Page 56

6

A120 I/O

The default operation of many A120 I/O cards with the CERI is the same as the operation of the card configured for 3x-register operation using Concept. Many of the intelligent cards require the CERI to perform automatic multiplexing/demultiplexing of the data across the backplane so these cards will have many more input and output registers than normally traffic-copped with a Compact PLC. The register maps for each supported module is shown in this chapter. NOTE: For complete module wiring and operating information consult the Modicon A120 Series I/O Modules User Guide (890 USE 109 00).

ADU 204 (4-point Voltage/RTD Analog Input) Modicon Module ID: x20 (32), NRD Module ID: x14 (20) The ADU 204 uses four 4x-registers (In-0 through In-3) for the analog data from Channels 1 through 4. There are no output registers assigned to this card. Table 6.1: ADU 204 input register map 4x Register

Description

In-0

Channel 1 input value

In-1

Channel 2 input value

In-2

Channel 3 input value

In-3

Channel 4 input value

ADU 205 (4-point Voltage/Current Analog Input) Modicon Module ID: x22 (34), NRD Module ID: x15 (21) The ADU 205 uses four 4x-register inputs (In-0 through In-3) and five 4x-register outputs (Out-0 through Out-4). The input registers show the analog values for Channels 1 through 4 while the output registers set the resolution and Channel configuration. NOTE: The values used in the four output registers are typically set through the Configuration page on the CERI's Web server. These values will not change CERI Manual

59

Page 57

during normal operation and do not need to be written by the controlling PLC. It is advised that these outputs not be included in the I/O Scanner writes. Table 6.2: ADU 205 input register map 4x Register

Description

In-0

Channel 1 input value

In-1

Channel 2 input value

In-2

Channel 3 input value

In-3

Channel 4 input value

Table 6.3: ADU 205 output register map 4x Register

Description

Out-0 (Module Resolution Configuration in hex) (Resolution) 0C = 12 bit 0E = 12 bit + sign 0B = 13 bit 0F = 15 bit + sign 0D = 16 bit Out-1 (Configuration Values in hex) (Channel 1) 00 = Inactive 01 = -20V to +20V 02 = -40mA to +40mA 04 = -10V to +10V 08 = -20mA to +20mA 10 = 0mA to 20mA 20 = 4mA to 20mA 40 = 0V to 10V 80 = 0V to 20V Out-2 (Same Configuration Values as above) (Channel 2) Out-3 (Same Configuration Values as above) (Channel 3) Out-4 (Same Configuration Values as above) (Channel 4)

60 A120 I/O 6

CERI Manual

Page 58

ADU 206 (4-point Voltage/Current Isolated Analog Input) Modicon Module ID: x23 (35), NRD Module ID: x16 (22) The ADU 206 use five 4x-register inputs (In-0 through In-4) and two 4x-register outputs (Out-0 and Out-1). The input registers show the status and analog values for Channels 1 through 4 while the output registers set the resolution and Channel configuration. NOTE: The values used in the two output registers are typically set through the Configuration page on the CERI's Web server. These values will not change during normal operation and do not need to be written by the controlling PLC. It is advised that these outputs not be included in the I/O Scanner writes. Table 6.4: ADU 206 input register map 4x Register In-0 (Status)

Description Bitmap (bit 0 is LSB) bits 8-15 not used bit 7 = set on Fault bit 6 = set if external supply bad bit 5 = Offset and extended resolution turned on bit 4 = set if Unipolar, clear if Bipolar bit 3 = Channel 4 out of range bit 2 = Channel 3 out of range bit 1 = Channel 2 out of range bit 0 = Channel 1 out of range

In-1

Channel 1 input value

In-2

Channel 2 input value

In-3

Channel 3 input value

In-4

Channel 4 input value

Out-0 Bitmap (bit 0 is LSB) (Resolution) bits 7-15 not used bit 6 = Display Overrange in Status bit 5 = Offset and extended range enabled bit 4 = set for Unipolar, clear for Bipolar bit 3 = Channel 4 Expanded Range (set for 0-10V range, clear for 0-1V range) bit 2 = Channel 3 Expanded Range bit 1 = Channel 2 Expanded Range bit 0 = Channel 1 Expanded Range

