Page 13
Overview of the DEP 218 Input Module
At a Glance Purpose
The purpose of this chapter is to describe the DEP 218 input module.
What’s in this Chapter?
This chapter contains the following topics:
890 USE 109 00 March 2003
Topic
Page
What is the DEP 218 Input Module?
444
DEP 218 Input Module LEDs
445
DEP 218 Input Module Field Wiring
446
DEP 218 Input Module Specifications
448
443
Page 14
DEP 218 Input Module
What is the DEP 218 Input Module? Brief Product Description
WARNING Operational Hazard The DEP 218 module will only operate properly when used with an A984, E984, or Micro 512/612 controller. Failure to follow this precaution can result in death, serious injury, or equipment damage. The DEP 218 is a 115 Vac, 16-point input module with 1.8kV isolation between field devices and the bus. It senses input signals received from field sensing devices such as pushbuttons, limit and proximity switches, or other 115 Vac input sources and converts those signals into logic voltage levels that can be used by the controller. Signals are field wired in two groups, eight signals/group. Inputs are optoisolated from the system bus. Note: The DEP 218 is designed for capacitive loads. Without any discharge bypass resistor. When using field devices with resistive loads you should use 120K 1/4 Watt resistors (approximately) across the input terminals of the DEP 218. This allows accurate switching of phase firing type solid state sensors by ensuring that the capacitor discharges within the sensor required 50 milliseconds. If your application permits, a DEP 210 may be substituted for the DEP 218. The DEP 210 has an internal input discharge circuit.
444
890 USE 109 00 March 2003
Page 15
DEP 218 Input Module
DEP 218 Input Module LEDs LEDs
The DEP 218 module has one green LED opposite terminal screw 1. When this LED is ON, it indicates the presence of working voltage from the power supply. The module also has 16 red LEDs, eight opposite terminal screws 3 ... 10 and eight opposite terminal screws 14 ... 21; when any one of these LEDs is ON, it indicates voltage present at the corresponding input. A front view and fill-in labels of the DEP 218 module is provided below.
DEP 218 DEP 218 1 ready N
2
N
3
1
4
2
5
3
6
4
7
5
8
6
9
7
10
8
11 N
12
N
13
9
14
10
15
11
16
12
17 18 19 20 21
22
13 14 15 16 card
890 USE 109 00 March 2003
445
Page 16
DEP 218 Input Module
DEP 218 Input Module Field Wiring Wiring Diagram for DEP 218
A sample wiring diagram for the DEP 218 input module is provided below. ac Neutral ac Hot ac Hot ac Neutral 0.16 A
0.16 A 1 2 Input 1
3
Input 2
4
Input 3
5
Input 4
6
Input 5
7
Input 6
8
Input 7
9
Input 8
10 11 12
Input 9 Input 10 Input 11 Input 12 Input 13 Input 14
446
13 14 15 16 17 18 19
Input 15
20
Input 16
21 22
890 USE 109 00 March 2003
Page 17
DEP 218 Input Module
Simplified Schematic for DEP 218
A simplified schematic for the DEP 218 input module is provided below.
ac Neutral
1
FIRST OF 16 INPUT CIRCUITS
2 3 4 5
Red PAB
6 7 8 9 10 11 5V 12 13
Green
14 0V 15 16 17 18 19 20 21 22
890 USE 109 00 March 2003
447
Page 18
DEP 218 Input Module
DEP 218 Input Module Specifications Table of Specifications for DEP 218
The following table contains DEP 218 input module specifications. Module Topology
Number of Inputs
16
Number of Groups
2
Points/group
8
Isolation
Optocoupler on each input point, 1.8 kV field-to-bus
Power Supplies External Source Requirement Rated Signal Value
115 Vac 115 Vac 47 ... 65 Hz
Internally Provided Source from the I/O bus 5 V, less tghan 50 mA
Electrical Characteristics
Internal Power Dissipation
3 W typical
ON State Signal Level
80 ... 132 Vac
OFF State Signal Level
0 ... 35 Vac
ON State Input Current
15.5 mA/input @ 115 Vac
OFF State Input Current
3 mA maximum
Response Time
ON
10 ms typical
OFF
40 ms typical
One wire
14 AWG
Two wires
20 AWG
6 mA @ 80 V, 20 mA @ 132 V
Operating Mode Wire Size/ terminal
I/O Map
Discrete 1x/0x
Dimensions
WxHxD
True High
16 in/0 out 40.3 x 145 x 117.5 mm 1.6 x 5.6 x 4.5 in
Weight
300 g 0.66 lb
Agency Approvals
448
VDE 0160; UL 508; and CSA 22.2 No.142 Standards
890 USE 109 00 March 2003