Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual ยท part 11 of 15

CERI Installation and Programming Manual: 6 A120 I/O, pages 83 to 91

Pages 83 to 91 of 122, from CERI Installation and Programming Manual

The original document is the PDF (1.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the AEG DEP-210

Page 83

DEP 210 (8-point 115 Vac Discrete Input) Modicon Module ID: x10 (16), NRD Module ID: x08 (8) The DEP 210 only uses one 4x-register (In-0) for its 8 discrete inputs. Bits 8-15 are not used. Table 6.62: DEP 210 input register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

In-0 (Input #)

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

DEP 211 (8-point 115 Vac Isolated Discrete Input) Modicon Module ID: x11 (17), NRD Module ID: x09 (9) The DEP 211 only uses one 4x-register (In-0) for its 8 discrete inputs. Bits 8-15 are not used. Table 6.63: DEP 211 input register bit-map 4x Register Bit #

15 14 13 (MSB)

12

11

10

9

8

In-0 (Input #)

7

6

5

4

3

2

1

0 (LSB)

1

2

3

4

5

6

7

8

1

0 (LSB)

DEP 214 (16-point 10-60Vdc Discrete Input) Modicon Module ID: x14 (20), NRD Module ID: x0C (12) The DEP 214 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.64: DEP 214 input register bit-map 4x Register Bit #

15 14 13 12 11 10 (MSB)

In-0 (Input #)

86 A120 I/O 6

1

2

3

4

5

6

9

8

7

6

5

4

3

2

7

8

9

10 11 12 13 14 15

16

CERI Manual

Page 84

DEP 215 (16-point 5Vdc TTL True Low Discrete Input) Modicon Module ID: x2E (46), NRD Module ID: x1A (26) The DEP 215 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.65: DEP 215 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

DEP 216 (16-point 24Vdc Discrete Input) Modicon Module ID: x0C (12), NRD Module ID: x04 (4) The DEP 216 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.66: DEP 216 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

DEP 217 (16-point 24Vdc Discrete Input) Modicon Module ID: x2D (45), NRD Module ID: x19 (25) The DEP 217 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.67: DEP 217 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

CERI Manual

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

6 A120 I/O 87

Page 85

DEP 218 (16-point 115VAC Discrete Input) Modicon Module ID: x12 (18), NRD Module ID: x0A (10) The DEP 218 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.68: DEP 218 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

DEP 254 (16-point 10-60Vdc Discrete Input) Modicon Module ID: x14 (20), NRD Module ID: x3C (60) The DEP 254 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.69: DEP 254 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

DEP 256 (16-point 24Vdc Discrete Input Extended Temp.) Modicon Module ID: x0C (12), NRD Module ID: x2C (44) The DEP 256 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.70: DEP 256 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

88 A120 I/O 6

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

CERI Manual

Page 86

DEP 257 (16-point 110Vdc Discrete Input) Modicon Module ID: x0C (12), NRD Module ID: x2D (45) The DEP 257 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.71: DEP 257 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

DEP 296 (16-point 60Vdc Isolated Discrete Input) Modicon Module ID: x0C (12), NRD Module ID: x2E (46) The DEP 296 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.72: DEP 296 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

DEP 297 (16-point 48Vdc Isolated Discrete Input) Modicon Module ID: x0C (12), NRD Module ID: x2F (47) The DEP 297 only uses one 4x-register (In-0) for its 16 discrete inputs. Table 6.73: DEP 297 input register bit-map 4x Register Bit #

15 14 13 (MSB)

In-0 (Input #)

CERI Manual

1

2

3

12

11

10

9

8

7

6

5

4

3

2

1

4

5

6

7

8

9

10

11 12 13 14 15

0 (LSB) 16

6 A120 I/O 89

Page 87

MOT 201 (Motion Module) Modicon Module ID: x6E (110), NRD Module ID: x20 (32) The CERI uses the same 6 register in/out layout of the Compact PLC. Table 6.74: MOT 201 input register map 4x Register

Description

In-0

Status

In-1

Echo of command register

In-2

Data register 1

In-3

Data register 2

In-4

Data register 3

In-5

Data register 4

Table 6.75: MOT 201 output register map 4x Register

Description

Out-0

Control register

Out-1

Command register

Out-2

Data register 1

Out-3

Data register 2

Out-4

Data register 3

Out-5

Data register 4

MOT 202 (Motion Module) Modicon Module ID: x6F (111), NRD Module ID: x21 (33) The CERI uses the same 6 register in/out layout of the Compact PLC. Table 6.76: MOT 202 input register map 4x Register