CERI Manual

6 A120 I/O 61

Page 59

Table 6.5: ADU 206 output register map 4x Register

Description

Out-0 Bitmap (bit 0 is LSB) (Resolution) bits 7-15 not used bit 6 = Display Overrange in Status bit 5 = Offset and extended range enabled bit 4 = set for Unipolar, clear for Bipolar bit 3 = Channel 4 Expanded Range (set for 0-10V range, clear for 0-1V range) bit 2 = Channel 3 Expanded Range bit 1 = Channel 2 Expanded Range bit 0 = Channel 1 Expanded Range Out-1 bits 9-15 not used (Resolution) bit 8 = clear for Unsigned, set for Signed bits 0-7 = decimal value to set the number of bits of resolution (11-16)

ADU 210 (4-point Voltage/Current Analog Input) Modicon Module ID: x38 (56), NRD Module ID: x31 (49) The ADU 210 uses four 4x-register inputs (In-0 through In-3) and two 4x-register outputs (Out-0 and Out-1). The input registers show the analog values for Channels 1 through 4 while the output registers set the Channel configuration. NOTE: The ADU 210 must have external 24Vdc power to function properly. The ADU 210 reports an incorrect module ID (255 instead of 56) when missing the external 24Vdc. The CERI will indicate that the slot in question contains the TST 999 card instead of the ADU 210 while the ADU 210 is not powered.

Table 6.6: ADU 210 input register map 4x Register

Description

In-0

Channel 1 input value

In-1

Channel 2 input value

In-2

Channel 3 input value

In-3

Channel 4 input value

62 A120 I/O 6

CERI Manual

Page 60

NOTE: The values used in the two output registers are typically set through the Configuration page on the CERI's Web server. These values will not change during normal operation and do not need to be written by the controlling PLC. It is advised that these outputs not be included in the I/O Scanner writes. Table 6.7: ADU 210 output register map 4x Register

Description

Out-0 High byte = Channel 1 configuration (Channels 1 and (hex values) 2 configuration) 01 = 0 to 10V 09 = 2 to 10V 02 = 0 to 5V (0 to 20mA) 0A = 1 to 5V (4 to 20mA) 11 = 0 to 10V – Limit <> 0 19 = 0 to 10V – Limit <> 0 12 = 0 to 5V (0 to 20mA) – Limit <> 0 1A = 1 to 5V (4 to 20mA) – Limit <> 0 21 = +/-10V 22 = +/-5V (+/-20mA) Low byte = Channel 2 configuration Out-1 High byte = Channel 3 configuration (Channels 3 and Low byte = Channel 4 configuration 4 configuration)

ADU 211 (8-point Universal Isolated Analog Input) Modicon Module ID: x76 (118), NRD Module ID: x23 (35) The ADU 211 uses eighteen 4x-register inputs (In-0 through In-17) and three 4xregister outputs (Out-0 through Out-2). The input registers show the analog values for Channels 1 through 4 while the output registers set the Channel configuration. NOTE: The values used in the three output registers are typically set through the Configuration page on the CERI's Web server. These values will not change during normal operation and do not need to be written by the controlling PLC. It is advised that these outputs not be included in the I/O Scanner writes.

CERI Manual

6 A120 I/O 63

Page 61

Table 6.8: ADU 211 input register map 4x Register

Description

In-0

Channel 1 input value (low word)

In-1

Channel 1 input value (high word)

In-2

Channel 2 input value (low word)

In-3

Channel 2 input value (high word)

In-4

Channel 3 input value (low word)

In-5

Channel 3 input value (high word)

In-6

Channel 4 input value (low word)

In-7

Channel 4 input value (high word)

In-8

Channel 5 input value (low word)

In-9

Channel 5 input value (high word)

In-10

Channel 6 input value (low word)

In-11

Channel 6 input value (high word)

In-12

Channel 7 input value (low word)

In-13

Channel 7 input value (high word)

In-14

Channel 8 input value (low word)

