Modicon 484 Programmable Controller Maintenance Manual, pages 51 to 60

Pages 51 to 60 of 160

The original document is the PDF (6.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Modicon B553, Modicon B557, AEG B553, Gould B553, Schneider B553, AEG B557, Gould B557 and Schneider B557

Page 51

control There are two nodes for entry of relay contact type The upper node controls when the to the left of the timer. time timers accumulate time. The lower node controls when the is reset to zero. The timer is enabled when the lower node reIt resets when no power flow is available. ceives power flow. preset contains the value The upper element of the timer which limits the maximum value of the timer. This preset may to 0999). These digits be fixed value of three digits (0001 represent up to 999 seconds, or up to 9.99 seconds. The timer can never exceed this preset value. location within the The lower element refers to a storage In the center of controller where the current timer is stored. parthe timer is a display to indicate the rate at which .that TO.1 = ticular timer is programmed to operate (T1.0 = seconds, tenths of seconds, and T.O~ = hundredths of seconds). logOn the right of the timer are two nodes from which the These nodes will proical output of the timer are available. programmed to the vide power to any contact, shunts, or coils right of the timer. its The upper node provides power only when the timer is at receiving stops This output is de&energized and preset value. stops. No the timer When this output is energized power. further accumulating of time beyond the preset is possible. NOT at The lower node provides power whenever the timer is stops passing power only when the This output its preset. timer is at its preset. uppe.r node to The timer will accumulate time whenever the can be turned signal The upper receives power. the left accumuON/OFF/ON as many times as necessary and the timer will Each late how long the signal was ON up to the preset value. be accumutime the upper node is re-energized, time begins to lated from its previous value held in the storage location, regardless of how long the signal was OFF. lower They are reset only by the Timers are accumulative. stored information completely node signal. They retain their de-enerWhenever the reset signal is during power failure. regardless of the time value, the timer will be reset to gized, re-enIt holds at that value until the reset signal is zero. ergized. The number entered into the lower element of the timer be a storage register (reference 4XxX) wherein the current is stored.

must time selected register each timer has its own holding Normally, with by the user. Thus, the maximum number of timers available Do not each memory size is the quantity of holding registers. more than for location use a holding register as the storage one timer. III-13

Page 52

3.2.5

COUNTERS conCounters operate the same way as timers except for the count by one current The counter increments its trol node. on this whenever the control signal goes from OFF to ON. Only positive transition, OFF to ON, is the count incremental. enable/reset of the The lower left node controls the the counter is Whenever this signal is de-energized counter. signal is again reset to zero. the This count is held until 999, is The number of events to be counted, up to energized. current The the counter. entered into the upper element of lower the count is stored in a holding register identified in be used to element of the counter. Separate registers should Do not store the current time or count of each timer/counter. share holding registers between timers and counters. current The output of the counter is energized whenever the value. the preset stops at Counting count equals preset. Whenever the counter is reset to zero via the lower node on the The current count is releft side, the coil is de-energized. tained during the power failure since it is stored in a holding Counters also have a second output register (reference 4XxX). that provides power flow as long as count is NOT at its preset. 3.2.6

CASCADED COUNTERS/TIMERS interconnected or Timers and counters can be cascaded Figure III-11 shows a cascade satisfy any required logic. time measuring timer and counters to produce a calendar seconds, minutes, and hours.

TS-80-0022-2

Figure 111-l1. Sample Timer/Counter Cascaded Logic

III-14 to of in

Page 53

installed Any 484 Controller can be equipped with a factory addition to reoption that provides extended capabilities in without available This option is and counters. timers, lays, this opFeatures that are included in regard to memory size. tion and discussed in the following paragraphs, are as follows: 0 0 0 0 0

3.2.7 subtract, operations Arithmetic (add, divide). Register Input/Output. Transitional Contacts. Eight separate sequencers. BCD Convert (Discrete Inputs-to-Register; Discrete Outputs). ARITHMETIC multiply,

Register-to-

OPERATIONS standard arithmetic operations: all This option provides and division. Each multiplication, subtraction, addition, arithmetic element has control input (ENABLE line), holding reThe arith111-12). gisters, and up to three outputs (Figure metic operation is performed on every scan of the controller in can be The outputs which power is applied to the ENABLE line. appliother function blocks, or coils as the tied to contacts, cation requires.

I

OUTPUT c

REGISTERS

TS-80-0010-1

1

OUTPUT

2

OUTPUT

3

Figure 111-12. General Format for Arithmetic Option ii

- the middle value to The ADDITION function adds the upper referenced holding lower the in value and places the result register. than greater If the result of an add function is a. value digits maximum value the holding register can store (three register of the result that will fit into the 999), the portion the reif 850 is added to 325, For example, is placed there. The value 175 (three least significant digits of sult is 1175. eneroutput result) is placed in the holding register and the output 1 is Only gized to indicate an overflow has occurred. III-15

Page 54

functional with when energized.

addition, and always indicates the value

1000

The SUBTRACTION function provides one of the most versatile function, this With tools available to the control designer. any holding in the designer can compare two numbers located operations with one of the register and control subsequent set point three outputs. can be used for Thus, this function functions, dead band funccontrol of analog loops, alarming tions, etc. The format for subtraction is as follows: OUTPUTS:

than middle 1 is ON if upper value is greater value. 2 is ON if upper value is equal to middle value. 3 is ON is upper value is less than middle value.

