The text of a manual · part 4 of 15
CERI Installation and Programming Manual: 3 Web Server
Pages 22 to 34 of 122, from CERI Installation and Programming Manual
The original document is the PDF (1.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the AEG DEP-210
Page 22
3
Web Server
Main Page The CERI is configured using its built-in Web server. Simply enter the CERI's IP Address in a browser's URL and a page similar to Figure 3.1 should be displayed. Menu Links
Click Slot # to edit module. Gray background is unconfigured module.
Detected module may be one of several with same ID.
Figure 3.1: Example Main Web Page CERI Manual
23
Page 23
Login Selecting the “Configuration” link will lead to the “Configuration” page. When the “Configuration” page is first accessed on a new Web connection the user will be prompted for a user name and password as shown in Figure 3.2. The “User name” is ignored by the CERI. The word “master” is commonly used. The “Password” defaults to “master” and is case sensitive. This password may be changed through the Web interface.
Figure 3.2: Login
The “Configuration” link should show a page similar to Figure 3.3. This page gives an overview of the CERI. The “Communications” settings including the IP Address, Subnet Mask, Default Gateway, and Serial Port settings are shown. The “Control” Settings gives the list of Allowed Masters and the Communications Timeout. The “General” settings show the mode of operations and the target action on a mismatch of configuration. The “Rack Mapping” gives an overview of the A120 I/O layout. See Chapter 4 on page 37 for more information on the Rack Mapper. The “Internal Mapping” gives a listing of the internal map entries. See Chapter 5 on page 43 for more information on the Internal Mapper. 24 Web Server 3
CERI Manual
Page 24
(© NR&D CERI - Configuration - Windows Internet Explorer, Ge) > [bes http://206.223.51. 191/config ¥| |||} | [eae : Eile Edit View Favorites Tools Help 7, : = A » we he |N_ Rap CERI - Configuration | > BL” the Epeage - G Tools
Mode: Config
Main
Configuration Comms Control General Rack
Mapper Password Backup Restore Firmware update Reset
Statistics
NR&D CERI
Communications
IP: 206.223.51.191
Mask: 255.255.255.0
Gateway: 206.223.51.1
Serial port: Modbus RTU: 9600bps, even parity, 8 data bits, 1 stop bit
Click here to modify the communications settings
Control Settings
Allowed Master (1): N/A
Allowed Master (2): N/A
Allowed Master (3): N/A
Allowed Master (4): N/A Communications Timeout (ms): 1000
Click here to modify the control settings
General
The CERI is currently in Config mode. The CERI is configured to Halt in case of a configuration mismatch.
Click here to modify the general configuration
Rack Mapping
Rcpu3 4 5 Rio2 345 A A
Cc Cc
K CERI DEP DAP DAP K DAP DAP
1 209 2** 204 2 210 216
R ai123 45 ai2345 c |
“a vv
Figure 3.3: Configuration Web Page
CERI Manual
2 eg Internet 100% +
3 Web Server 25
Page 25
Comms Page A fixed IP Address may be entered through the “Comms” link. BOOTP and/or DHCP operation may also be enabled on this page. If either BOOTP or DHCP are enabled then the CERI will attempt to connect to a BOOTP or DHCP server on power-up and retrieve new IP settings. These new settings will override any fixed values until the next power cycle.
Figure 3.4: Comms Page These settings may also be edited through the front panel of the CERI. See Chapter 7 for more information.
26 Web Server 3
CERI Manual
Page 26
Control Page The “Control” page allows the editing of the IP Addresses of the four potential controlling masters of the CERI I/O. Any client may connect to the CERI via Modbus/TCP and read the state of the I/O but only clients listed in this table will be allowed the ability to write the outputs. The first client included in this table that sends a Modbus/TCP write to the CERI will be declared the “Controlling Master” and will have sole control of the outputs. This sole control is maintained until this master allows the “Timeout” to elapse without sending a write to the CERI. After the timeout expires, the CERI will allow any of the masters in the table to gain control.
Figure 3.5: Control Page CERI Manual
3 Web Server 27
Page 27
General Configuration Page The “General” page controls the operating mode of the CERI. The Run Mode has options of “Config”, “Run”, and “Halt”. •
Config – This mode allows the editing of the CERI's configuration while possibly having the I/O controlled by one of the Masters.