In-15

Channel 8 input value (high word)

In-16

Bits 8-15, Range Error (bit 15 = channel 1) Bits 0-7, Data Valid (bit 0=channel 8)

In-17

Bit 2 = Module Memory Fault bit 3 = Module Hardware Fault (bit 0 is LSB)

Table 6.9: ADU 211 output register map 4x Register

Description

Out-0

Refer to Modicon I/O User Guide

Out-1

Refer to Modicon I/O User Guide

Out-2

Reserved for Modicon future use

64 A120 I/O 6

CERI Manual

Page 62

ADU 212 (8-point Universal Isolated Analog Input) Modicon Module ID: x76 (118), NRD Module ID: x24 (36) The ADU 212 uses eighteen 4x-register inputs (In-0 through In-17) and three 4xregister outputs (Out-0 through Out-2). The input registers show the analog values for Channels 1 through 4 while the output registers set the Channel configuration. NOTE: The values used in the three output registers are typically set through the Configuration page on the CERI's Web server. These values will not change during normal operation and do not need to be written by the controlling PLC. It is advised that these outputs not be included in the I/O Scanner writes. Table 6.10: ADU 212 input register map 4x Register

Description

In-0

Channel 1 input value (low word)

In-1

Channel 1 input value (high word)

In-2

Channel 2 input value (low word)

In-3

Channel 2 input value (high word)

In-4

Channel 3 input value (low word)

In-5

Channel 3 input value (high word)

In-6

Channel 4 input value (low word)

In-7

Channel 4 input value (high word)

In-8

Channel 5 input value (low word)

In-9

Channel 5 input value (high word)

In-10

Channel 6 input value (low word)

In-11

Channel 6 input value (high word)

In-12

Channel 7 input value (low word)

In-13

Channel 7 input value (high word)

In-14

Channel 8 input value (low word)

In-15

Channel 8 input value (high word)

In-16

Bits 8-15, Range Error (bit 15 = channel 1) Bits 0-7, Data Valid (bit 0=channel 8)

In-17

Bit 2 = Module Memory Fault bit 3 = Module Hardware Fault (bit 0 is LSB)

CERI Manual

6 A120 I/O 65

Page 63

Table 6.11: ADU 212 output register map 4x Register

Description

Out-0

Refer to Modicon I/O User Guide

Out-1

Refer to Modicon I/O User Guide

Out-2

Reserved for Modicon future use

66 A120 I/O 6

CERI Manual

Page 64

ADU 214 (8-point Non-Isolated Analog Input) Modicon Module ID: x24 (36), NRD Module ID: x17 (23) The ADU 212 uses eight 4x-register inputs (In-0 through In-7) and four 4xregister outputs (Out-0 through Out-3). The input registers show the analog values for Channels 1 through 8 while the output registers set the Channel configuration. NOTE: The values used in the four output registers are typically set through the Configuration page on the CERI's Web server. These values will not change during normal operation and do not need to be written by the controlling PLC. It is advised that these outputs not be included in the I/O Scanner writes. Table 6.12: ADU 214 input register map 4x Register

Description

In-0

Channel 1 input value

In-1

Channel 2 input value

In-2

Channel 3 input value

In-3

Channel 4 input value

In-4

Channel 5 input value

In-5

Channel 6 input value

In-6

Channel 7 input value

In-7

Channel 8 input value

Table 6.13: ADU 214 output register map 4x Register

Description

Out-0

Refer to Modicon I/O User Guide

Out-1

Refer to Modicon I/O User Guide

Out-2

Refer to Modicon I/O User Guide

Out-3

Refer to Modicon I/O User Guide

ADU 216 (8-point Thermocouple Isolated Analog Input) Modicon Module ID: x3B (59), NRD Module ID: x1D (29) The ADU 216 uses nine 4x-register inputs (In-0 through In-3) and one 4x-register output (Out-0). The input registers show the status and analog values for Channels 1 through 8 while the output register sets the Channel configuration. NOTE: The values used in the output register are typically set through the Configuration page on the CERI's Web server. These values will not

CERI Manual

6 A120 I/O 67