CERI Installation and Programming Manual

Manual122 pagesPDF 1.9 MB

Installation and programming manual for the Niobrara CERI Ethernet interface for A120 I/O, with register maps for modules such as the DEP 210.

What this file really is

The old site listed this file as a manual for the AEG DEP-210. This is not a manual for the AEG DEP-210 itself but the Niobrara CERI Ethernet interface manual, which includes the DEP 210 among the A120 modules it supports.

Download the PDF1.9 MB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Niobrara's manual for the CERI Compact Ethernet Remote Interface, a module that replaces the Modicon Compact PLC CPU and turns A120 Series I/O into distributed Ethernet I/O controlled over Modbus/TCP. It covers installation, the built-in web server, rack configuration, the data mapper, register maps for each supported A120 module (including the DEP 210 8-point 115 Vac discrete input), front panel operation, the register list and virtual PLC memory.

Its parts

  1. Introduction
  2. Installation
  3. Web Server
  4. Rack
  5. Mapper
  6. A120 I/O
  7. Front Panel Operation
  8. Register List
  9. Virtual PLC Memory

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

The CERI Installation and Programming Manual (Niobrara Research & Development, effective February 11, 2011) for the CERI Compact Ethernet Remote Interface, a module that replaces a Modicon Compact 984 PLC CPU so A120 Series I/O can be run over Modbus/TCP. The DEP 210 8-point 115 Vac input module appears only as one of the many A120 modules whose register layout the CERI maps. The manual covers installing the CERI, its web pages, rack and mapper setup, front panel screens and a virtual PLC memory for older serial HMIs.

Read for this summary: pages 1 to 2, 10 to 23, 35 to 36, 41, 82 to 83, 92 to 96 and 106 to 107 of 122.

What the CERI is
Compact 984 compatible module that replaces the Compact CPU to make A120 I/O Ethernet I/O over Modbus/TCP p. 11
Mounting
Double-width, slots 1 and 2 of the DTA 200 processor rack; up to three DTA 201 or DTA 202 expansion racks p. 11
Power
24Vdc in; built-in 2.5A supply feeding 5Vdc to the A120 racks p. 11, 17
Ethernet
RJ45, CAT5, 10/100MB FD/HD, automatic cross-over p. 15, 20
Serial port
Port 1, RJ45 RS-232 with Compact CPU pinout; Modbus RTU slave, default 9600,E,8,1 p. 17, 93
IP address source
Fixed, DHCP or BOOTP p. 93
Indicators
Power (green), Overload (red), LINK (green), 10/100 (amber), serial TX and RX p. 17, 18, 20
Front panel
LCD screen and keypad for setup, mode, status and info screens p. 14, 92
Mapping capacity
Up to 50 mapper entries shared between 18 rack entries and at least 32 internal entries p. 41
Software
CERI_SETUP.EXE with manual, ceri.fwl firmware, FWLOAD.EXE loader and NRDTOOL.EXE register viewer p. 16
DEP 210 mapping
DEP 210, 8-point 115 Vac input: one 4x register (In-0), bits 8-15 unused; Modicon module ID x10 (16) p. 83
Modbus slave addresses
255 setup registers; 0 or 1 Compact I/O data; 200, 201, 202 virtual PLC p. 107
Virtual PLC memory
Mimics the 0x, 1x, 3x and 4x memory of the old PLC so an existing serial HMI keeps working p. 106

What this manual walks you through

  • Installing the CERI in place of the Compact CPU p. 14
  • Setting the IP address from the front panel p. 14
  • Connecting a PC and opening the CERI web pages p. 15, 22
  • Updating the CERI firmware with FWLOAD p. 20, 21
  • Configuring A120 modules on the rack page p. 35, 36
  • Setting up mapper entries, modes and packing p. 41
  • Using the front panel keypad and screens p. 92, 93, 94, 95, 96
  • Keeping an old serial HMI with the virtual PLC memory p. 106, 107

Good to know

  • Many A120 cards share one module ID, so the CERI cannot always tell which card is fitted; the user selects it. p. 36
  • Loading new firmware may return the CERI to factory defaults; back up the configuration first. p. 20
  • Set the power switch to OFF when adding or removing A120 cards. p. 17
  • In Halt mode all A120 outputs are forced to their default conditions. p. 94
  • Rebooting from the System screen causes a loss of control of the A120 I/O. p. 96

Questions this manual answers

Is this a manual for the DEP 210 module?

No. It is the manual for the Niobrara CERI Ethernet interface; the DEP 210 appears only as one A120 module whose inputs the CERI maps into one 4x register. p. 83

How is a DEP 210 read through the CERI?

Its 8 inputs sit in one 4x register (In-0); bits 8-15 are not used. p. 83

How do I replace a Modicon Compact 984 CPU with Ethernet?

The CERI fits in slots 1 and 2 of the DTA 200 rack in place of the Compact CPU and serves the A120 I/O over Modbus/TCP. p. 11, 14

What power does the CERI need?

24Vdc, like the Compact PLC; it supplies 5Vdc to the A120 racks from a 2.5A supply. p. 11, 17

Can an old serial HMI stay connected after replacing the Compact CPU?

