Page 14

2

Installation

Module Installation •

Mount the CERI in slots 1 and 2 of a Compact processor rack (DTA 200). The Compact PLC must be removed from this slot before the CERI is installed.

•

Tighten the mounting screw to ensure that the card will not accidentally be removed.

•

Move the power switch on the CERI to OFF.

•

Connect the 24Vdc power to the CERI removable green connector.

NOTE: It is advisable to configure the IP Address of the CERI before connecting the unit to the Ethernet network to avoid the possibility of a duplicate address with an existing Ethernet device. •

•

Move the CERI's power switch to ON. The LCD screen should light up and show the booting sequence. The IP Address will be displayed on the screen when the booting sequence is finished. If the IP Address does not conflict with any devices on the network then proceed to the next step, otherwise modify the address using the keys on the CERI front panel. •

Press the key to select Setup.

•

Press the key to select Communications.

•

Press the key to select Ethernet.

•

Press the key to select the IP Address.

•

Use the arrow keys to modify the IP Address. Press the the chosen address.

•

Use the same procedure to modify the Default Gate and Subnet Mask if needed.

•

Press the key to accept arrow to exit to the main screen.

Connect the Ethernet port of the CERI to a switch or hub with a standard CAT5 Ethernet cable. The LINK light should illuminate on the CERI and begin flashing as Ethernet data is received by the CERI. The 100MB light will illuminate if a

CERI Manual

15

Page 15

100MB connection is established with the switch. The CERI may be configured to operate at 10/100MB FD/HD. •

Configure the IP Address of a PC to match the same subnet of the CERI. Be careful to set the PC to an unused IP Address to avoid a conflict. For example, if the CERI is configured for 10.10.10.10 then set the PC to 10.10.10.11.

•

Ping the CERI to verify a good IP connection to the PC. Figure 2.1 shows a Command Prompt window in XP. Simply type ping followed by the target IP Address. If the target device replies then move to the next step.

Figure 2.1: Ping 10.10.10.10 • Point a Web Browser (IE, Firefox, Opera) at the IP Address of the CERI. The page will look something like Figure 2.2 although the exact layout of detected A120 modules (in gray) will depend on the installation. •

Proceed to Chapter 3 for more information about configuration.

16 Installation 2

CERI Manual

Page 16

Figure 2.2: Example Default Web Page

Software Installation The CERI_SETUP.EXE file includes this user manual, the ceri.fwl firmware file, the FWLOAD.EXE firmware loader utility, and the NRDTOOL.EXE register viewer utility. The latest version of this file is located at www.niobrara.com. Follow the link for “Download Area”, select “CERI”.

CERI Manual

2 Installation 17

Page 17

Power Supply The CERI operates on 24Vdc just like the Compact PLC. The removable power supply connector pinout is shown in Figure 2.3. The CERI includes an ON/OFF switch. This switch should be set to OFF when adding/removing A120 I/O cards to/from the rack(s). A green “Power” LED is on when the CERI is providing 5Vdc power to the A120 rack(s). A red “Overload” LED is on when the power load of the A120 rack(s) exceeds the rating of the CERI's power supply.

Figure 2.3 Power Connector Diagram 24Vdc (+)

24Vdc (-)

Frame GND

RS-232 Serial Port Port 1 of the CERI is a standard Compact CPU pinout RJ45 RS-232 port. The pinout is shown in Table 2.1: RJ45 RS-232 Pinout. The Niobrara MM1 cable is used to connect Port 1 of the CERI is to the a standard 9-pin serial port on a PC. This connection would rarely be used since all features of the CERI may be accessed through the Ethernet port. This port may be used to load firmware into the CERI if an Ethernet connection is unavailable. It also supports Modbus RTU communications at a default value of 9600,E,8,1. CERI firmware revisions 16Nov2010 or later support a unique data mailbox scheme to allow a serial Modbus master to interchange data with the new controlling CPU. This feature is extremely useful for applications with an existing Human Machine Interface (HMI) was serially connected to the old Compact CPU and now may be directly connected to the CERI. See Chapter 9 for more information. 18 Installation 2

CERI Manual

Page 18

Table 2.1: RJ45 RS-232 Pinout Pin

Function

1

+5Vdc

2

DSR (pulled high)

3

Data TX

4

Data RX

5

Signal GND

6

RTS

7

CTS

8

Chassis GND

Figure 2.4 Serial Port Diagram

TX LED

Pin 1

CERI Manual

RX LED

2 Installation 19

Page 19 read from a scan by OCR; it may hold reading errors

Figure 2.5.: MMI1 Serial Cable

CERI Connection 1

PC Serial Port Pin 1 oN Hn nH FBP W NY

0 WAN Dn BP W WN

20 Installation 2

CERI Manual

Page 20

Ethernet Port The CERI includes a standard RJ45 Ethernet port. The pinout is shown in Table 2.2: RJ45 Ethernet Pinout. Standard CAT5 cabling is used between the CERI and other Ethernet devices like a switch or hub. The green LINK LED will be on when a link is established and blinks off when data is arriving at the CERI. The CERI will automatically cross-over if needed. The amber 10/100 LED is on when the CERI is operating at 100Mbps. Table 2.2: RJ45 Ethernet Pinout Pin

Function

1

Transmit (+)

2

Transmit (-)

3

Receive (+)

4

Unused

5

Unused

6

Receive (-)

7

Unused

8

Unused

Figure 2.6 Ethernet Port Diagram Link LED

Pin 1

100Mbps LED

Updating the CERI Firmware NOTE: Loading the CERI firmware through the serial port is not recommended. Loading firmware through the CERI's Web server is many times faster and may be done remotely. (See page 31)

NOTE: Loading new firmware into the CERI may cause the unit to revert to factory defaults. Always perform a backup of the CERI's configuration through the Web server before preforming a firmware download. On occasion it may be necessary to update the operating system of the CERI. The FWLOAD program is used to install the CERI firmware through the RS-232 serial port. 1. Move the power switch on the CERI to OFF. 2. Hold down the key and then move the power switch to ON. The screen on the CERI will power up and eventually show “FIRMWARE LOADER”. CERI Manual

2 Installation 21

Page 21

3. Start FWLOAD.EXE. The Windows Start Menu link is “Start, Programs, Niobrara, CERI, FWLOAD CERI Firmware”. 4. Click on the Browse button and select CERI.FWL. 5. Ensure that the proper PC serial port is selected (COM1). 6. Connect the MM1 cable from the CERI port 1 to the selected PC serial port. 7. Press the “Start Download” button. FWLOAD will open a progress bar to show the status of the download. 8. Cycle power on the CERI to return the unit to normal operation. The module is ready for use. Figure 2.7: FWLOAD Screen

22 Installation 2