CERI Installation and Programming Manual: 7 Front Panel Operation
Pages 92 to 96 of 122, from CERI Installation and Programming Manual
The original document is the PDF (1.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the AEG DEP-210
Page 92
7
Front Panel Operation
Keypad The keypad includes the , , , , and buttons. In general, the button moves to the left and also acts as an “escape” key to move back one menu level. The button moves to the right and also moves down one menu level. The up and down buttons increment and decrement numbers and step up and down menu lists. The button acts as an “enter” key.
Splash Screen The CERI splash screen shows the Nameplae (defaults to CERI when empty), IP Address (206.223.51.190), the operating mode (CONFIG, RUN, HALT), the controlling Master number (-,1,2,3,4), and error messages.
Backlight The backlight will illuminate on any key press and will also flash on an error condition. The timeout for the backlight is configured through Modbus drop 255 register 7003 and defaults to 300 seconds.
Main Screen Pressing the , , , or buttons from the splash screen will lead to the “Main” menu page. Use the or keys to choose the sub-menu. The or will drill down into the next menu level while the key will back up to the splash screen.
CERI Manual
95
Page 93
Config Screens The Config screen allows the adjustment/viewing of the communications parameters, NamePlate, and Display settings.
NOTE: The IP Mask automatically increments/decrements the bit mask using the UP/DOWN keys. NOTE: The IP Source includes: Fixed, DHCP, and BOOTP.
NOTE: The serial port is fixed as a Modbus RTU Slave. The baud rate and parity are adjustable. The data bits are fixed at 8 and stop bits are fixed at 1. The CERI responds to Modbus RTU messages to slaves 0, 1, or 200, 201, 202, and 255. The RTU Address page allows the user to adjust the drop number for the virtual PLC memory from 200 to another number within the range 1-200. See Chapter 9 for more information.
96 Front Panel Operation 7
CERI Manual
Page 94
Note: Select the “<” character to backspace. Only capital letters A-Z, numbers 00, and underscore “_” are allowed in the nameplate. Press the key while not on a “<” character to accept the nameplate and return to the previous screen.
NOTE: The Contrast value may be adjusted between 240-300.
Mode Screens
NOTE: The Mode values are Run, Config, and Halt. “Run” is a read-only configuration setting. Configuration values may be altered in “Config” or “Halt”. The CERI must be in “Halt” to load new firmware. The A120 outputs are all forced to default conditions while in “Halt”.
CERI Manual
7 Front Panel Operation 97
Page 95
Status Screens
NOTE: The Stats screens may have multiple pages that are accessed using the up and down keys. Press the Enter key to return to the previous menu. NOTE: The Backplane WatchDogs counter indicates the number of times that the controlling master has been lost and the watchdog timer has expired causing the A120 I/O to revert to the default values.
NOTE: All Stats values are zeroed on a power cycle.
Info Screens
98 Front Panel Operation 7
CERI Manual
Page 96
System Screen
NOTE: Pressing the or keys while “Reboot” is selected will cause an immediate reboot of the CERI. This will cause a loss of control of the A120 I/O.
NOTE: Selecting “Defaults” will result in the loss of all configuration of the CERI with a return to factory default settings.
NOTE: Selecting a password of a number greater than 0000 will cause the user to enter this password on any parameter change through the front panel. The value 0000 will disable the password feature. NOTE: This password is not the same password used by the Web server.
CERI Manual
7 Front Panel Operation 99