Page 74

Table 6.37: DAP 250 output register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

Out-0 (Output #)

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

DAP 252 (8-point In/4-point Out Combined I/O) Modicon Module ID: x08 (8), NRD Module ID: x32 (50) The DAP 252 uses one 4x-register (In-0) for its 8 discrete Inputs and one 4xregister (Out-0) for its 4 discrete Outputs. Bits 8-15 are not used on In-0 and bits 4-15 are not used on Out-0. Table 6.38: DAP 252 input register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

In-0 (Input #)

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

Table 6.39: DAP 252 output register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

Out-0 (Output #)

DAP 253 (8-point In/4-point Out Combined I/O) Modicon Module ID: x08 (8), NRD Module ID: x33 (51) The DAP 253 uses one 4x-register (In-0) for its 8 discrete Inputs and one 4xregister (Out-0) for its 4 discrete Outputs. Bits 8-15 are not used on In-0 and bits 4-15 are not used on Out-0. Table 6.40: DAP 253 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

CERI Manual

12

11

10

9

8

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

6 A120 I/O 77

Page 75

Table 6.41: DAP 253 output register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

7

6

5

4

Out-0 (Output #)

3

2

1

0 (LSB)

1

2

3

4

DAP 258 (8-point Relay Discrete Output) Modicon Module ID: x18 (24), NRD Module ID: x2B (43) The DAP 258 only uses one 4x-register (Out-0) for its 8 discrete Outputs. Bits 815 are not used. Table 6.42: DAP 258 register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

Out-0 (Output #)

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

DAP 292 (8-point In/4-point Out Combined I/O) Modicon Module ID: x08 (8), NRD Module ID: x34 (52) The DAP 292 uses one 4x-register (In-0) for its 8 discrete Inputs and one 4xregister (Out-0) for its 4 discrete Outputs. Bits 8-15 are not used on In-0 and bits 4-15 are not used on Out-0. Table 6.43: DAP 292 input register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

In-0 (Input #)

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

Table 6.44: DAP 292 output register bit-map 4x Register Bit #

15 14 13 (MSB)

Out-0 (Output #)

78 A120 I/O 6

12

11

10

9

8

CERI Manual

Page 76

DAU 202 (2-point Voltage/Current Analog Output) Modicon Module ID: x30 (48), NRD Module ID: x1B (27) The DAU 202 uses three 4x-registers (Out-0 through Out-2). The first register configures the resolution while the second and third set output values for Channels 1 and 2. Table 6.45: DAU 202 output register map 4x Register Out-0 (LSB Resolution MSB Hold Last Value)

Description LSB Value 0 = 15 bit + sign LSB Value 6 = 12 bit bit 8 = Channel 1 Hold Last Value (1=Hold, 0=User Default bit 9 = Channel 2 Hold Last Value (1=Hold, 0=User Default

Out-1

Channel 1 output value (-32768 to 32752 or 0 to 4095)

Out-2

Channel 2 output value (-32768 to 32752 or 0 to 4095)

Each output channel of the DAU 202 may be independently configured to Hold Last Value or revert to a User Default value when the CERI is halted. Table 6.46: DAU 202 Output Operating Values Voltage (Vdc)

Current (mA)

12-bits

15-bits + sign

<-10

<-20

0..47

-32768...-32016

-10

-20

48

-32000

0

0

2048

0

10

20

4048

32000

>10

>20

4049..4095 +32016...+32752

Range Under Normal Over

DAU 204 (4-point Voltage/Current Analog Output) Modicon Module ID: x75 (117), NRD Module ID: x22 (34) NOTE: The DAU 204 must be powered when in the rack and the power switch on the CERI must not be turned off while the DAU 204 is powered. The 24Vdc power used for the CERI should also be the same power for the DAU 204. Cycling power independently on either the CERI or DAU 204 may cause unpredictable output operation on the DAU 204. The DAU 204 includes one 4x-register input (In-0) for status and seven registers four output and configuration (Out-0 through Out-6). CERI Manual

6 A120 I/O 79

Page 77

Table 6.47: DAU 204 input register bit-map 4x Register Bit #

15 (MSB)

14

13..5

In-0 (Status)

