Modicon 484 Programmable Controller Maintenance Manual, pages 41 to 50

Pages 41 to 50 of 160

The original document is the PDF (6.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Modicon B553, Modicon B557, AEG B553, Gould B553, Schneider B553, AEG B557, Gould B557 and Schneider B557

Page 41

MAX.

I .

LEFT LEG

10 ELEMENT%

-3

COILS I

ABCDEFGHI

T MAX 7 RUNGS

RIGHT LEG

J

ANY CONTACTS,

MIX OF RELAY TIMER,

AND ARITHMETIC

COUNTER, ELEMENTS

MAX. 7 COILS (ANY REFERENCE, ANY ORDER)

TS-80-0005-1

Figure 111-3.Multi-Node Program Format

Below each contact is a four digit number that reference to Controller (Refer controls the power flow of the contact. section.) Within a Reference Numbers discussion later in this network, power flow is allowed from left to right or up and down. to left. When It is never allowed to flow from right power is indicated properly displayed on the P18O CRT Screen, images as for all relay contacts by intensifying these contact power is passed from left to right. Model P180 Programming Panel ber of words used for previously displays in real entered logic.

time the num-

Data entered into the controller is entered directly into If power is interrupted before the memory of the controller. is completion of the programming, whatever data already entered assemNo additional processing is required, such as retained. Data entered is sorted for use by the controller. bly of data. deleted, Networks can be totally or partially changed, added or i.nterThis does not at any time with the Programming Panel. coil Any input or output rupt the controller's scan. may be disable feathis tested by simulating inputs or outputs with (Refer to Disable/Enable discussion later in this secture. tion.) able

Pre-formatted through your ladder diagram forms (Form #484-D) local MODICON sales offices. III-3 are avail-

Page 42 read from a scan by OCR; it may hold reading errors

TII-4

Table Ill-1. I/O Reference Configuration

B546

Byte Select

Module Number (Top of Bottom)

Circuit

CHANNEL ONE HOUSING NUMBER

(Strip Select)

Output

Input

Output

TWO

Input Output

THREE

Input

Output

FOUR Input

Upper Byte

0001 0002 0003 0004

1001 1002 1003 1004

0033 0034 0035 0036

1033 1034 1035 1036

0065 0066 0067 0068

1065 1066 1067 1068

0097 0098 0099 0100

1097 1098 1099 1100

0005 0006 0007 0008

1005 1006 1007 1008

0037 0038 0039 0040

0069 0070 0071 0072

1037 1038 1039 1040

1069 1070 1071 1072

9101 0102 103 0104

1101 1192 1103 1104

Lower Byte

0009 0010 0011 0012

1009 1010 1011 1012

0041 0042 0043 0044

0073 0074 0075 0076

1041 1042 1043 1044

1073 1074 1075 1076

N05 0106 107 9108

1105 1106 1107 1108

0013 0014 0015 0016

1013 1014 1015 1016

0045 0046 0047 0048

0077 0078 0079 0080

1045 1046 1047 1048

1077 1078 1079 1080

9109 0110 0111 0112

1109 1110 1111 1112

Second B546 Upper Byte

0017 0018 0019 0020

1017 1018 1019 1020

0049 0050 0051 0052

9081 0082 0083 0084

1049 1050 1051 1052

1081 1082 1083 1084

0113 114 0115 9116

1113 1114 1115 1116

0021 0022 0023 0024

1021 1022 1023 1024

0053 0054 0055 0056

1053 1054 1055 1056

0085 0086 0087 9088

1085 1086 1087 1088

0117 9118 0119 0120

1117 1118 1119 1120

Lower Byte

0025 0026 0027 0028

1025 1026 1027 1028

0057 0058 0059 0060

1057 1058 1059 1060

0089 0090 0091 0092

1089 1090 1091 1092

0121 0122 0123 0124

1121 1122 1123 1124

: ANMSTILANMSANMALANMSHANMALANMTA ANMATANM a

0029 0030 0031 0032

1029 1030 1031 1032

0061 0062 0063 0064

1061 1062 1063 1064

0093 0094 0095 0096

1093 1094 1095 1096

0125 0126 127 0128

1125 1126 1127 1128

Page 43

3.1.2

CONTROLLER REFERENCE NUMBERS

Four-digit reference numbers are used to build user's logic throughout the proqramming of any 484 Controller. These references are divided into two broad categories: discrete and reused for individual Discrete references are items gisters. that can be ON or OFF. These items include limit switches, relay contacts, motor starters, relay coils, and pushbuttons, solenoid valves. Register references are used to store numervalues, and the ical values such as counters, timers, analog like. All register references are three BCD digits long (maximum 999). Only five types of references are required to program a 484 Any specific reference can be used as many times Controller. as needed by a particular application. There are no limits other than memory availability. References are identified as follows:

OXXX-coilsjdiscrete outputs lxxx-discrete inputs 2XxX-sequence steps 3XxX-input registers 4XxX-holding registers/ output registers

