peak start-up amp on 220 V) Operating
Storage
Ambient Temperature
0°C to 60°C
-4O'C
Humidity
0% to 95%
0% to 95%
Environmental
Dimensions
Requirement:
(non-condensing)
to 80°C
(WXHXD):
Processor
(w/Power
Supply)
Single I/O (including housing I/O Duct)
15 in. x 20.5 in. x 6.5 in. (38 cm x 53 cm x 16.5 cm) 5 in. x 32 in. 6 in. (13 cm x 81 cm x 15 cm)
Eight Housings (One Channel)
40 in. 32 in. 6 in. (102 cm x 81 cm x 15 cm)
Weight: Processor I/O
Supply)
Module
33 lbs
(15 Kg)
1 lb
Kg)
(0.5
Single I/O Housing (w/Modules)
15 lbs
(7 Kg)
Eight Housings w/Modules & Duct)
136 lbs
(62 Kg)
Controls
I/O
(w/Power and Indicators:
CPU
RUN light POWERon light RATT OK light MFNORY PROTECT key
Modules:
Circuit Terminal Blow Fuse light I-2
Voltage (outputs light ONLY)
Page 13
Figure I-1. 484 Controller
A typical PC (Figure Power Supply, Processor, r 1
_---PROGRAMMING
I-2) I/O four components: is divided into and a Programming Device. Section,
1 1
System
> >
PROCESSOR
I/O SECTIONS
USER’S EQUIPMENT
A
USER ’ FIELD WIRING TS-80-0002-1
Figure I-2 Basic Block Diagram
1.2
COMPONENTS:
SYSTEM
DESCRIPTION
Each of the four components of a PC are described in this section (Figure I-3). Peripherals available Modicon 484 are also introduced.
I-3 briefly for the
Page 14
TS-80-0002-2
Figure l-3. 484 Components
1.2.1
PROCESSOR solidThe processor or brain of the PC is a completely Processing the Central called It is sometimes state device. the This is the mainframe. Unit (CPU) and sometimes called timer/ and relays replaces actually PC which the part of for expandable iS In the MODICON 484 the processor counters. of stopper switches. computational functions or for simulation ladder relay The processor is programmed in The program uses up to ten relay contacts guage.
diagram per rung.
lan- power The processor operates on DC power furnished by the the prothrought routed This internal DC power is supply. entered When the program is cessor to operate the I/O Section. into the processsor it remains until changed deliberately by a the Power failure or power-off conditions do not destroy user. program. and and data An access port enables entry of instructions The most permits monitoring of perviously entered information. into the processor common method of entering data or programs Panel. P180 CRT Programming the through this port is with this port are a Tape Other devices that may be connected to Communication Interface. a Telephone Loader, a Computer, or simulwhich allows with these devices is done via an adapter taneous operation with the CRT Programming Panel. I-4
Page 15
1.2.2
POWER SUPPLY the proThe Power Supply mounts inside the front cover of (non It operates on 115 VAC, 6OHz or 115/220 VAC, 50Hz cessor. required. are No adjustments or maintenance interchangeable). cooling is external NO A lamp indicates power-ready status. The required. circulation is free air necessary, although the processor; Power Supply has sufficient capacity to operate used An expander power supply is and 128 outputs. 128 inputs, to extend the PC/s capability to 256 inputs and 256 outputs. 1.2.3
INPUT/OUTPUT
(110) SECTION the input A major characteristic of the 484 Controller is connected to the and-output control devices that are directly accompuser wiring to and from the controller is controller. These housings are dehousings. lished through heavy duty Each module contains signed to hold up to eight I/O modules. A smaller I/O housing either input or output. four circuits; The covered accommodating up to four I/O modules is available. the wireway (I/O duct) enables easy installation and access to wiring. The modules are A'wide variety of I/O modules is offered. consolidlv These output driving or input handling circuits. their into structed units are easily removed from or plugged automatically contact is Once inserted, electrical housings. I/O modules can be remade through plated spring connectors. field devices moved and replaced without removing power on the There is no need to shut down the system to or internal logic. replace I/O modules. diodes by photo Each input and output circuit is isolated from affecting wiring thus preventing transients on the field required. The No periodic maintenance is the internal logic. fuses. output individual 484 output modules, AC or DC, have and outIndicators on each module show the field power status can be loI/O modules and field wiring put fuses condition. cated in any possible configuration regardless of voltage level. There are four classes and the user's equipment: 0 0
0
0 of signals between the
484 svstem
Discrete I/O connections. and interfaces, to Register I/O (three-digit numeric special analog multiplexer; register from the I/O: purpose modules). from the EIA Adapter, interface RS232C peripheral using the appropriate MODICON protocol. connecting MODBUSCommunication Interface - Used in intelor other communication options to a computer ligent device. I-5
Page 16
Field inputs consist of up to 128 discrete points or 256 Each has an ON or OFF state. Each with the I/O expander unit. has up to 32 inputs or register data. Register data is represented by a decimal number in the range of 0 to 999. All discrete inputs are read once during every scan. 1.2.4 CRT PROGRAMMING PANEL CRT The Model P180 CRT Programmer (Figure I-4) is a 5-inch work site near It is easily carried to the in a rugged case. the suited to the controller. The entire CRT unit is well locati_ons i n designed to operate industrial setting. It is and humidity, where electromagnetic noise, temperatures high environmental problems threatening mechanical shock, or other may be present.
