The text of a manual · part 5 of 15
CERI Installation and Programming Manual: 4 Rack
Pages 35 to 39 of 122, from CERI Installation and Programming Manual
The original document is the PDF (1.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the AEG DEP-210
Page 35
4
Rack
Figure 4.1 shows the features of the Rack I/O Configuration Web page of the CERI. Click Slot # to edit module. Click Module ID to view status. Gray background is unconfigured module. Orange background is module Error. Click here to save setup.
Figure 4.1: Rack I/O Configuration Page
Red link indicates error condition.
This Web page is accessed by the Configuration>Rack links in the green column. The layout of the racks on the Web page is always 1-2/3-4 and may not bare resemblance to the actual physical layout of the A120 I/O. The CERI always displays all four racks, CERI Manual
37
Page 36
even if they don't physically exist. Unused slots should remain empty in the CERI's configuration. Detected A120 modules are displayed by name in their slot. If the module is configured in the CERI then this name will also be a link. If a module matches the ID configured in the CERI then the background will be white. If a module is properly configured but reporting a module error or the module ID doesn't match the configuration then the background will be orange. If a module is not yet configured then the background will be gray. Many A120 cards share the same module ID making it impossible for the CERI to accurately determine which card is present. The CERI will display the detected card name with “*” characters in the digits it is unable to uniquely define until the proper card is selected. Figure 4.2 shows an example of a detected module DAP 2*8. This card may be a DAP 208 or a DAP 258. Both cards share the same module ID and behave the same across the backplane.
Figure 4.2: Module Selection A slot is edited by simply clicking on the slot number of the appropriate rack. A page similar to Figure 4.3 will be shown. 38 Rack 4
CERI Manual
Page 37
Figure 4.3: Module Edit Page The First Input value determines where the 5 words of input are placed in the drop 0/1 register area. The First Output determines where the 2 words of output start. The ADU 206 includes a “Configure” button used to set up the analog inputs (Figure 4.4). In most cases that include a “Configure” button, most if not all of the output words assigned to that card are set through the Web page and do not need to be controlled from the Master. Recommended Practice: Niobrara recommends that analog input cards have their outputs mapped to registers not written by the controlling PLC master. These outputs are usually configured once through the CERI's web page and should not be written by the PLC.
CERI Manual
4 Rack 39
Page 38
Figure 4.4: Configure Page for ADU 206
Clicking on the Module ID on the Rack page will give a status page for that card (Figure 4.5). This page gives a summary about the configuration as well as the actual data reported by the card.
40 Rack 4
CERI Manual
Page 39
(© NR&D CERI - I/O status for Rack 2 Slot 3 - Windows Internet Explorer
Ge yr ihe http://206.223.51, 190/stats/slot?slot ¥| +4||X | Pi
: File Edit View Favorites Tools Help
I NR&D CERI -1/O status for Rack 2S... | : fi > GE) ~ mb ~ |=) Page ~ GQ Tools -
“a
NR&D CERI
Mode: Halt Status for Rack 2 Slot 3 Main Configuration V/O configuration for Rack 2 Slot 3 Statistics ADU206 4 Channel Register Input ADU 2*6 Module reporting Bad Problem Health Module Input Words 45
Module Output Words
Inputs Mapped to 4x (%MW) 3011 - 3015 Outputs Mappedto 4x (%MW) 4020 - 4021
Detected Module
2
Inputs
Register Meaning iia
3011 (Module Status 12289 3012 |Channel 1 Data 12290 3013 = | Channel 2 Data | 12291 3014 |Channel 3 Data 12292 3015 |Channel 4 Data 12293
Outputs
Register Meaning iba we
4020 Analog Config |0 3 4021 DataConfig 0 11
\¢
Done (4) @ internet 100% + Figure 4.5: Status Page for ADU 206
CERI Manual 4 Rack 41