The outputs can be tied together so that a "greater than or function can be logical equal to" or "less than or equal to" performed. that is, The outputs are mutually exclusive, only The to the enable. one will be energized when power flows will always holding register referenced in the lower element operasubtraction contain the absolute numerical value of the tion (i.e., the difference of the two numbers). and a values are multiplied In MULTIPLICATION, two 3-digit 6-digit product is obtained. Double precision accuracy is a valuable feature of the multiplication function. The register referenced in the lower element is in reality two consecutive registers, the one named and the next one. The one named will contain'the three most significant digits of The the result. through output coil will be ON as long as there is power flow the Enable contact. In DIVISION, a double precision number (up to 999999 in two consecutive registers) can be divided by a fixed number or by a register content. funcThis capability allows following the tions to be performed: 0 0 0 0

Scaling of analog signals to engineering Controlling ratio. Solving of formulas. Splitting register contents.

The format for division

OUTPUTS:

1 is ON if value. 2 is ON if 3 is ON if units.

is as follows:

upper value is greater than upper values is equal to middle upper value is less than middle middle value. value.

The output represents successful division or results of ila result legal division such as dividing by zero or obtaining greater than one register can hold. III-16

Page 55

3.2.8

REGISTER l/O

Register I/O provides the capabilitv of handli,ng numerical values in the I/O structure. These numerical values can be both received from an external source (input registers) and driven to an external destination (output registers). Each register includes a three-digit quantity, values from 000 to 3001 to There are 32 input registers assigned references 999. 3031 and 32 output registers, references 4001 to 4032. The connected to input registers receive their values from devices from the I/O structure and can be only referenced, not altered, special registers are the controller. The output within holding registers (references 4001-4032) that can perform the dual purpose of storing (holding) numerical values as well as driving them to the outside world.

3.2.9

TRANSITIONAL

CONTACTS

In addition to the conventional normally open and normally 484 Controllers, with all closed contacts that are available provide transitional the Enhanced Instruction Set options also Transitional contacts can be used contacts (Figure 111-13). anywhere in networks where the more conventional NO and NC concontransitional These tacts had previously been utilized. signal the tacts will pass power for exactly one scan whenever is transitioned from either OFF to to which they are referenced selected. depending upon transitional ON or ON to OFF, type inter(output or to any input or coil They can be referenced to sequencer steps. nal) but cannot be referenced TRANSITIONAL TYPE

CONTACT

SELECTED

SYMBOL

OFF REFERENCE r i‘

OFF

TRANSITION

I

1 CLOSE

CONTACT

POWER

,

FLOW

Figure 111-13. Transitional Contacts III-17

CLOSE

Page 56

These contacts respresent a "one shot" necessary when performing a function (e.g., division) only once. 3.2.10 sometimes which is multiplication or

SEQUENCERS

Each are provided. sequencers Eight independent 32-step sequencer operates similarly to a stepping switch with a single the stepping specific reference energized at each position of form 2 in the These references start with the digit switch. three digits of the The significance of the remaining 2xxx. reference is as follows: YSequencer No. (1 through 8) xx - Step Number (1 through 32) values placed in by mumerical Sequencers are controlled funcspecific registers (4051 to 4058) by any of the non-relay or any arithmetic operations. A tions such as counter, timers, that value of zero or above 32 will result in all references to Values between one and 32 will sequencer being de-energized. other and all result in that single reference being energized references to that sequencer being de-energized (Figure 111-14).

2301 a2302

231200

0 0 0 11

2311 0012

CNT

2310

4053

2309

3

T 4053

10

9

2300

0 0 0 6

0 00 6

7

4

5

2303

2304

2305

2306

2307

TS-80-0012-1

Figure 111-14.Twelve-Step Sequencer and Equivalent Circuit count The counter has a preset of 12 and stores its current the 1047 is energized, time input in register 4053. Every equivaThis is value in register 4053 is incremented by one. If register lent to moving the stepping switch one position. III-18

Page 57

(third sequencer, 4053 contains the value five, reference 2305 step five) is energized. When the current count equals the with reference 2312 the stepping switch stops preset (0012), energized. Whenever coil 0031 is energized, the counter is goes back to home (no reset to zero and the stepping switch regardless of its current count, references energized); intermediate references are not energized. Each sequencer is completely independent since it is controlled by separate register values. Sequencer references can be used as often as necessary, anywhere in the logic where relay contacts are appropriate. By using calculate logic, any sequencer can be made to skip steps and jump forward or move backwards as necessary; intermediate references are NOT enerSequencers references are updated as soon as a change gized. in the content of a sequencer register is changed. Thus, one network can drive the sequencers, and the next network use the most recent value of the sequencer references. Sequencer references cannot be used on transitional contacts.