Available only with enhanced capabilities

The address of each I/O housing (Section II of this manual) establishing is very important in references. Table proper III-1 defines the exact reference for each I/O module installed in channel one. Similar numbering is used for channel two, with each reference increased by 128. 3.1.3

SCAN interThe 484 Controller examines (solves) each network of sequence. Network connected logic elements in their numerical This is One is the first network to be solved on each scan. available all followed by network Two, Three and so on until network The controller then goes back to networks are solved. This solving each network. One and solves it and continues typically from fixed scanning occurs at a very rapid speed, the The scanning begins from four to 20 milliseconds per scan. removed. time power is applied to the processor until power is solved by columns Within each network, logic elements are all located, are from the left rail to the right rail where coils and from top to bottom within each column. The result of each network scan is It makes no all following networks. state or coil result is a change in order Networks are solved in value. quence number and not by the reference coil. III-5 immediately available to this difference whether numerical in a change numerical setheir of to any number assigned

Page 44

The time All inputs and outputs are updated once per scan. the netfrom solving any individual network on one scan until time" work is solved again on the next scan is called the "scan depending upon the varies The scan time of the controller. increase with Typical scans amount and type of logic entered. memory size (Table 111-2). Table 111-2.484 Memory Configurations

Model 484

Typical Memory Elements (8 Bit (Contacts (Words) & Coils)

Maximum I/O Inputs

Outputs

Internal coils

Balding Reg.

Typical Scan Time (M Set)

01

256

100

64

64

64

62

4

02

512

200

64

64

64

62

6

03

1024

400

128

128

128

126

8

04

2048

800

192

192

192

190

12

05

4096

1600

256

256

256

254

20

06

8192

3200

256

256

256

318

40

3.1.4

MEMORY PROTECT

The 484 Controller is provided with a Memory Protect hardaccidental or unauthorized ware feature designed to prevent changes to the memory. When the MEMORYPROTECT keylock switch (Figure 11-3) is placed in the ON position, the user's logic Programcannot be altered by any external device, such as the Inor Computer ming Panel, Tape Loader, Telephone Interface, terface.. Thus, by placing MEMORYPROTECT ON and removing the Panel to Programming key, maintenance personnel can use the changes. make unauthorized monitor the system but they cannot Only specific personnel who are provided access to the key can change the system. The Memory Protect feature does not protect those that normally change such as registers and I/O status.

3.1.5 elements

DISABLE/ENABLE built-in feature in all The Disable function is another the checkout and mainThis feature simplifies controllers. The Disable status may be changed tenance of a control system. coil selected only when the MEMORYPROTECT is OFF. Any logic III-6

Page 45

by the CRT cursor may be disconnected from its logic by depresthe coil was sing the DISABLE pushbutton (Figure 111-17). If the coil will remain OFF when the pushbutton was depressed, remain ON. To re-enable a If the coil was ON it will OFF. logic coil, the DISABLE pushbutton is depressed a second time while the cursor is under that coil. When DISABLE is operating the coil disabled is no longer user via the controlled by the operator or CRT Programming Panel. The coil can be toggled ON/OFF/ON/OFF by consecutivelv depressing the FORCE pushbutton (Figure 111-17). When disabled, the logic coil, all references to this coil driven from the in the ladder diagram, and any outputs coil Internally will be affected by the Disable function. programre-establish med logic remains in the controller and will control when the coil is enabled. The internal logic is completely by-passed for the coil because of the DISABLE function. until changed The disable status for any coil is permanent by a programming device. New networks can be displayed, other MEMORYPROTECT turned ON, or coils disabled, power interrupted, any other change made to the system but the disable status of a coil does not change. A programming device must be used to change the disable status of any coil. CAUTION THE USER MUST TAKE CARE NOT TO CREATE UNSAFE CONDITIONS WITH MACHINE OPERATIONS BY USING THE DISABLE FUNCTION. ALL COILS DISABLED SHOULD BE RETURNED TO THEIR ORIGINAL STATE PRIOR TO REMOVING THE DISABLE FUNCTION. Discrete inputs can also be disabled in a manner similar to is placed in the reference The selected input logic coils. inarea by the GET command. Then the cursor is placed on the This action reput and the DISABLE pushbutton is depressed. world real and assigns the moves control of that input from Panel. via the CRT Programming that control to the operator logic this that uses The input can be forced ON or OFF. All discrete input will now respond to the disable status and not the real world. The disable status is permanent and may be altered only bv programming devices with MEMORYPROTECT OFF. At any one time, as many logic coils and discrete inputs as desired can be disabled each ON or OFF. NOTE all Since the disable status is permanent, a record of disabled logic coils and inputs should be kept so that show A ladder listing will they can be enabled later. the disable state of any logic or input. III-7

Page 46

verify the proper may be used to The disable function inputs. Each output is wiring and operation of all discrete displayed in‘a network on the CRT Programming Panel and then disabled. The coil can be cycled ON/OFF/ON/OFF and so on, so St is observed. that the operation of the discrete device is enabled before the recommended that the logic coil checked be undesirable disable statuses next output is tested to prevent from occuring. to operate profails If an input such as a limit switch the its effect can be temproarily simulated by disabling perly, This is input and forcing it to the required state, ON or OFF. input is preventing the control the particularly useful if system from functioning.

