The text of a manual · part 4 of 4
Overview of the DEP 216/256 Input Module: Overview of the DEP 220 Input Module
Pages 19 to 24 of 24, from Overview of the DEP 216/256 Input Module
The original document is the PDF (312 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AEG DEP-216
Page 19
Overview of the DEP 220 Input Module
At a Glance Purpose
The purpose of this chapter is to describe the DEP 220 input module.
What’s in this Chapter?
This chapter contains the following topics:
890 USE 109 00 March 2003
Topic
Page
What is the DEP 220 Input Module?
450
DEP 220 Input Module LEDs
451
DEP 220 Input Module Field Wiring
452
DEP 220 Input Module Specifications
454
449
Page 20
DEP 220 Input Module
What is the DEP 220 Input Module? Brief Product Description
The DEP 220 is a 24 Vdc +25 percent/-15 percent, 16-point discrete input module similar to the DEP 216 module, with a much faster response time (0.5 ms). It senses input signals received from field sensing devices such as pushbuttons, limit and proximity switches, or other 24 Vdc input sources and converts those signals into logic voltage levels that can be used by the PLC. Signals are field wired in two groups, eight signals per group. Inputs are opt-isolated from the system bus. CAUTION Operational Hazard Modicon recommends using two separate power sources with the DEP 220-one for outputs and one for inputs-in order to avoid electrical switching noise. Failure to follow this precaution can result in injury or equipment damage.
Note: Inputs do not work if output supply is disconnected.
450
890 USE 109 00 March 2003
Page 21
DEP 220 Input Module
DEP 220 Input Module LEDs LEDs
890 USE 109 00 March 2003
The DEP 220 module has two green LEDs, opposite terminal screws 1 and 12. When one of these LEDs is ON, it indicates that power available to the eight inputs directly below it. The module also has 16 red LEDs, eight opposite terminal screws 3 ... 10 and eight opposite terminal screws 14 ... 21; when any one of these LEDs are ON, it indicates voltage present at the corresponding input.
451
Page 22
DEP 220 Input Module
DEP 220 Input Module Field Wiring Introduction
The DEP 220 is a 24 Vdc +25 percent/-15 percent, 16-point discrete input module similar to the DEP 216 module, with a much faster response time (0.5 ms). It senses input signals received from field sensing devices such as pushbuttons, limit and proximity switches, or other 24 Vdc input sources and converts those signals into logic voltage levels that can be used by the PLC. Signals are field wired in two groups, eight signals per group. Inputs are opto-isolated from the system bus. CAUTION Operational Hazard Modicon recommends using two separate power sources with the DEP 220-one for outputs and one for inputs-in order to avoid electrical switching noise. Failure to follow this precaution can result in injury or equipment damage.
Note: Inputs do not work if output supply is disconnected.
452
890 USE 109 00 March 2003
Page 23
DEP 220 Input Module
Wiring Diagram and Simplified Schematic
A sample wiring diagram and simplified schematic for the DEP 220 input module is provided below.
24 Vdc 24 V Common Green
0.16 A
In1 In2 In3 In4 In5 In6 In7 In8
In9 In10 In 11 In12 In 13 In14 In15 In16
890 USE 109 00 March 2003
I/O Bus Interface
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
5V
Red Opto Coupler First of 16 Input Circuits
GND
453
Page 24
DEP 220 Input Module
DEP 220 Input Module Specifications Table of Specifications
The following table contains DEP 220 input module specifications. Module Topology
Number of Inputs
16
Number of Groups
2
Points/group
8
Isolation
Optocoupler on each input
Power Supplies External Source Requirement Rated Signal Value
20 ... 30 Vdc for eight inputs +24 Vdc
Internally Provided Source from the I/O bus 5 V; less than 25 mA Internal Power Dissipation Electrical Characteristics
2 W typical
ON State Signal Level
12 ... 30 Vdc
OFF State Signal Level
-2 ... +5 Vdc
ON State Input Current
7 mA @ 24 Vdc 8.5 mA @ 30 Vdc
Response Time
0.5 ms typical
Operating Mode
True High
Wire Size/terminal
One wire
14 AWG
Two wires
20 AWG
I/O Map
Discrete 1x/0x
16 in/0 out
Dimensions
WxHxD
40.3 x 145 x 117.5 mm
Weight
220 g
1.6 x 5.6 x 4.5 in
0.5 lb Agency Approvals
454
VDE 0160; UL 508; and CSA 22.2 No.142 Standards
890 USE 109 00 March 2003