3.2.11 BCD CONVERT The BCD CONVERT function allows discrete (ON-OFF) modI/O regisCoded Decimal) ules to be referenced as a BCD (Binary inter. This is, if it is desired to wire a thumbwheel switch put into a set of discrete input modules, the BCD CONVERT function will allow these 12 inputs to be used as a numerical value a if it is desired to connect Conversely, in the controller. discrete output modules, of the BCD LED display to a set data) CONVERT function will allow a holding register (numerical to be transmitted to a display.

3.2.12 ENHANCED II INSTRUCTION SET OPTION tion

InstrucThis instruction set is similar to the Enhanced I option and has the same capabilities, plus the following: 0

0 0 0 0

3.2.13

Binary convert (discrete inputs-to-register; to-discrete outputs). Register-to-table move. Table-to-register move. SKIP and BY-PASS I/O. MODBUSCommunication Interface.

register-

BINARY CONVERT now This function is similar to the BCD CONVERT except that data as numerical the input and output modules do not receive bits This BINARY data is in the form of such, but BINARY data. done Conversion is (ones and zeros) contained in a register. with ten bits. III-19

Page 58

discrete The BINARY CONVERT function allows the transfer of binary the inputs to be made to registers, and the transfer of bit pattern of registers to be made to discrete outputs. example, a known This capability is very useful when, for or bit pattern is desired to be outputted upon reaching a step could be O=de-energize) (l=energize; The bit pattern cycle. the output upon held in a register and then simply moved to When a new step is reached, a different acutation of a cycle. register and transbit pattern can be retrieved from another ferred to the output modules. may In a similar fashion, the status of inputs into the controller and stored as bits in a register. for be a method for setting different bit patterns status discussed previously.

3.2.14 be brought This may the output

MOVE FUNCTION contents) The MOVE function allows numerical data (register to another on command. These to be moved from one register source functions allow a table to be utilized with recipe or to be retained and examined at a later data, report information and data time, errors stored in the order they were detected, with structure the to be multiplexed through the discrete I/O BINARY CONVERT operation. found in the The concept is similar to the MOVE codes MODICON Model 184 and 384 Controllers which have made them so somewhat different. powerful. The implementation, however, is different values The MOVE function can be used for presetting in timers and counters, doing comparisons, etc. The MOVE in the 484 Controller is a form of INDIRECT takes the form of a block ADDRESSING. The function with two register references in it; a TO register on the bottom and a FROM register on the top (Figure 111-15).

ENABLE I] T+R

1 FROM) OR R+T 4xxx

TS-80-0013-1

Figure 111-15.MOVE Format III-20

(TO)

Page 59

The FROM register may be an input register 13XxX) such as a thumbwheel input or a holding register (4XxX). The TO register must be a holding register. A discussion of the two MOVE functions (i.e., Table-to-Register and Register-to-Table) follows. 3.2.15 TABLE-TO-REGISTER

MOVE

Similar to the T+R Move, the R+T Move allows the loading register whose conof a table of registers from one central receives tents are changing. When the ENABLE signal power bottom register will lock at the flow, the R+T function (TO) be changed. The upper content to determine the register to this be placed in the value to register (FROM) content is register and thus alter its content. ENABLE 4100

EXAMPLE:

T+R 4001

In either MOVE function, it Manual and 484 Application Notes typical applications.

If 4100 contains the value 43, register 4043 (4000+043) will have its content transferred to register 4001.

recommended is be reviewed for that the operation

484 and

ENABLE EXAMPLE:

4095

R+T 4120

3.2.16

If 4120 contains the value 225, register 4225 (4000+225) will be loaded with the content of register 4095.

SKIP set of The SKIP function allows a designated network or This the controller. networks to be "skipped" by the scan of that required effectively reduces the potential scan time from required by the minimum monito solve all networks to that timer times toring logic until a certain event happens (e.g., achieved, limit switch activated, level out, set point reached, etc.). 3.2.17

BY-PASS I/O

BY-PASS I/O allows unused I/O Similar to the SKIP function, the scanning function. and not serviced in to be "by-passed" register Portions of both the discrete I/O as well as the I/O III-21

Page 60

can be by-passed with separate user controlled savings is 7 msec on the scan time.

limits.

Maximum tools, Because SKIP and BY-PASS functions are very powerful their use should be considered only by those designers that are totally familiar with the 484 Manual and its precautions. Using both SKIP and BY-PASS I/O, the 484 can be operated at a minimum scan time of 1.5 msec. 3.2.18 MODBUS COMMUNICATION

CAPABILITY unit interface that Combined with a MODBUScommunications the communication attaches the controller to a MODBUS system, the capability to Enhanced II Instruction Set Option includes details For respond to commands received from a remote master. refer to MODICON MODBUS System on configurations and features, User's Manual.

3.3

USE OF P180 CRT PROGRAMMING PANEL

TS-80-0023-2

Figure 111-16. Pl80 CRT Programming Panel

3.3.1

INTRODUCTION

The most commonly used programming device is the P180 CRT provides the This device Programming Panel (Figure 111-16). proprimary human-machine interface that determines how the keyboard The programming panel is small, cessor will be used. portable, and ruggedly built. III-22