Manual · AEG
Overview of the DEP 216/256 Input Module
Manual24 pagesPDF 312 KB
Chapters describing the A120 DEP 216/256, DEP 217, DEP 218 and DEP 220 16-point discrete input modules: LEDs, wiring and specifications.
Names · 1 model
The models it names
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Four chapters taken from a larger A120 I/O manual, each describing one 16-point discrete input module: the DEP 216/256 (24 Vdc), the DEP 217 (24 Vdc true low), the DEP 218 (115 Vac) and the DEP 220 (fast 24 Vdc). Each chapter gives a product description, what the LEDs show, field wiring with a simplified schematic, and a specification table with signal levels, response time, wire size, temperature, dimensions, weight and agency approvals.
Its parts
- Overview of the DEP 216/256 Input Module
- Overview of the DEP 217 Input Module
- Overview of the DEP 218 Input Module
- Overview of the DEP 220 Input Module
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Four chapters from a Modicon A120 I/O manual (890 USE 109 00, March 2003) covering the DEP 216/256, DEP 217, DEP 218 and DEP 220 discrete input modules. For each module it explains what it does, what the LEDs show, how to wire it, and its specifications.
- Module type
- DEP 216: 24 Vdc, 16-point discrete input module, two groups of eight, opto-isolated p. 2
- Signal levels
- DEP 216: ON 12 ... 30 Vdc, OFF -2 ... +5 Vdc, true high p. 5
- Input current
- DEP 216: 7 mA @ 24 Vdc, 8.5 mA @ 30 Vdc p. 5
- Response time
- DEP 216: 4 ms typical p. 5
- Operating temperature
- DEP 216: 0 ... 60 degrees C; DEP 256: -40 ... +70 degrees C p. 5
- Field supply
- DEP 216: 24 Vdc for each group of eight inputs, +25 percent/-15 percent p. 5
- Dimensions
- 40.3 x 145 x 117.5 mm (1.6 x 5.6 x 4.5 in), all four modules p. 5, 11, 18, 24
- Weight
- DEP 216, DEP 217, DEP 220: 220 g; DEP 218: 300 g p. 5, 11, 18, 24
- Wire size
- 14 AWG with one wire per terminal, 20 AWG with two p. 5
- Bus supply
- DEP 216: 5 V, 15 mA from the I/O bus; 2 W typical dissipation p. 5
- DEP 256
- DEP 256: same as DEP 216 at extended temperature; DEP 256C is conformal coated and meets EN 50 155 p. 2
- DEP 217
- DEP 217: 24 Vdc, 16-point true low (sinking) input module p. 8, 11
- DEP 218
- DEP 218: 115 Vac, 16 inputs, ON 80 ... 132 Vac, 1.8 kV field-to-bus isolation p. 14, 18
- DEP 220
- DEP 220: like the DEP 216 with 0.5 ms typical response p. 20, 24
What this manual walks you through
- What the DEP 216/256 input module does p. 2
- Reading the DEP 216/256 LEDs p. 3
- Wiring the DEP 216/256 p. 4
- DEP 216/256 specifications p. 5
- How the DEP 217 true low inputs are read p. 8, 10
- Wiring the DEP 217 and its specifications p. 10, 11
- Wiring the DEP 218 for 115 Vac inputs p. 14, 15, 16, 17
- DEP 218 specifications p. 18
- Powering and wiring the DEP 220 p. 20, 23
- DEP 220 specifications p. 24
Good to know
- The DEP 218 operates properly only with an A984, E984, or Micro 512/612 controller. p. 14
- The DEP 218 is designed for capacitive loads; with resistive field devices, fit about 120K 1/4 Watt resistors across its inputs. p. 14
- Use separate power sources for outputs and inputs with the DEP 220; its inputs do not work if the output supply is disconnected. p. 20
- The DEP 217 needs the loadable SW-IODR-001 with some PLCs (A984-1xx, E984-24x/251/255) under Modsoft. p. 8
Questions this manual answers
What voltage does the DEP 216 input module use?
It is a 24 Vdc, 16-point discrete input module, wired in two groups of eight inputs. p. 2
What is the difference between the DEP 216 and the DEP 256?
The DEP 256 works like the DEP 216 but at extended temperature, -40 to +70 degrees C instead of 0 to 60 degrees C. p. 2, 5
What is the difference between the DEP 216 and the DEP 220?
The DEP 220 is similar but responds in 0.5 ms typical, against 4 ms for the DEP 216. p. 5, 20
What do the LEDs on the DEP 216 show?
Two green LEDs show power to each group of eight inputs; 16 red LEDs show voltage at each input. p. 3
How does the DEP 217 read its inputs?
It is true low: a level no more than 6 Vdc below the external source is read as logic 0, and a level at least 12 Vdc below it as logic 1. p. 8
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 4 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.