TS-80-0003-2
Figure 1-4.P180CRT Programming Panel
The P180 CRT connects directly to the 484 Controller. It provides a simple method to program the processor. The ladder diagram language used for programming the PC is familiar relay symbology. There are no required programmer languages to learn. The CRT also allows rapid system checkout and easy, maintenance. A delux CRT permits the use of a standard RS232C printer. Thus, a hard copy of the ladder diagram contained in the controller can be generated. 1.2.5
PERIPHERALS
Several standard MODICON support units are available for use with the 484 Controller. These units provide a wide variety of support functions. Complete system support is always I-6
Page 17
The support units use the J470 EIA Adapter for conavailable. adapter allows a P180 ProThis nection to the processor. grammer and another peripheral device to be connected to the controller simultaneously. Available 0
0
0
0 0 0
1.3 support equipment includes:
communication with Interface for T158 Telephone MODICON's service center. the L206 Universal Tape Loader for local recording of user's program. MODBUS Interface (J474) which allows plant-wide or nation-wide communications. I?180 CRT Programmer for entering user logic. 5470 Communications interface. J471 I/O Expander for additional I/O capacitv.
SUMMARY
Programmable controllers are used in industrial settings to devices. Conreplace relays and other solid-state electronic with trollers are faster to respond to instructions and operate easily programmed with They are ladder maximum reliability. easier to Because they are modular they are diagram language. Hardware space is required. maintain and install, and less They operate in hostile environments. costs are lower. ProA typical controller is divided into four components: and a Programming Device. cessor, Power Supply, I/O Section, operThe processor is the brain of the PC. The processor SecThe I/O ates on DC power furnished by the power supply. The protion is the controller's link with the "real world". the congramming panel is the main device used to program troller. The MODICON 484 Programmable Controller is desigend to reIt has an expandplace control systems of 10 to 400 relays. also has an expandable able I/O with four point modules. It memory in six sizes ranging from 1/4K to 8K. The P180 Programming Device is connected directly to the 484. make the All of these features Controller one of the most up-to-date
I-7/1-8
MODICON 484 Programmable PC's on the market todav.
Page 18
Page 19
SECTION
II
INSTALLATION 2.0
INTRODUCTION
The MODICON 484 Controller Its circuitry allows troller. gic to be programmed. Section II describes formation necessary for 2.1
SYSTEM
2.1.1.
MAINFRAME is a microprocessor-based relay ladder diagram control the system configuration installation.
and gives conloin-
CONFIGURATION CODE several basic options. The 484 is manufactured with The variacustomer chooses from six memory sizes, two power supply These choices are reflected tions, and three instruction sets. in the Mainframe Code shown in Table 11-l. Table
Code:
11-l. C484 Mainframe
Code
1
C484-XYZ
X represents Instruction O-Basic l-Enhanced 2-Enhanced
Set I II
Y represents Power Supply 5-50Hz 6-60Hz l15VAC 115VAC
2 represents Memory Size l-
2 3 4 5 6 -
1/4K 1/2K 1K 2K 4K 8K
A C484-162, for example, indicates a C484 with an Enhanced Memory I Instruction set, 60~~ 115 VAC Power Supply, and a 1/2K Size. 2.1.2
HARDWARE
A typical ure includes the system.
CONFIGURATION
This figsystem layout is shown in Figure II-l. components of all major mounting dimensions for should be mounted vertiFor proper heat flow, all units heat Vertical orientation allows the fullest removal of cally. mounting template A ful-size via the heavy-duty housing fins. may be purchased from any MODICON sales office. II-1
Page 20
Figure 11-l. Typical System
Layout
Another system layout frequently used is shown in Figure This configuration is referred to as Half-Housing. 11-2. The housing is four I/O modules in the vertical orientation and up to 16 modules in the horizontal orientation. 2.13
PROCESSOR/POWER
SUPPLY
The latest techniques in CMOS semi-conductor memory with battery backup are used in the 484 Controller. Controller memory is not affected when the AC power supply is lost provided good batteries are installed in the unit. Batteries can be removed while the system is operating on primary AC power. When loss of primary power occurs, the alkaline batteries will maintain memory for approximately l-1/2 years. life is Shelf two approxiyears. Lithium batteries that maintain memory for mately five years are available as an option. Their shelf life worst case is ten years. Battery life is calculated for temperature, and bit configuration. memory size, a back panel for The processor is mounted directly onto other vertical support. joined to the is The power supply It may be removed separately. front door of the processor. opened. System operation is not interrupted when the door is The internal components of the processor and power supply may, therefore, be accessed without system. System halting the completely operation is halted only when the is power supply halted. Table II-2 summarizes the AC power requirements. II-2