CERI Installation and Programming Manual: 1 Introduction

Pages 11 to 13 of 122, from CERI Installation and Programming Manual

The original document is the PDF (1.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the AEG DEP-210

Page 11

1

Introduction

The Niobrara CERI is a Modicon Compact 984 compatible module that replaces the Compact PLC CPU to convert the A120 Series I/O into distributed Ethernet I/O capable of remote control using Modbus/TCP. The The CERI is a standard double-width module that resides in slots 1 and 2 of the processor rack (DTA 200). The full compliment of main rack and up to three expansion racks (DTA 201 and DTA 202) are supported by the CERI. The CERI includes a 2.5A power supply powered by 24VDC. Figure 1.1: Typical Configuration DAP 212

PLC

NOE

CERI DEP 209 N R & D

DAP 210

DAP 204

DAP 216

CERI

Ethernet Switch

Figure 1.1 shows a typical configuration where a CERI is installed in a Compact PLC rack with A120 I/O. The primary rack contains the CERI, DEP 209, DAP 212, DAP 204 while the two-slot secondary rack contains a DAP 210 and DAP 216. The CERI is connected to a standard Ethernet switch using a normal CAT5 cable. A Quantum PLC with its own NOE Ethernet card is also connected to the Ethernet switch. The CERI is configured to map its A120 I/O into a block of 4x Holding Registers. The Quantum PLC uses the I/O Scanner feature of its NOE to communicate with the CERI to read and write the 4x registers and thus control the remote I/O. The CERI's Web page is shown in Figure 1.2. CERI Manual

11

Page 12

CERI operation mode.

Click for Module Configuration. Click for Module Information.

Menu Tree

Figure 1.2: CERI Main Web Page The Main Web page of the CERI shows each of the four possible A120 racks. The CERI is installed in the CPU slots of Rack 1. Racks 2, 3, and 4 are always displayed on the CERI's Web pages, even if they are not physically present. The CERI Web page always displays the racks in the over/under 1-2/3-4 layout regardless of the actual physical rack layout. NOTE: Consult the Modicon 984-A120 Compact PLC User Guide (890 USE 108 00) for a complete listing of legal rack arrangements. Figure 1.3 shows the configuration page for the DAP 212. This module includes 8 discrete inputs that are mapped to 4x register 3102 and four discrete outputs mapped to 4x register 4101. The I/O Scanner in the Quantum would simply read register 3102 from the CERI (Modbus/TCP Index 0) to gather the input values and write register 4101 to set the outputs for this car

12 Introduction 1

CERI Manual

Page 13

Figure 1.3: DAP212 Config Web Page NOTE: Many A120 cards share the same Module ID so the CERI is unable to uniquely identify certain modules.

CERI Manual

1 Introduction 13