The text of a manual · part 3 of 16
Modicon 484 Programmable Controller Maintenance Manual, pages 21 to 30
Pages 21 to 30 of 160
The original document is the PDF (6.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B553, Modicon B557, AEG B553, Gould B553, Schneider B553, AEG B557, Gould B557 and Schneider B557
Page 21
=~ 13 1 We, ae ee a ey
=. om
1 ‘ ‘ ' 4 ‘ a; 1 t a
TS-80-0004-2
Figure I!-2. Half-Housing Configuration
II-3
Page 22
Table 11-2. Summaryof RequiredAC Power Normal Voltage: Standard Optional Transient
Voltage
Voltage
115V RMS + 30% (80-150V 115V RMS T - 1.00% (0-200V
RMS) RMS)
(Optional): 220V RMS + 30% (160-3OOV RMS) 220V RMS z 100% (O-400V RMS)
Max. 10 seconds Max. 17 m set Line
RMS) RMS)
(Standard):
Max. 10 seconds Max. 17 m set Transient
115V RMS + 15% (loo-130v 220V RMS '7 - 15% (187-265V
1OOV max 500 usec duration, (0.5% max duty cycle)
Spikes:
Frequency: 60 Hz + 5% (57-63 Hz) 50 Hz -7 5% (47.5-52.5 Hz)
Standard Optional
50 Volt-amps min 150 Volt-amps max (depending and peripheral deupon I/O vices connected)
Normal Load:
Recommended Distribution: Transformer
500 Volt-amps (fuse secondary at 5 amps) (3 amp peak ON transient)
On the front of the processor power supply unit are three LED indicators, a memory protect lockswitch, an interface connector, and AC power connections (Figure They are as II-3). follows: 0
LED Indicators The three
LED indicators
The power supply: The controller: The batteries:
II-4 show proper operation
POWER RUN BATT OK of:
Page 23
-S-80,.0005-2
Figure 11-3.Mainframe Controls and Indicators
0
Memory Protect user logic The MEMORYPROTECT lockswitch protects the lockswitch is in from being changed or lost when the normal Items that must change during the ON position. the operation of operation are not included in the MEMORYPROTECT lockswitch.
0
Interface
Connector
The connector next to the indicators is used to concontroller. P.180 the nect the auxilliary devices to this recepCRT Programmer is connected directly to auxilliary devices. no other tacle when used with this connected to when Adapter J470 is receptacle additional peripheral devices are required.
II-5
Page 24
0
AC Power Connections Below the Mainframe Controls and Indicators is supplied AC power is minal board to which 11-4).
a ter(Figure
TS-80-0008-2
Figure 11-4.Mainframe AC Power Connections the power supply Voltage sensing, circuitry is provided in If the AC power is to detect out-of tolerance line voltages. processor may the not within the specifications (Table II-2), when restored Operation will be automatically stop operating. one-scan delay There will be a AC power is within tolerances. this During after a failure. in restoring processor operation time the processor goes through its power-up sequence. 2.1.4 INPUT/OUTPUT (l/O) CHANNELS Each channel. All 484 Controllers communicate with an I/O points channel has a maximum of 128 input points and 128 output points The system can be expanded to 256 input (Figure 11-5). Instrucand 256 output points with the use of the Enhanced II tion Set and a Model 5471 Expander. II-6
Page 25
‘ rs-80~ QOO7-2
Figure 11-5. Typical 484 with Single I/O Channel
(Figure modules Specific I/O circuitry is provided on I/O This circuitry converts various voltages to input/out11-5). put signal levels compatible with the processor. Input/output modules have four circuits each which must be used as either all input or all output. The modules are installed in T/O housings which accomodate up to eight modules of either Usually, eight housings type. are connected to a processor making one complete channel.
2.1.5
INPUT/OUTPUT (l/O) BUS CONNECTOR CABLE
The I/O Bus Connector Cable is connected to the processor Processor board connection locations and to the I/O channel. are found on the right and left top of the processor board (Figure 11-G).
L
Connections on the I/O made on intermediate channel are These connections connectors on each housing (Figure II-7). are shielded in an I/O duct which mechanically connects the I/O eight discrete housings section to the processor. up to I/O can be connected to a single bus cable.
II-7
Page 26
I/O I/O
CON1
CONNECTK)N
/
\
I/O/ CONNECTION
Figure 11-6.Processor II0 Connection Options
TS-80-0009-2
Figure 11-7.Typical II0 Module
II-8
Page 27
2.1.6 l/O MODULE
FUSES AND BUS CONNECTIONS fuses All output circuits (AC or DC) have field replaceable The blown-fuse indicator is viewand a blown-fuse indicator. There is one able from the front of the module (Figure 11-8). To replace fuses the module blown-fuse indicator per circuit. Fuses located on the are must be removed from the housing. Figure II-9 shows bus connections left side of the module. also viewable from the front of the module.
FUSE O ‘ R
TS-80-001 o-2
Figure
11-8. Input/Output
Figure 11-9. Input/Output
Module
Indicators
Bus Connections
Page 28
2.1.7 l/O ADDRESSING
Addressing is done within the channel four the top of each housing is a set of the housing (Figure II-IO).
At at each housing. switches to address
I/O HOUSIN( ADIIRESS SEI,ECTION
TS-80-0012-2
Figure 11-10.Address Selecting of II0 Housings
Any housing can address. One switch is closed to select Within a housing, the eight have any address from one to four. However, since modules can be of any type, input or output. posithere are a maximum of eight housings and only four index tions, two housings can have the same address selected. Any two housings with the same address must have I/O configuration Thus, the in which are opposite from each other. top module if the housings one must be an input and the other an output are addressed the same. The same is true for every module POSition in the housing pair. A channel with four I/O housings can be addressed one to four and I/O modules may be inserted in any order. There is no
II.-10
Page 29
restriction housings, previously relative to the mixing of voltages. Beyond each housing must contain the exact opposite of similarly addressed housing.
four the
2.1.8 l/O FIELD WIRING Field wiring can be instaLled on the housings either I/O installed. However, are for before or after the I/O modules field wiring be the user convenience, it is recommended that The I/O housing address can be installed prior to I/O modules. modules fFigure the readjusted at any time by removing I/O 11-11).
Figure II-1 1. Field Wiring in II0 Housing Conduit
II-11
Page 30
2.2
SYSTEM
INSTALLATION system
The various parts of the MODICON 484 Controller packaged in separate containers as follows:
are
Contents
Container C484
Processor unit
R545/546
Discrete housings
I/O Housing per box).
(up to four
B547/548
Register housings
Housing I/O per box).
(up to four
5540/5541
Input/output
BXXX
Modules Input/output (up modules per box; 4, 8, or 12 carton).
J 471
Discrete
B571/570
Register Multiplexers multiplexers per box).
J470
EIA Adapter.
I/O with power supply.
Duct with
I/O cable. four to boxes per
Expander. (up to four surThe 484 Controller is easily installed on any vertical Each unit has face capable of sustaining its specified weight. mounting shows a typical holes for mounting. Figure II-1 wall prior to bolt-hole This may be used to mark the plan. left of drilling. Input/output housings can be mounted to the below the the processor, or the processor, to the right of processor. A maximum of two locations may be used. Regardless of the location of mounting, no more than 32 inthe processor put and 32 output modules can be connected to Table II-3 summarizes the unless a J471 Expander is also used. installation requirements of the 484 Controller.
II-12