Page 65

change during normal operation and do not need to be written by the controlling PLC. It is advised that this output register not be included in the I/O Scanner writes. Table 6.14: ADU 216 input register map 4x Register

Description

In-0 (Status)

bits 8-15 are not used. bit 7 = module ready if set, not ready/defect if clear bit 6 = reference sensor open circuit if set bit 5 = open circuit or over-temperature if set bits 4-2 = channel number with open circuit detected (binary value) bit 1 = channel 8 input, 0=terminals 20&21, 1=reference sensor bit 0 = not used

In-1

Channel 1 input value

In-2

Channel 2 input value

In-3

Channel 3 input value

In-4

Channel 4 input value

In-5

Channel 5 input value

In-6

Channel 6 input value

In-7

Channel 7 input value

In-8

Channel 8 input value (or reference sensor)

Table 6.15: ADU 216 output register map 4x Register

Description

Out-0 Bits 5-15 are not used (Configuration) bits 2-4 thermocouple type 000=K, 010=J, 111=linear voltage bits 1 channel 8 input, 0=terminals 20&21, 1=reference sensor bit 0 not used

ADU 254 (4-point Voltage/RTD Analog Input) Modicon Module ID: x20 (32), NRD Module ID: x3A (58) The ADU 254 uses four 4x-registers (In-0 through In-3) for the analog data from Channels 1 through 4. There are no output registers assigned to this card.

68 A120 I/O 6

CERI Manual

Page 66

Table 6.16: ADU 254 input register map 4x Register

Description

In-0

Channel 1 input value

In-1

Channel 2 input value

In-2

Channel 3 input value

In-3

Channel 4 input value

ADU 256 (4-point Voltage/Current Isolated Analog Input) Modicon Module ID: x2A (42), NRD Module ID: x23 (35) The ADU 256 use five 4x-register inputs (In-0 through In-4) and two 4x-register outputs (Out-0 and Out-1). The input registers show the status and analog values for Channels 1 through 4 while the output registers set the resolution and Channel configuration. NOTE: The values used in the two output registers are typically set through the Configuration page on the CERI's Web server. These values will not change during normal operation and do not need to be written by the controlling PLC. It is advised that these outputs not be included in the I/O Scanner writes.

CERI Manual

6 A120 I/O 69

Page 67

Table 6.17: ADU 256 input register map 4x Register In-0 (Status)

Description Bitmap (bit 0 is LSB) bits 8-15 not used bit 7 = set on Fault bit 6 = set if external supply bad bit 5 = Offset and extended resolution turned on bit 4 = set if Unipolar, clear if Bipolar bit 3 = Channel 4 out of range bit 2 = Channel 3 out of range bit 1 = Channel 2 out of range bit 0 = Channel 1 out of range

In-1

Channel 1 input value

In-2

Channel 2 input value

In-3

Channel 3 input value

In-4

Channel 4 input value

Out-0 Bitmap (bit 0 is LSB) (Resolution) bits 7-15 not used bit 6 = Display Overrange in Status bit 5 = Offset and extended range enabled bit 4 = set for Unipolar, clear for Bipolar bit 3 = Channel 4 Expanded Range (set for 0-10V range, clear for 0-1V range) bit 2 = Channel 3 Expanded Range bit 1 = Channel 2 Expanded Range bit 0 = Channel 1 Expanded Range

Table 6.18: ADU 256 output register map 4x Register

Description

Out-0 Bitmap (bit 0 is LSB) (Resolution) bits 7-15 not used bit 6 = Display Overrange in Status bit 5 = Offset and extended range enabled bit 4 = set for Unipolar, clear for Bipolar bit 3 = Channel 4 Expanded Range (set for 0-10V range, clear for 0-1V range) bit 2 = Channel 3 Expanded Range bit 1 = Channel 2 Expanded Range bit 0 = Channel 1 Expanded Range Out-1 bits 9-15 not used (Resolution) bit 8 = clear for Unsigned, set for Signed bits 0-7 = decimal value to set the number of bits of resolution (11-16)

70 A120 I/O 6

CERI Manual

Page 68

ADU 257 (8-point mV/RTD/TC/Resistance Analog Input) The ADU 257 requires the same 20 input register layout as with the Compact PLC. Table 6.19: ADU 257 input register map 4x Register

Description

In-0

Input Status Word.

