The text of a manual · part 2 of 4
Overview of the DEP 216/256 Input Module: Overview of the DEP 217 Input Module
Pages 7 to 12 of 24, from Overview of the DEP 216/256 Input Module
The original document is the PDF (312 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AEG DEP-216
Page 7
Overview of the DEP 217 Input Module
At a Glance Purpose
The purpose of this chapter is to describe the DEP 217 input module.
What’s in this Chapter?
This chapter contains the following topics:
890 USE 109 00 March 2003
Topic
Page
What is the DEP 217 Input Module?
438
DEP 217 Input Module LEDs
439
DEP 217 Input Module Field Wiring
440
DEP 217 Input Module Specifications
441
437
Page 8
DEP 217 Input Module
What is the DEP 217 Input Module? Brief Product Description
Note: Some A120 I/O modules (DEP 211/214/215/217, DAP211/217, ADU204/ 211/214/216, DAU204, VIC2xx, and MOT20x) require a loadable (SW-IODR-001) for proper operation when using certain PLCs (A984-1xx, E984-24x/251/255) with Modsoft. The DEP 217 is a 24 Vdc, 16-point discrete true low input module. It senses levels provided by field devices such as pushbuttons, limit and proximity switches, or other 24 Vdc input sources and converts those signals into logic voltage levels that can be used by the PLC. Signals are field wired in two groups, eight signals/group. Inputs are opto-isolated from the system bus. Note: The DEP 217 is a true low module; therefore, a high (greater than or equal to external source minus 6Vdc) is read by the PLC as a logic 0. Conversely, a low (less than or equal to external source minus 12Vdc) is read by the PLC as a logic 1.
438
890 USE 109 00 March 2003
Page 9
DEP 217 Input Module
DEP 217 Input Module LEDs LEDs
890 USE 109 00 March 2003
The DEP 217 module has two green LEDs, opposite terminal screws 1 and 12. When one of these LEDs is ON, it indicates that power is available to the group directly below it. The module also has 16 red LEDs, eight opposite terminal screws 3 ... 10 and eight opposite terminal screws 14 ... 21; when any one of these LEDs are ON, it indicates 3 external source minus 12 V at the corresponding input.
439
Page 10
DEP 217 Input Module
DEP 217 Input Module Field Wiring Introduction
The DEP 217 is a 24 Vdc, 16-point discrete true low input module. It senses levels provided by field devices such as pushbuttons, limit and proximity switches, or other 24 Vdc input sources and converts those signals into logic voltage levels that can be used by the PLC. Signals are field wired in two groups, eight signals/group. Inputs are opto-isolated from the system bus. Note: The DEP 217 is a true low module; therefore, a high (greater than or equal to external source minus 6Vdc) is read by the PLC as a logic 0. Conversely, a low (less than or equal to external source minus 12Vdc) is read by the PLC as a logic 1.
Wiring Diagram and Simplified Schematic for DEP 217
A wiring diagram and simplified schematic for the DEP 217 input module is provided below.
24 Vdc 24 V Common
Red
0.16 A
In1 In2 In3 In4 In5 In6 In7 In8
In9 In10 In11 In12 In13 In14 In15 In16
440
I/O Bus Interface
First of 16 Input Circuits 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
5V
Green GND
890 USE 109 00 March 2003
Page 11
DEP 217 Input Module
DEP 217 Input Module Specifications Table of Specifications for DEP 217
The following table contains DEP 217 input module specifications. Module Topology
Number of Inputs
16
Number of Groups
2
Points/group
8
Isolation
Optocoupler on each input
Required Loadable SW-IODR-001 (See Requirements for CE Compliance, p. 779) Power Supplies
External Source Requirement
24 Vdc for eight inputs
Rated Signal Value
Sinking device
Internally Provided Source from 5 V; 25 mA I/O bus
Electrical Characteristics
Internal Power Dissipation
3 W typical
False Condition Signal Level greater than or equal to external source minus 6 Vdc
True Condition Signal Level less than or equal to external source minus 12 Vdc
True Condition Input Current
7 mA @ 0 Vdc
Response Time
4 ms typical
Operating Mode Wire Size/ terminal
True Low One wire
14 AWG
Two wires
20 AWG
I/O Map
Discrete 1x/0x
16 in/0 out
Dimensions
WxHxD
40.3 x 145 x 117.5 mm 1.6 x 5.6 x 4.5 in
Weight
220 g 0.5 lb.
Agency Approvals
890 USE 109 00 March 2003
VDE 0160; UL 508; and CSA 22.2 No.142 Standards
441
Page 12
DEP 217 Input Module
442
890 USE 109 00 March 2003