NOTE: Changing the configuration while the outputs are being controlled may result in a temporary loss of control of the outputs resulting in equipment damage, injury or death. •
Run – This mode does not allow changes to the CERI configuration. This is effectively a 'memory protect' setting for the CERI.
•
Halt – This mode forces all outputs to their default state. The CERI must be in Halt mode for a firmware upgrade.
Name Plate
Figure 3.6: General Page The “Action when configured card missing” determines the action the CERI will take when this event occurs. “Halt” will force the CERI into halt and all outputs to their default state. “Run Allowed” will cause the CERI to post an error but continue to allow the outputs to be remotely controlled. The “Name Plate” is displayed on the LCD and in the Title of the HTML pages. This value is limited to 16 characters of A-Z, 0-9, and _. All characters will be 28 Web Server 3
CERI Manual
Page 28
capitalized by the CERI. An empty Name Plate will result in the default of CERI to be displayed in the HTML title and front display.
Rack Page The Rack page is fully described in Chapter 4 on page 37.
Mapper Page The Mapper page is fully described in Chapter 5 on page 43.
Password Page The Update Password page allows the changing of the Web page password. This is not the same password used to control access to the front panel of the CERI.
Figure 3.7: Password Update Page
CERI Manual
3 Web Server 29
Page 29
Backup The Backup page allows the saving of the entire configuration of the CERI to a text file on the PC. Right-click the “here” link and select “Save Target As...” to save a copy of the file. The default filename is config_IPAddress.ceri.
Figure 3.8: Backup Page The structure of the backup file is simply the register number = value. Values with a leading “x” are in hexadecimal. Factory default values are not included in the backup file to keep the file size down.
Restore Page The Configuration Restore page simply prompts for the filename of the backup text file. The extension should be .ceri. After selecting the proper file, press “Start Download”. If the process is completed successfully the screen should look like Figure 3.9.
30 Web Server 3
CERI Manual
Page 30
Figure 3.9: Restore
Firmware The Firmware Upload page allows the easy upgrading of the CERI's firmware over the Ethernet. NOTE: The CERI must be in Halt to perform this upload.
NOTE: A backup of the CERI should be performed before the firmware update. The new update may cause the CERI to revert to factory defaults. Restoring the old backup will return the CERI to its proper settings.
CERI Manual
3 Web Server 31
Page 31
Figure 3.10: Firmware Page The firmware file is normally saved in c:\Niobrara\ceri\ceri.fwl.
Reset The Rest page will clear all mapper entries including the Rack and Internal mappers. It will also clear all default output values. It does not affect the configuration stored in Flash memory, only the current working configuration. To complete the reset, type “YES” in the box and press “Go”. NOTE: Reverting the CERI completely to factory defaults may be done through the front panel. See page 99.
32 Web Server 3
CERI Manual
Page 32
Figure 3.11: Reset Page
Statistics CERI Statistics The Statistics page gives a wealth of information about the CERI. This page is automatically refreshed every 30 seconds. The Firmware and Bootcode Revisions, serial number, MAC Address, scan time, IP Address of the current master, Ethernet and Serial port statistics, and per client statistics are all displayed.
CERI Manual
3 Web Server 33
Page 33
Figure 3.12: Statistics Page
Register Map The Register Map page gives a cross-reference of all Drop 0/1 registers in use. Source registers (outputs) are shown in black while destination registers (inputs) are shown in blue. Registers used in both the Rack and Internal mapping are shown.
34 Web Server 3
CERI Manual
Page 34
(© NR&D CERI - Register Usage Map - Windows Internet Explorer
= we
Nt, http://206.223.51.191/sta v +4||X |
: File Edit View Favorites
Tools
Help w we
CERI
N _ NR&D CERI - Register Usa...
|e el : f- & my ~ sp Page » (Of Tools ~
»>
NR&D CERI
CERI Register Usage Map
Mode: Halt
Register(s) Use 1 - 3000 Unused
3001 3002
Rack 1, Slot 3 (Dst) Rack 1, Slot 4 (Dst)
3003 - 4000 (Unused
4001 4002 4003 4004
Rack 1, Slot 4 (Src) Rack 1, Slot 5 (Src) Rack 2, Slot 1 (Src) Rack 2, Slot 2 (Src)
4005 - 10000 Unused
Ninhrara Recearch and NDNierrelanment
Copyright 2009
“a vv
(@ @ internet
100% +
Figure 3.13: Register List
CERI Manual
3 Web Server 35