In-1

Input Status Word

In-2

Input #1 data (low word)

In-3

Input #1 data (high word)

In-4

Input #2 data (low word)

In-5

Input #2 data (high word)

In-6

Input #3 data (low word)

In-7

Input #3 data (high word)

In-8

Input #4 data (low word)

In-9

Input #4 data (high word)

In-10

Input #5 data (low word)

In-11

Input #5 data (high word)

In-12

Input #6 data (low word)

In-13

Input #6 data (high word)

In-14

Input #7 data (low word)

In-15

Input #7 data (high word)

In-16

Input #8 data (low word)

In-17

Input #8 data (high word)

In-18

Input #9 data (cold junction sensor) (low word)

In-19

Input #9 data (cold junction sensor) (high word)

Table 6.20: ADU 257 output register map 4x Register

Description

Out-0

MSB = Temperature & CJC Settings LSB = Ch. 1 Config

Out-1

MSB = Ch 2 Config LSB = Ch 3 Config

Out-2

MSB = Ch 4 Config LSB = Ch 5 Config

Out-3

MSB = Ch 6 Config LSB = Ch 7 Config

Out-4

MSB = Ch 8 Config LSB = Reserved = 0

CERI Manual

6 A120 I/O 71

Page 69

BKF 201 (Interbus S Master) 16 Word Modicon Module ID: x5C (92), NRD Module ID: x37 (55) 64 Word Modicon Module ID: x5D (93), NRD Module ID: x38 (56) The BKF 201 may be configured for either 16 output/input registers or 64 output/input registers. The register layout and operation is the same for the CERI as with the Compact PLC. DIP Switch S0=ON and S1=OFF sets the BKF 201 for 16 word operation. DIP Switch S0=ON and S1=ON sets the BKF 201 for 64 word operation. NOTE: 64 register operation is valid only in the primary CPU rack. Sixteen register operation is valid in the primary and all expansion racks. Table 6.21: BFK 201 input register map 4x Register In-0 (Status)

Description Bits 15-8 display the configuration checksum Bits 7-5 not used. Bits 4-0 Status bitmap.

In-1

Interbus data – Input word 1

In-2

Interbus data – Input word 2

...

...

In-15 or In-63

Interbus data – Input word 15 or Input word 63

Table 6.22: BFK 201 output register map 4x Register

Description

Out-0

Bits 15-8 bus configuration checksum (copy from In-0 high byte) Bits 7-0 command value bit 1 = alarm stop bit 2 = start cycle bit 3 = quit error bit 4 = not used bits 3 and 5 only = get configuration

Out-1

Interbus data – Output word 1

Out-2

Interbus data – Output word 2

... Out-15 or Out-63

72 A120 I/O 6

... Interbus data – Output word 15 or Output word 63

CERI Manual

Page 70

DAO 216 (16-point 24Vdc Non-isolated Discrete Output) Modicon Module ID: x1B (27), NRD Module ID: x11 (17) The DAO 216 only uses one (Out-0) 4x-register for its 16 discrete outputs. Table 6.23: DAO 216 output register bit-map 4x Register Bit #

15 14 13 (MSB)

Out-0 (Output #)

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

DAP 204 (4-point Relay Discrete Output) Modicon Module ID: x17 (23), NRD Module ID: x0D (13) The DAP 204 only uses one 4x-register (Out-0) for its 4 discrete Outputs. Bits 415 are not used. Table 6.24: DAP 204 output register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

7

6

5

4

Out-0 (Output #)

3

2

1

0 (LSB)