Yes. The CERI's virtual PLC memory answers the HMI's Modbus RTU requests on its RS-232 port, at slave address 200 by default or one set to match the old PLC. p. 106

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1 Introduction11
  2. 2 Installation14
    1. Module Installation14
    2. Software Installation16
    3. Power Supply17
    4. RS-232 Serial Port17
    5. Ethernet Port20
    6. Updating the CERI Firmware20
  3. 3 Web Server22
    1. Main Page22
    2. Login23
    3. Statistics32
  4. 4 Rack35
  5. 5 Mapper40
    1. Mapper Description41
    2. Mapper Examples42
  6. 6 A120 I/O56
    1. ADU 204 (4-point Voltage/RTD Analog Input)56
    2. ADU 205 (4-point Voltage/Current Analog Input)56
    3. ADU 206 (4-point Voltage/Current Isolated Analog Input)58
    4. ADU 210 (4-point Voltage/Current Analog Input)59
    5. ADU 211 (8-point Universal Isolated Analog Input)60
    6. ADU 212 (8-point Universal Isolated Analog Input)62
    7. ADU 214 (8-point Non-Isolated Analog Input)64
    8. ADU 216 (8-point Thermocouple Isolated Analog Input)64
    9. ADU 254 (4-point Voltage/RTD Analog Input)65
    10. ADU 256 (4-point Voltage/Current Isolated Analog Input)66
    11. ADU 257 (8-point mV/RTD/TC/Resistance Analog Input)68
    12. BKF 201 (Interbus S Master)69
    13. DAO 216 (16-point 24Vdc Non-isolated Discrete Output)70
    14. DAP 204 (4-point Relay Discrete Output)70
    15. DAP 208 (8-point Relay Discrete Output)70
    16. DAP 210 (8-point 24..240 Vac Discrete Output)71
    17. DAP 211 (Monitored 4-point Out Combined I/O)71
    18. DAP 212 (8-point In/4-point Out Combined I/O)71
    19. DAP 216 (16-point 24Vdc Discrete Output)72
    20. DAP 217 (16-point 5-24Vdc Discrete Output True Low)72
    21. DAP 218 (16-point 24-249Vac Discrete Output)72
    22. DAP 220 (8-point In/8-point Out Combined I/O)73
    23. DAP 250 (8-point In/8-point Out Combined I/O)73
45 more lines, from page 74 on
  1. DAP 252 (8-point In/4-point Out Combined I/O)74
    1. DAP 253 (8-point In/4-point Out Combined I/O)74
    2. DAP 258 (8-point Relay Discrete Output)75
    3. DAP 292 (8-point In/4-point Out Combined I/O)75
    4. DAU 202 (2-point Voltage/Current Analog Output)76
    5. DAU 204 (4-point Voltage/Current Analog Output)76
    6. DAU 208 (8-point +/-10Vdc Isolated Analog Output)80
    7. DAU 252 (2-point Voltage/Current Analog Output)81
    8. DEO 216 (16-point 24Vdc Non-Isolated Discrete Input)81
    9. DEP 208 (8-point 230Vac Discrete Input)82
    10. DEP 209 (8-point 120Vac Discrete Input)82
    11. DEP 210 (8-point 115 Vac Discrete Input)83
    12. DEP 211 (8-point 115 Vac Isolated Discrete Input)83
    13. DEP 214 (16-point 10-60Vdc Discrete Input)83
    14. DEP 215 (16-point 5Vdc TTL True Low Discrete Input)84
    15. DEP 216 (16-point 24Vdc Discrete Input)84
    16. DEP 217 (16-point 24Vdc Discrete Input)84
    17. DEP 218 (16-point 115VAC Discrete Input)85
    18. DEP 254 (16-point 10-60Vdc Discrete Input)85
    19. DEP 256 (16-point 24Vdc Discrete Input Extended Temp.)85
    20. DEP 257 (16-point 110Vdc Discrete Input)86
    21. DEP 296 (16-point 60Vdc Isolated Discrete Input)86
    22. DEP 297 (16-point 48Vdc Isolated Discrete Input)86
    23. MOT 201 (Motion Module)87
    24. MOT 202 (Motion Module)87
    25. TST 999 (NR&D Test Module)88
    26. UCM 001 (NR&D Communications Module)88
    27. ZAE 201 (Counter/Position Module)88
    28. ZAE 204 (High Speed Counter)90
  2. 7 Front Panel Operation92
    1. Keypad92
    2. Splash Screen92
    3. Backlight92
    4. Main Screen92
    5. Config Screens93
    6. Mode Screens94
    7. Status Screens95
    8. Info Screens95
    9. System Screen96
  3. 8 Register List97
    1. Drop 0/1 Register List97
    2. Drop 255 Register List98
  4. 9 Virtual PLC Memory106
    1. Overview106
    2. Operation107

From the PDF’s own bookmarks.

The whole text · 15 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. 1 Introduction11-13
  3. 2 Installation14-21
  4. 3 Web Server22-34
  5. 4 Rack35-39
  6. 5 Mapper, pages 40 to 4740-47
  7. 5 Mapper, pages 48 to 5548-55
  8. 6 A120 I/O, pages 56 to 6456-64
  9. 6 A120 I/O, pages 65 to 7365-73
  10. 6 A120 I/O, pages 74 to 8274-82
  11. 6 A120 I/O, pages 83 to 9183-91
  12. 7 Front Panel Operation92-96
  13. 8 Register List97-105
  14. 9 Virtual PLC Memory, pages 106 to 114106-114
  15. 9 Virtual PLC Memory, pages 115 to 122115-122

The file

Revision and size

RevisionEffective: February 11, 2011
PublisherNiobrara Research & Development Corporation
Pages122
PDF1.9 MB
TextText from the PDF itself; pages 19, 24, 34 and 39 are scans, read by OCR, which may hold reading errors.