Description

In-0

Status

In-1

Echo of command register

In-2

Data register 1

In-3

Data register 2

In-4

Data register 3

In-5

Data register 4

90 A120 I/O 6

CERI Manual

Page 88

Table 6.77: MOT 202 output register map 4x Register

Description

Out-0

Control register

Out-1

Command register

Out-2

Data register 1

Out-3

Data register 2

Out-4

Data register 3

Out-5

Data register 4

TST 999 (NR&D Test Module) Modicon Module ID: x7F (127), NRD Module ID: x35 (53) The TST 999 module uses 32 registers of input (IN-0 through IN-31) and 32 registers of output (OUT-0 through OUT-31).

UCM 001 (NR&D Communications Module) Modicon Module ID: x40 (64), NRD Module ID: x36 (54) The CUCM uses 32 registers of input (IN-0 through IN-31) and 32 registers of output (OUT-0 through OUT-31). The actual meaning of each register is dependent upon the user program loaded into the CUCM.

ZAE 201 (Counter/Position Module) Modicon Module ID: x60 (96), NRD Module ID: x1E (30) Table 6.78: ZAE 201 input register map 4x Register

Description

In-0

Status

In-1

Position or Count (high word)

In-2

Position or Count (low word)

CERI Manual

6 A120 I/O 91

Page 89

Table 6.79: ZAE 201 register map 4x Register

Description

Out-0

Command Word

Out-1

Target Position (high word)

Out-2

Target Position (low word)

Out-3

Parameter 1

Out-4

Parameter 2 (P1 high word)

Out-5

Parameter 3 (P1 low word)

Out-6

Parameter 4 (P2 high word)

Out-7

Parameter 5 (P2 low word)

Out-8

Parameter 6 (P3 high word)

Out-9

Parameter 7 (P3 low word)

92 A120 I/O 6

CERI Manual

Page 90

ZAE 204 (High Speed Counter) Modicon Module ID: x61 (97), NRD Module ID: x1F (31) Table 6.80: ZAE 204 input register map 4x Register In-0 (Status) (Bit-Map)

In-1 (Channel 4) (Error Code) (Decimal Value)

Description bit 15 (msb) = Comms Loss bit 14 = Module Unhealthy (wrong personality code read) bits 13,12 = Unused bit 11 = Channel 4 has exceeded the target count bit 10 = Channel 3 has exceeded the target count bit 9 = Channel 2 has exceeded the target count bit 8 = Channel 1 has exceeded the target count bit 7 = Channel 4 has reached the target count bit 6 = Channel 3 has reached the target count bit 5 = Channel 2 has reached the target count bit 4 = Channel 1 has reached the target count bit 3 = Channel 4 count gate input is 12-30V bit 2 = Channel 3 count gate input is 12-30V bit 1 = Channel 2 count gate input is 12-30V bit 0 (lsb) = Channel 1 count gate input is 12-30V 0 = No Error 1 = Differential and 10kHz requested on channel 1 2 = Differential and repetitive mode requested on channels 1 or 3 3 = 10kHz operation requested on channels 2, 3, or 4 4 = Mode change requested on channels 2 or 4 while channels 1 or 3 are set for differential operation 5 = Differential operation requested on channels 2 or 4 6 = Invalid target value has been specified

In-2

Channel 3 Error Code

In-3

Channel 2 Error Code

In-4

Channel 1 Error Code

In-5

Channel 4 Current Count

In-6

Channel 3 Current Count

In-7

Channel 2 Current Count

In-8

Channel 1 Current Count

CERI Manual

6 A120 I/O 93

Page 91

Table 6.81: ZAE 204 register map 4x Register

Description

Out-0 (Counter 1) (Mode Bit-Map)

bits 15-7 = unused bit 6 = Count direction (1=up) bit 5 = Active level for counter output channel (1=Active Low) bit 4 = Count enable config (1=High enable allows counting) bit 3 = Transition level for count (1=Negative edge) bit 2 = 10kHz operation (channel 1 only) (1=10kHz) bit 1 = Differential mode operation (channels 1 & 3 only) (1=Diff)

Out-1

Counter 1 Target Count

Out-2

Counter 2 Mode Bit-map

Out-3

Counter 2 Target Count

Out-4

Counter 3 Mode Bit-map

Out-5

Counter 3 Target Count

Out-6

Counter 4 Mode Bit-map

Out-7

Counter 4 Target Count

94 A120 I/O 6

CERI Manual