Module Module Not USed Error Memory Error

4

3

Ch 4 Current Error

2

Ch 3 Ch 2 Current Current Error Error

1

0 (LSB)

Ch 1 Current Error

Current Error

Table 6.48: DAU 204 output register map 4x Register

Description

Out-0 (LSB Resolution MSB Hold Last Value)

LSB Value 0 = 15 bit + sign LSB Value 6 = 12 bit bit 8 = Channel 1 Hold Last Value (1=Hold, 0=User Default bit 9 = Channel 2 Hold Last Value (1=Hold, 0=User Default

Out-0

Channel 1 output value (-32768 to 32752 or 0 to 4095)

Out-1

Channel 2 output value (-32768 to 32752 or 0 to 4095)

Out-2

Channel 3 output value (-32768 to 32752 or 0 to 4095)

Out-3

Channel 4 output value (-32768 to 32752 or 0 to 4095)

Out-4

Control Word 0, Range Select

Out-5

Control Word 1, Fault State

Out-6

Control Word 2, Scaling

The Range Select includes a nybble for each output channel. The least significant nybble selects channel 0 while the most significant nybble selects channel 4. Table 6.49: DAU 204 Range Values Nybble value

Range

0

4..20mA

1

0..20mA

2

0..1V

3

+/-1V

4

0..5V

5

+/-5V

6

0..10V

7

-10...+10V

The Fault State word include configuration for hold last value (bits8-11) and 80 A120 I/O 6

CERI Manual

Page 78

other calibration and test mode bits. Refer to the IO User guide for information on calibrating the DAU 204. Table 6.50: DAU 204 Fault State register bit-map 4x Register Bit #

15 (MSB)

14-12

11

10

9

8

7-0 (LSB)

Out-5 (Fault State)

Calibration

Test Ch 4 Hold Ch 3 Hold Ch 2 Hold Ch 1 Hold Calibration Mode Last Value Last Value Last Value Last Value

Each output channel of the DAU 204 may be independently configured to Hold Last Value or revert to a User Default value when the CERI is halted. The Scale Select includes a nybble for each output channel. The least significant nybble selects channel 0 while the most significant nybble selects channel 4. NOTE: The loadable used in Concept for 15-bit+sign functions as expected on +/- voltage ranges with -32000,0,+32000 values corresponding with -full scale, zero, and +full scale. The loadable used in ProWORX32 and ProWORXnXT for 15-bit+sign actually functioned as a 14-bit setting. See Table 6.54 Table 6.51: DAU 204 Scale Values Nybble value

Scale

0

12-bit

1

11-bit

2

15-bit + Sign (Concept)

3

16-bit

4

15-bit + Sign (ProWORX)

Table 6.52: DAU 204 Output Operating Values for 0-1, 0-5, 0-10 VDC 0...1 Vdc

0...5 Vdc

0..10 Vdc

11-bits

12-bits

15-bits + sign

15-bits + 16-bits sign

(ProWORX)

(Concept)

0

0

0

0

0

0

0

0

0.5

2.5

5

1024

2048

16000

16000

32768

1

5

10

2047

4095

32000

32000

65520

CERI Manual

6 A120 I/O 81

Page 79

Table 6.53: DAU 204 Output Operating Values for 0/4...20mA 0...20 4...20 mA mA

11-bits

12-bits

15-bits + sign

15-bits + 16-bits sign

(ProWORX)

(Concept)

0

4

0

0

0

0

0

10

12

1024

2048

16000

16000

32768

20

20

2047

4095

32000

32000

65520

Table 6.54: DAU 204 Output Operating Values for +/-1, +/-5, +/-10 VDC +/-1 Vdc

+/-5 Vdc

+/-10 Vdc

11-bits

12-bits

15-bits + sign

15-bits + 16-bits sign

(ProWORX)

(Concept)

-1

-5

-10

0

0

0

-32000

0

0

0

0

1024

2048

16000

0

32768

1

5

10

2047

4095

32000

32000

65520

82 A120 I/O 6

CERI Manual

Page 80

DAU 208 (8-point +/-10Vdc Isolated Analog Output) Modicon Module ID: x32 (50) , NRD Module ID: x1C (28) The DAU 208 uses nine 4x-registers (Out-0 through Out-8). The first register configures the resolution and hold last value while the rest set output values for Channels 1 through 8. Table 6.55: DAU 208 output register map 4x Register Out-0 (LSB Resolution MSB Hold Last Value)

