Page 19

Overview of the DEP 220 Input Module

At a Glance Purpose

The purpose of this chapter is to describe the DEP 220 input module.

What’s in this Chapter?

This chapter contains the following topics:

890 USE 109 00 March 2003

Topic

Page

What is the DEP 220 Input Module?

450

DEP 220 Input Module LEDs

451

DEP 220 Input Module Field Wiring

452

DEP 220 Input Module Specifications

454

449

Page 20

DEP 220 Input Module

What is the DEP 220 Input Module? Brief Product Description

The DEP 220 is a 24 Vdc +25 percent/-15 percent, 16-point discrete input module similar to the DEP 216 module, with a much faster response time (0.5 ms). It senses input signals received from field sensing devices such as pushbuttons, limit and proximity switches, or other 24 Vdc input sources and converts those signals into logic voltage levels that can be used by the PLC. Signals are field wired in two groups, eight signals per group. Inputs are opt-isolated from the system bus. CAUTION Operational Hazard Modicon recommends using two separate power sources with the DEP 220-one for outputs and one for inputs-in order to avoid electrical switching noise. Failure to follow this precaution can result in injury or equipment damage.

Note: Inputs do not work if output supply is disconnected.

450

890 USE 109 00 March 2003

Page 21

DEP 220 Input Module

DEP 220 Input Module LEDs LEDs

890 USE 109 00 March 2003

The DEP 220 module has two green LEDs, opposite terminal screws 1 and 12. When one of these LEDs is ON, it indicates that power available to the eight inputs directly below it. The module also has 16 red LEDs, eight opposite terminal screws 3 ... 10 and eight opposite terminal screws 14 ... 21; when any one of these LEDs are ON, it indicates voltage present at the corresponding input.

451

Page 22

DEP 220 Input Module

DEP 220 Input Module Field Wiring Introduction

The DEP 220 is a 24 Vdc +25 percent/-15 percent, 16-point discrete input module similar to the DEP 216 module, with a much faster response time (0.5 ms). It senses input signals received from field sensing devices such as pushbuttons, limit and proximity switches, or other 24 Vdc input sources and converts those signals into logic voltage levels that can be used by the PLC. Signals are field wired in two groups, eight signals per group. Inputs are opto-isolated from the system bus. CAUTION Operational Hazard Modicon recommends using two separate power sources with the DEP 220-one for outputs and one for inputs-in order to avoid electrical switching noise. Failure to follow this precaution can result in injury or equipment damage.

Note: Inputs do not work if output supply is disconnected.

452

890 USE 109 00 March 2003

Page 23

DEP 220 Input Module

Wiring Diagram and Simplified Schematic

A sample wiring diagram and simplified schematic for the DEP 220 input module is provided below.

24 Vdc 24 V Common Green

0.16 A

In1 In2 In3 In4 In5 In6 In7 In8

In9 In10 In 11 In12 In 13 In14 In15 In16

890 USE 109 00 March 2003

I/O Bus Interface

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

5V

Red Opto Coupler First of 16 Input Circuits

GND

453

Page 24

DEP 220 Input Module

DEP 220 Input Module Specifications Table of Specifications

The following table contains DEP 220 input module specifications. Module Topology

Number of Inputs

16

Number of Groups

2

Points/group

8

Isolation

Optocoupler on each input

Power Supplies External Source Requirement Rated Signal Value

20 ... 30 Vdc for eight inputs +24 Vdc

Internally Provided Source from the I/O bus 5 V; less than 25 mA Internal Power Dissipation Electrical Characteristics

2 W typical

ON State Signal Level

12 ... 30 Vdc

OFF State Signal Level

-2 ... +5 Vdc

ON State Input Current

7 mA @ 24 Vdc 8.5 mA @ 30 Vdc

Response Time

0.5 ms typical

Operating Mode

True High

Wire Size/terminal

One wire

14 AWG

Two wires

20 AWG

I/O Map

Discrete 1x/0x

16 in/0 out

Dimensions

WxHxD

40.3 x 145 x 117.5 mm

Weight

220 g

1.6 x 5.6 x 4.5 in

0.5 lb Agency Approvals

454

VDE 0160; UL 508; and CSA 22.2 No.142 Standards

890 USE 109 00 March 2003