1

2

3

4

DAP 208 (8-point Relay Discrete Output) Modicon Module ID: x0F (15), NRD Module ID: x07 (07) The DAP 208 only uses one 4x-register (Out-0) for its 8 discrete Outputs. Bits 815 are not used. Table 6.25: DAP 208 output register bit-map 4x Register Bit #

15 14 13 (MSB)

Out-0 (Output #)

CERI Manual

12

11

10

9

8

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

6 A120 I/O 73

Page 71

DAP 210 (8-point 24..240 Vac Discrete Output) Modicon Module ID: x10 (16), NRD Module ID: x08 (08) The DAP 210 only uses one 4x-register (Out-0) for its 8 discrete Outputs. Bits 815 are not used. Table 6.26: DAP 210 output register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

Out-0 (Output #)

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

DAP 211 (Monitored 4-point Out Combined I/O) Modicon Module ID: x0A (10), NRD Module ID: x03 (03) The DAP 211 uses one 4x-register (In-0) for its 4 discrete Inputs and one 4xregister (Out-0) for its 4 discrete Outputs. Bits 4-15 are not used on In-0 and bits 4-15 are not used on Out-0. Table 6.27: DAP 211 input register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

7

6

5

4

In-0 (Input #)

3

2

1

0 (LSB)

1

2

3

4

3

2

1

0 (LSB)

1

2

3

4

Table 6.28: DAP 211 output register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

7

6

5

4

Out-0 (Output #)

DAP 212 (8-point In/4-point Out Combined I/O) Modicon Module ID: x08 (08), NRD Module ID: x01 (01) The DAP 212 uses one 4x-register (In-0) for its 8 discrete Inputs and one 4xregister (Out-0) for its 4 discrete Outputs. Bits 8-15 are not used on In-0 and bits 4-15 are not used on Out-0.

74 A120 I/O 6

CERI Manual

Page 72

Table 6.29: DAP 212 input register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

In-0 (Input #)

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

Table 6.30: DAP 212 output register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

Out-0 (Output #)

DAP 216 (16-point 24Vdc Discrete Output) Modicon Module ID: x19 (25), NRD Module ID: x0F (15) The DAP 216 only uses one (Out-0) 4x-register for its 16 discrete outputs. Table 6.31: DAP 216 output register bit-map 4x Register Bit #

15 14 13 (MSB)

Out-0 (Output #)

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

DAP 217 (16-point 5-24Vdc Discrete Output True Low) Modicon Module ID: x2A (42), NRD Module ID: x18 (24) The DAP 217 only uses one (Out-0) 4x-register for its 16 discrete outputs. Table 6.32: DAP 217 output register bit-map 4x Register Bit #

15 14 13 (MSB)

Out-0 (Output #)

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

DAP 218 (16-point 24-249Vac Discrete Output) Modicon Module ID: x1D (29), NRD Module ID: x13 (19) The DAP 218 only uses one (Out-0) 4x-register for its 16 discrete outputs. CERI Manual

6 A120 I/O 75

Page 73

Table 6.33: DAP 218 output register bit-map 4x Register Bit #

15 14 13 (MSB)

Out-0 (Output #)

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

DAP 220 (8-point In/8-point Out Combined I/O) Modicon Module ID: x09 (9), NRD Module ID: x02 (2) The DAP 220 uses one 4x-register (In-0) for its 8 discrete Inputs and one 4xregister (Out-0) for its 8 discrete Outputs. Bits 8-15 are not used on In-0 and bits 8-15 are not used on Out-0. Table 6.34: DAP 220 input register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

In-0 (Input #)

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

Table 6.35: DAP 220 output register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

Out-0 (Output #)

DAP 250 (8-point In/8-point Out Combined I/O) Modicon Module ID: x09 (9), NRD Module ID: x39 (57) The DAP 250 uses one 4x-register (In-0) for its 8 discrete Inputs and one 4xregister (Out-0) for its 8 discrete Outputs. Bits 8-15 are not used on In-0 and bits 8-15 are not used on Out-0. Table 6.36: DAP 250 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

76 A120 I/O 6

12

11

10

9

8

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

CERI Manual