Description LSB Value 0 = 15 bit + sign LSB Value 6 = 12 bit bit 8 = Channel 1 Hold Last Value (1=Hold, 0=User Default bit 9 = Channel 2 Hold Last Value (1=Hold, 0=User Default bit 10 = Channel 3 Hold Last Value (1=Hold, 0=User Default bit 11 = Channel 4 Hold Last Value (1=Hold, 0=User Default bit 12 = Channel 5 Hold Last Value (1=Hold, 0=User Default bit 13 = Channel 6 Hold Last Value (1=Hold, 0=User Default bit 14 = Channel 7 Hold Last Value (1=Hold, 0=User Default bit 15 = Channel 8 Hold Last Value (1=Hold, 0=User Default

Out-1

Channel 1 output value (-32768 to 32752 or 0 to 4095)

Out-2

Channel 2 output value (-32768 to 32752 or 0 to 4095)

Out-3

Channel 3 output value (-32768 to 32752 or 0 to 4095)

Out-4

Channel 4 output value (-32768 to 32752 or 0 to 4095)

Out-5

Channel 5 output value (-32768 to 32752 or 0 to 4095)

Out-6

Channel 6 output value (-32768 to 32752 or 0 to 4095)

Out-7

Channel 7 output value (-32768 to 32752 or 0 to 4095)

Out-8

Channel 8 output value (-32768 to 32752 or 0 to 4095)

Each output channel of the DAU 208 may be independently configured to Hold Last Value or revert to a User Default value when the CERI is halted. Table 6.56: DAU 208 Output Operating Values Voltage (Vdc)

12-bits

15-bits + sign

Range

<-10

0..47

-32768...-32016

Under

-10

48

-32000

0

2048

0

10

4048

32000

>10

4049..4095

+32016...+32752

CERI Manual

Normal Over

6 A120 I/O 83

Page 81

DAU 252 (2-point Voltage/Current Analog Output) Modicon Module ID: x30 (48), NRD Module ID: x3B (59) The DAU 252 uses three 4x-registers (Out-0 through Out-2). The first register configures the resolution while the second and third set output values for Channels 1 and 2. Table 6.57: DAU 252 output register map 4x Register

Description

Out-0 (LSB Resolution MSB Hold Last Value)

LSB Value 0 = 15 bit + sign LSB Value 6 = 12 bit bit 8 = Channel 1 Hold Last Value (1=Hold, 0=User Default bit 9 = Channel 2 Hold Last Value (1=Hold, 0=User Default

Out-1

Channel 1 output value (-32768 to 32752 or 0 to 4095)

Out-2

Channel 2 output value (-32768 to 32752 or 0 to 4095)

Each output channel of the DAU 202 may be independently configured to Hold Last Value or revert to a User Default value when the CERI is halted. Table 6.58: DAU 252 Output Operating Values Voltage (Vdc)

Current (mA)

12-bits

15-bits + sign

<-10

<-20

0..47

-32768...-32016

-10

-20

48

-32000

0

0

2048

0

10

20

4048

32000

>10

>20

4049..4095 +32016...+32752

Range Under Normal Over

DEO 216 (16-point 24Vdc Non-Isolated Discrete Input) Modicon Module ID: x0D (13), NRD Module ID: x05 (5) The DEO 216 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.59: DEO 216 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

84 A120 I/O 6

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

CERI Manual

Page 82

DEP 208 (8-point 230Vac Discrete Input) Modicon Module ID: x0F (15), NRD Module ID: x07 (7) The DEP 208 only uses one 4x-register (In-0) for its 8 discrete inputs. Bits 8-15 are not used. Table 6.60: DEP 208 input register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

In-0 (Input #)

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

DEP 209 (8-point 120Vac Discrete Input) Modicon Module ID: x13 (19), NRD Module ID: x0B (11) The DEP 209 only uses one 4x-register (In-0) for its 8 discrete inputs. Bits 8-15 are not used. Table 6.61: DEP 209 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

CERI Manual

12

11

10

9

8

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

6 A120 I/O 85