3.2

BASIC PROGRAMMING capabilitv of the All 484 Controllers are provided with function of the relays, simulating being programmed and of basic done on the timers, and counters. All programming is format of up to ten elements in each horizontal row or rung and form a network. up to seven of these rungs connected together seven rungs or up to two A network can be a single rung, elements of the There must be some connection between rungs. This connection may be as simple as the left leg of each rung. seven coils. the ladder diagram. Each network may have up to the right of Coils are shown on the CRT screen at the extreme rungs of the network. number These coils may be assigned logic coil any valid numbers can be used available in the controller. Logic coil storonly once. The quantity of logic coils, discrete inputs, (Table depends upon memory size age locations and the like, 111-2). 3.2.1

RELAYS

The basic programming element possible relay contacts available is contact. the relay are shown in Figure 111-Q.

The occurs Contacts cannot be placed vertically. Power flow only form the left leg towards the right or vertically up or down. Power flow is not the reverse direction. possible in the controls Below each contact is a reference number that power flow of that contact.

III-8

Page 47

Without Normally

Open:

Normally

Closed:

With Vertical

Vertical

-It-

-It-T TS-80-0008-1

+k-

Figure 111-4.Relay Contacts

With and Without

Verticals into divided references Logic coils (0XxX references) are comthat can be used to control discrete outputs or to provide pletely internal references as follows: Output Coils Internal Coils

0001-0256 0258-05.12 NOTE

Internal coil 0257 is an internal indicator of battery voltage This reference is ON as long as the voltage. retention of in the batteries is sufficient to ensure their capacity reduce memory. Whenever the batteries to a minimum level coil 0257 will de-energize and the This is a BATT OK LED will extinquish (Figure 11-2). be able warning level only. The batteries will still AC to maintain memory for at least seven days without power. Any output or internal logic coil can be used as a coil only once. References to contacts controlled by a coil can be used as many times as required. There is no limit to how many times any reference is used in a program. coils output that are not used to drive discrete outputs can still be used as coils in programming. Therefore, any unused output coils can be used for internal functions exactly as internal coils are used. An example of Relay Logic is shown in Figure 111-5.

PERMISSIVE

SAFETY

TS-80-0007-1

Figure 111-5.Relay Logic Example

III-9

Page 48

If the logic (Figure 111-5) was implemented in the 484 Concirinput to troller the control elements must be connected assigned. outputs and the I/O configuration Any cuits in may be used. level voltage the proper available inputs of and assignments assumed input the illustrates Figure III-6 the operate assigned to Output number 12 is wiring details. conthe The internal logic programmed into external device. troller may be seen in Figure 111-7.

1006

0

1010

SAFETY 1 l-0

1027

OVERLOAD TS-80-0008-l

ASSUMED INPUT CONNECTIONS

ASSUMED OUTPUT CONNECTIONS

Figure 111-6.Assumed II0 Wiring Logic in Figure Ill-5

TS-80

Figure 111-7.484 Program Equivalent To Assumed I/O Wiring In Figure Ill-6

Page 49

3.2.2

LATCH ES

Any logic coil can be latched so that it is returned to its previous state (ON or OFF) after a power failure. This is similar to a latching relay. Therefore, if a latched coil is ON and power is lost, it will return to ON state when power is restored regardless of how long the power was off. If the coil was OFF, it will remain OFF when power is restored. All logic coils that are not latched will be de-energized when power iS restored. All logic coils are latchable. If the logic coil in Figure III-7 were latched it would be programmed as such and displayed on the CRT Screen (Figure 111-8).

,0019-2

Figure 111-8. 484 Latched Coil Program

3.2.3

EXTENDED LOGIC

If more than ten elements are required in a rung to- satisfy may be used to coil a complex control function, an internal this coil A contact referenced to represent a partial result. network. Addiis then placed as the first element in another The coil tional contacts are entered into the second network. the reof the second network can be an output that represents elements or an internal sultant logic of up to 19 series of number of the The only limit to coil for further extension. times the logic can be cascaded like this is established by the with Internal coils can be used memory size of the controller. to be logic up to ten elements to represent a single block of logic may be An example of extended repeated in the program. seen in Figure 111-9.

III-11

Page 50

TS-80 -002 1-2

Figure 111-9.484. Extended Logic Program

3.2.4

TIMERS

Timers can be placed anywhere in a network where sufficient space exists. Timers are built vertically and require two elements, one on top, the other on the bottom (Figure 111-10).

CONTROL -1

‘;y;E(

I RESET

TXXX

I-

OUTPUT

I

CURRENT TIME

OUTPUT

TS-80-0009-1

Figure 111-10.Timer Format

Within all 484 Controllers are three crystal-controlled clock signals that drive all timers. Any timer can be programmed to respond to either the second clock, l/10-second clock, or l/100-second clock. There is no limitation on which or how many timers are referenced to any of the three clock signals.

III-12