For the AEG DEP-216

Page 13

Overview of the DEP 218 Input Module

At a Glance Purpose

The purpose of this chapter is to describe the DEP 218 input module.

What’s in this Chapter?

This chapter contains the following topics:

890 USE 109 00 March 2003

Topic

Page

What is the DEP 218 Input Module?

444

DEP 218 Input Module LEDs

445

DEP 218 Input Module Field Wiring

446

DEP 218 Input Module Specifications

448

443

Page 14

DEP 218 Input Module

What is the DEP 218 Input Module? Brief Product Description

WARNING Operational Hazard The DEP 218 module will only operate properly when used with an A984, E984, or Micro 512/612 controller. Failure to follow this precaution can result in death, serious injury, or equipment damage. The DEP 218 is a 115 Vac, 16-point input module with 1.8kV isolation between field devices and the bus. It senses input signals received from field sensing devices such as pushbuttons, limit and proximity switches, or other 115 Vac input sources and converts those signals into logic voltage levels that can be used by the controller. Signals are field wired in two groups, eight signals/group. Inputs are optoisolated from the system bus. Note: The DEP 218 is designed for capacitive loads. Without any discharge bypass resistor. When using field devices with resistive loads you should use 120K 1/4 Watt resistors (approximately) across the input terminals of the DEP 218. This allows accurate switching of phase firing type solid state sensors by ensuring that the capacitor discharges within the sensor required 50 milliseconds. If your application permits, a DEP 210 may be substituted for the DEP 218. The DEP 210 has an internal input discharge circuit.

444

890 USE 109 00 March 2003

Page 15

DEP 218 Input Module

DEP 218 Input Module LEDs LEDs

The DEP 218 module has one green LED opposite terminal screw 1. When this LED is ON, it indicates the presence of working voltage from the power supply. The module also has 16 red LEDs, eight opposite terminal screws 3 ... 10 and eight opposite terminal screws 14 ... 21; when any one of these LEDs is ON, it indicates voltage present at the corresponding input. A front view and fill-in labels of the DEP 218 module is provided below.

DEP 218 DEP 218 1 ready N

2

N

3

1

4

2

5

3

6

4

7

5

8

6

9

7

10

8

11 N

12

N

13

9

14

10

15

11

16

12

17 18 19 20 21

22

13 14 15 16 card

890 USE 109 00 March 2003

445

Page 16

DEP 218 Input Module

DEP 218 Input Module Field Wiring Wiring Diagram for DEP 218

A sample wiring diagram for the DEP 218 input module is provided below. ac Neutral ac Hot ac Hot ac Neutral 0.16 A

0.16 A 1 2 Input 1

3

Input 2

4

Input 3

5

Input 4

6

Input 5

7

Input 6

8

Input 7

9

Input 8

10 11 12

Input 9 Input 10 Input 11 Input 12 Input 13 Input 14

446

13 14 15 16 17 18 19

Input 15

20

Input 16

21 22

890 USE 109 00 March 2003

Page 17

DEP 218 Input Module

Simplified Schematic for DEP 218

A simplified schematic for the DEP 218 input module is provided below.

ac Neutral

1

FIRST OF 16 INPUT CIRCUITS

2 3 4 5

Red PAB

6 7 8 9 10 11 5V 12 13

Green

14 0V 15 16 17 18 19 20 21 22

890 USE 109 00 March 2003

447

Page 18

DEP 218 Input Module

DEP 218 Input Module Specifications Table of Specifications for DEP 218

The following table contains DEP 218 input module specifications. Module Topology

Number of Inputs

16

Number of Groups

2

Points/group

8

Isolation

Optocoupler on each input point, 1.8 kV field-to-bus

Power Supplies External Source Requirement Rated Signal Value

115 Vac 115 Vac 47 ... 65 Hz

Internally Provided Source from the I/O bus 5 V, less tghan 50 mA

Electrical Characteristics

Internal Power Dissipation

3 W typical

ON State Signal Level

80 ... 132 Vac

OFF State Signal Level

0 ... 35 Vac

ON State Input Current

15.5 mA/input @ 115 Vac

OFF State Input Current

3 mA maximum

Response Time

ON

10 ms typical

OFF

40 ms typical

One wire

14 AWG

Two wires

20 AWG

6 mA @ 80 V, 20 mA @ 132 V

Operating Mode Wire Size/ terminal

I/O Map

Discrete 1x/0x

Dimensions

WxHxD

True High

16 in/0 out 40.3 x 145 x 117.5 mm 1.6 x 5.6 x 4.5 in

Weight

300 g 0.66 lb

Agency Approvals

448

VDE 0160; UL 508; and CSA 22.2 No.142 Standards